Eaton PDI Universal User manual

p/n: P-164001105
Revision 01
WaveStar®Static Transfer Switches
Power Distribution nits
PowerPak
PowerPak 2
PowerHub 2
WaveStar®Primary Systems
WaveStar®Secondary Systems
Installation Manual
Eaton®PDI Universal Floor Stands

Eaton reserves the right to change specifications without prior notice. Eaton is a registered trademark of Eaton. PDI, JCOMM, Quad-Wye,
ToughRail Technology, and WaveStar are registered trademarks of Power Distribution Inc. All other trademarks are held by their
respective owners. All other trademarks are property of their respective companies.
©Copyright 2023 Eaton, Raleigh, NC, SA. All rights reserved. No part of this document may be reproduced in any way without the
express written approval of Eaton.
Thank you for your recent purchase of an Eaton PDI Universal Floor Stands.
For any questions regarding the installation, operation, service or maintenance
Please call the Eaton Help Desk at
United States 1-800-843-9433 or 1-919-870-3028
Canada 1-800-461-9166 ext 260
All other countries Call your local service representative
Please use the following e-mail for manual comments, suggestions, or to report a technical error in
this manual.
You can download the most recent version of this product manual from the Eaton web site’s Product
page, Resources section
https //www.eaton.com/us/en-us/catalog/low-voltage-power-distribution-controls-systems/eaton-pdi-
busway.resources.html
Eaton Universal Floor Stands
Installation Manual
Cover Photo Eaton Universal Floor Stands
NOTE The term PDI in this manual refers to products previous manufactured by
Power Distribution, Inc. All service and support for these features are now
supplied by Eaton.

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 iii
TTaabbllee ooff CCoonntteennttss
11 SSaaffeettyy......................................................................................................................................................................................................................................................................................................................11
22 FFlloooorr SSttaannddss bbyy PPrroodduucctt..................................................................................................................................................................................................................................................................33
2.1 Overview..................................................................................................................................................3
2.2 PowerHub 2 PDU .......................................................................................................................................4
2.3 PowerPak PDU ..........................................................................................................................................8
2.4 PowerPak 2 PDU...................................................................................................................................... 10
2.5 WaveStar® TFA/Static Transfer Switch ......................................................................................................... 13
2.6 WaveStar® Static Transfer Switch ............................................................................................................... 16
2.7 WaveStar® Primary System ....................................................................................................................... 22
2.8 WaveStar® Secondary System.................................................................................................................... 23
33 IInnssttaalllliinngg aa FFlloooorr SSttaanndd ................................................................................................................................................................................................................................................................ 2277
44 AAsssseemmbblliinngg aa FFlloooorr SSttaanndd.......................................................................................................................................................................................................................................................... 2299
4.1 Assembling the Floor Stands....................................................................................................................... 29
4.2 Assembling Compound Floor Stands ............................................................................................................ 31

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 v
iisstt ooff FFiigguurreess
Figure 1. PowerHub 2 PDU Floor Stand 60"H x 40"D........................................................................................... 5
Figure 2. PowerHub 2 PDU Floor Stand 60"W x 54"D..........................................................................................6
Figure 3. PowerHub 2 PDU Floor Stand 86"W x 54"D..........................................................................................7
Figure 4. PowerPak PDU Floor Stand 34.75"W x 32.5"D ......................................................................................9
Figure 5. PowerPak 2 PDU Floor Stand 42"W x 40"D ........................................................................................ 11
Figure 6. PowerPak 2EX PDU Floor Stand 54"W x 40"D..................................................................................... 12
Figure 7. TFA/STS Floor Stand 50"W x 36"D.................................................................................................... 14
Figure 8. TFA/STS Floor Stand 60"W x 36"D.................................................................................................... 15
Figure 9. WaveStar STS (≤ 600A) Floor Stand 34.75"W x 32.5"D.......................................................................... 18
Figure 10. WaveStar STS Floor Stand (800A) 45.75"W x 32.5"D ............................................................................ 19
Figure 11. WaveStar STS (1000-1200A) Floor Stand 82.5"W x 43"D ....................................................................... 20
Figure 12. WaveStar STS (1600A) Floor Stand 87.75"W x 43"D ............................................................................. 21
Figure 13. Primary System Floor Stand, PDU ≤ 300 kVA, STS ≤ 600A .................................................................... 24
Figure 14. Secondary System, PDU ≤ 300 kVA and (2) STS ≤ 600A ....................................................................... 25
Figure 15. Secondary System, PDU 288 kVA, (2) STS 800A ................................................................................. 26
Figure 16. Floor Stand Feet — Details ............................................................................................................. 27

