
080505-NIN-SQ-EN 16/24 EN
Operating the unit on short cycle
The compressor is starting
but its thermal protection is
operating incorrectly.
-Too much or too little refrigerant,
incondensable air or gas in the circuit.
-Defective compressor capacitor (single
phase models).
-Voltage too low or too high.
-Flare connections are crushed or
compressed.
- Valve capillaries or nozzle obstructed
(damp).
-Insufficient air circulation.
-Inversion valve damaged or blocked
mid-way (reversible models).
-Empty the installation, repair the
leaks, create a vacuum and refill.
-Determine the exact cause and
change the compressor.
-Change the capacitor.
-Fix the power supply problem.
-Locate and fix the crushed sections.
- Empty the installation, create a
vacuum and refill.
-Clean the coils and the filters, check
that the fan motors are functioning
correctly.
-Change the inversion valve.
Indoor coil iced up
Evaporation pressure too
weak.
- Lack of cooling fluid, leakage.
-Insufficient air circulation.
- Lowest temperature limit in cooling
mode exceeded.
-Empty the installation, repair the
leaks, create a vacuum and refill.
-Clean the coils and the filters,
check the fan motors are
functioning correctly, position the air
vents correctly.
-Install a low temperature kit.
Unit noisy
Faulty installation -Check that anti-vibration blocks are
installed and tubes are correctly fixed
into place.
-Re-tighten the fixings and fit anti-
vibration blocks if absent.
Compressor noisy -Check whether the compressor is
leaking oil.
-Excess of refrigerant.
-Repair leak and top up the oil.
-Remove excess refrigerant.
Insufficient or excessive condensation pressure
Excessive high pressure -Coil is clogged.
-Indoor unit fan (heating mode) or
outdoor unit fan (cooling mode) faulty.
-Too much refrigerant
-Presence of air or non-condensable
gas.
-Liquid side blocked or crushed.
-Clean the coil.
-Change the ventilator.
- Remove excess refrigerant.
- Empty the installation, create a
vacuum and refill.
- Fix the blockage or crushed
section.
Insufficiently high pressure -Too little refrigerant, leaks.
-Compressor valves are worn.
-Empty the installation, repair the
leaks, create a vacuum and refill.
-Replace the compressor.
Excessive or insufficient evaporation pressure
Excessive evaporation
pressure
-Too much refrigerant
-Cycle inversion valve is faulty or
leaking (reversible product).
-Remove the excess fluid.
-Change the valve.
- Insufficient evaporation
pressure
-Too little refrigerant, leaks.
-Indoor unit coil (cooling mode) or
outdoor unit coil (heating mode) iced
up.
-Insufficient airflow in indoor unit
(cooling mode) or in outdoor unit
(heating mode).
-Liquid side blocked or crushed.
- Valve capillaries or nozzle obstructed
-Empty the installation, repair the
leaks if necessary, create a vacuum
and refill.
- Find the cause and fix it.
-Check that the ventilator is working
correctly.
-Remove