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 vii
iisstt ooff TTaabblleess
Table 1. PowerHub 2 PDU Floor Stand Options - 60" W x 40" D............................................................................. 4
Table 2. PowerHub 2 PDU Floor Stand Options - 60" W x 54" D (for 56" Deep PDU Cabinet) ........................................4
Table 3. PowerHub 2 PDU Floor Stand Options - 86" W x 54" D (for 56" Deep PDU Cabinet) ........................................5
Table 4. PowerPak PDU Floor Stand Options .................................................................................................... 8
Table 5. PowerPak PDU Floor Stand Options - Manual Dual .................................................................................8
Table 6. PowerPak 2 PDU Floor Stand Options - 42" W x 40" D ........................................................................... 10
Table 7. PowerPak 2 PDU Floor Stand Options - 54" W x 40" D ........................................................................... 10
Table 8. WaveStar TFA/STS Floor Stand Options - 50" x 36" - 250A-600A .............................................................. 13
Table 9. WaveStar TFA STS Floor Stand Options - 60" x 36" - 800A-1200A ............................................................. 13
Table 10. WaveStar STS Floor Stand Options - 150A-600A .................................................................................. 16
Table 11. WaveStar STS Floor Stand Options - 800A .......................................................................................... 16
Table 12. WaveStar STS Floor Stand Options - 1000A & 1200A ............................................................................ 17
Table 13. WaveStar STS Floor Stand Options - 1600A ........................................................................................ 17
Table 14. WaveStar Primary System (1) PowerPak PDU (≤ 300kVA) and (1) WaveStar STS (≤ 600A) ............................ 22
Table 15. Secondary System (2) PowerPak PDUs (≤225kVA) and (1) WaveStar STS (≤ 600A) ...................................... 23
Table 16. WaveStar Secondary System - (2) PowerPak PDUs (=288 kVA) and (1) WaveStar STS (=800A) ...................... 23
Table 17. Single Floor Stand — BOM .............................................................................................................. 29
Table 18. Single Floor Stand with Side Bracing — BOM ...................................................................................... 29

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 1
CChhaapptteerr 11 SSaaffeettyy
Please pay special attention to the use of “Danger” symbols throughout this manual indicating electrical or
other safety hazards. Following these safety instructions is extremely important to avoid possible injury or
death.
This symbol is used throughout this manual to indicate the presence of high voltages, representing a hazard for
electric shock, burn or explosion. Follow the instructions carefully to avoid serious or fatal injury.
Follow safe electrical work practices
• Read, understand, and follow the instructions before installing this product.
• Disconnect and lock-out all power supplying equipment before working on or installing power distribution
equipment. Use a properly rated voltage sensing device to confirm power is OFF.
• Install equipment in an appropriate electrical environment per local regulations.
• PCBs are ESD sensitive equipment Ground yourself, discharge any static charge and ensure that the
device is effectively grounded before handling the unit.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel and in
accordance with all local safety codes. Power Distribution, Inc. assumes no responsibility for any
consequences arising out of the use of this manual. This document should not be viewed as sufficient by
otherwise non- ualified personnel to operate, service, or maintain the e uipment discussed.

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 3
CChhaapptteerr 22 FFlloooorr SSttaannddss bbyy PPrroodduucctt
22..11 OOvveerrvviieeww
Eaton provides floor stands as options for the following power distribution products
• All Eaton Power Distribution Units (PDUs)
• Eaton Static Transfer Switches (STSs) up to 1600A
• Primary and Secondary Systems using PowerPak PDUs and WaveStar Static Transfer Switches
Eaton Universal Floor Stands have a common design, construction, and installation
• 1020 steel construction
• Removable conduit plate(s)
• Height-adjustable feet
• Each foot has (4) holes with clearance for 1/2" anchor bolts.
Universal Floor Stands come in a range of nominal heights and adjustment ranges that are standard for all floor
stands
• 15" nominal height, adjustable range 12-18"
• 20" nominal height, adjustable range 18-22"
• 24" nominal height, adjustable range 22-26"
• 28" nominal height, adjustable range 26-30"
• 32" nominal height, adjustable range 30-34"
• 36" nominal height, adjustable range 34-38"
• 40" nominal height, adjustable range 38-42"
• 44" nominal height, adjustable range 42-46"
• 48" nominal height, adjustable range 46-50"
Floor stands of greater height and weight have extra side bracing that is variable according to product. See
drawings for each product.

4 Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01
22..22 PPoowweerrHHuubb 22 PPDDUU
The following floor stands are available for PowerHub 2 PDUs
Table 1. PowerHub 2 PDU Floor Stand Options - 60 W x 40 D
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 255 MOD70101-H15
20" Adjustable +/- 2" 18" - 22" 271 MOD70101-H20
24" Adjustable +/- 2" 22" - 26" 282 MOD70101-H24
28" Adjustable +/- 2" 26" - 30" 291 MOD70101-H28
32" Adjustable +/- 2" 30" - 34" 300 MOD70101-H32
36" Adjustable +/- 2" 34" - 38" 360 MOD70101-H36
40" Adjustable +/- 2" 38" - 42" 370 MOD70101-H40
44" Adjustable +/- 2" 42" - 46" 428 MOD70101-H44
48" Adjustable +/- 2" 46" - 50" 440 MOD70101-H48
Table 2. PowerHub 2 PDU Floor Stand Options - 60 W x 54 D (for 56 Deep PDU Cabinet)
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 330 MOD70102-H15
20" Adjustable +/- 2" 18" - 22" 349 MOD70102-H20
24" Adjustable +/- 2" 22" - 26" 358 MOD70102-H24
28" Adjustable +/- 2" 26" - 30" 367 MOD70102-H28
32" Adjustable +/- 2" 30" - 34" 376 MOD70102-H32
36" Adjustable +/- 2" 34" - 38" 443 MOD70102-H36
40" Adjustable +/- 2" 38" - 42" 452 MOD70102-H40
44" Adjustable +/- 2" 42" - 46" 519 MOD70102-H44
48" Adjustable +/- 2" 46" - 50" 532 MOD70102-H48
Floor Stands by Product

Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01 5
Table 3. PowerHub 2 PDU Floor Stand Options - 86 W x 54 D (for 56 Deep PDU Cabinet)
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 521 MOD70620-H15
20" Adjustable +/- 2" 18" - 22" 562 MOD70620-H20
24" Adjustable +/- 2" 22" - 26" 580 MOD70620-H24
28" Adjustable +/- 2" 26" - 30" 600 MOD70620-H28
32" Adjustable +/- 2" 30" - 34" 617 MOD70620-H32
36" Adjustable +/- 2" 34" - 38" 693 MOD70620-H36
40" Adjustable +/- 2" 38" - 42" 712 MOD70620-H40
44" Adjustable +/- 2" 42" - 46" 788 MOD70620-H44
48" Adjustable +/- 2" 46" - 50" 813 MOD70620-H48
• Qty. 1 - MOD70102-HXX - 60" W x 54"D Main Cabinet
• Qty. 1 - MOD70618-HXX - 26" W x 54"D Sidecar
Figure 1. PowerHub 2 PDU Floor Stand 60"H x 40"D
Floor Stands by Product

8 Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01
22..33 PPoowweerrPPaakk PPDDUU
Floor stands for PowerPak PDUs support the main enclosure. Side cars do not need floor stands.
The following floor stands are available
Table 4. PowerPak PDU Floor Stand Options
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 152 MOD70105-H15
20" Adjustable +/- 2" 18" - 22" 172 MOD70105-H20
24" Adjustable +/- 2" 22" - 26" 181 MOD70105-H24
28" Adjustable +/- 2" 26" - 30" 191 MOD70105-H28
32" Adjustable +/- 2" 30" - 34" 200 MOD70105-H32
36" Adjustable +/- 2" 34" - 38" 209 MOD70105-H36
40" Adjustable +/- 2" 38" - 42" 219 MOD70105-H40
44" Adjustable +/- 2" 42" - 46" 259 MOD70105-H44
48" Adjustable +/- 2" 46" - 50" 271 MOD70105-H48
Table 5. PowerPak PDU Floor Stand Options - Manual Dual
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 152 MOD70105-H15
20" Adjustable +/- 2" 18" - 22" 172 MOD70105-H20
24" Adjustable +/- 2" 22" - 26" 181 MOD70105-H24
28" Adjustable +/- 2" 26" - 30" 191 MOD70105-H28
32" Adjustable +/- 2" 30" - 34" 200 MOD70105-H32
36" Adjustable +/- 2" 34" - 38" 209 MOD70105-H36
40" Adjustable +/- 2" 38" - 42" 219 MOD70105-H40
44" Adjustable +/- 2" 42" - 46" 259 MOD70105-H44
48" Adjustable +/- 2" 46" - 50" 271 MOD70105-H48
PowerPak PDU floor stands are also used with STS floor stands for Primary and Secondary Systems. See these
sections
• 2.3 Primary System Floor Stand
• 2.4 Secondary System Floor Stands
Floor Stands by Product

10 Eaton PDI niversal Floor Stands Installation Manual P-164001105—Rev 01
22..44 PPoowweerrPPaakk 22 PPDDUU
The following Floor Stands are available for PowerPak 2 PDUs
Table 6. PowerPak 2 PDU Floor Stand Options - 42 W x 40 D
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 201 MOD70104-H15
20" Adjustable +/- 2" 18" - 22" 222 MOD70104-H20
24" Adjustable +/- 2" 22" - 26" 230 MOD70104-H24
28" Adjustable +/- 2" 26" - 30" 240 MOD70104-H28
32" Adjustable +/- 2" 30" - 34" 250 MOD70104-H32
36" Adjustable +/- 2" 34" - 38" 298 MOD70104-H36
40" Adjustable +/- 2" 38" - 42" 308 MOD70104-H40
44" Adjustable +/- 2" 42" - 46" 316 MOD70104-H44
48" Adjustable +/- 2" 46" - 50" 329 MOD70104-H48
Table 7. PowerPak 2 PDU Floor Stand Options - 54 W x 40 D
Height Height
Adjustment
Height Range Weight (lbs) Part Number
15" Adjustable +/- 3" 12" - 18" 235 MOD70103-H15
20" Adjustable +/- 2" 18" - 22" 254 MOD70103-H20
24" Adjustable +/- 2" 22" - 26" 263 MOD70103-H24
28" Adjustable +/- 2" 26" - 30" 273 MOD70103-H28
32" Adjustable +/- 2" 30" - 34" 281 MOD70103-H32
36" Adjustable +/- 2" 34" - 38" 337 MOD70103-H36
40" Adjustable +/- 2" 38" - 42" 346 MOD70103-H40
44" Adjustable +/- 2" 42" - 46" 355 MOD70103-H44
48" Adjustable +/- 2" 46" - 50" 368 MOD70103-H48
Floor Stands by Product
Table of contents
Other Eaton Rack & Stand manuals

Eaton
Eaton Two Post Rack User manual

Eaton
Eaton Series NRX Manual

Eaton
Eaton AMT Vari-Depth Manual

Eaton
Eaton 9E1000IR Assembly instructions

Eaton
Eaton Paramount Enclosure User manual

Eaton
Eaton RE 2 User manual

Eaton
Eaton xStorage Home Quick start guide

Eaton
Eaton TRIPP LITE Series User manual

Eaton
Eaton KA146W5 Instruction manual

Eaton
Eaton ALL-PRO WPFLD-TRN User manual
Popular Rack & Stand manuals by other brands

SilverStone
SilverStone RK06U-OF quick start guide

StarTech.com
StarTech.com WALLMOUNTH1 quick start guide

Reer
Reer MZ T4P quick start guide

Audio Contractor
Audio Contractor MBT 1000 Series Instructions for use

NeoMounts
NeoMounts CPU-D200BLACK instruction manual

Marantz
Marantz RMK8003AV installation instructions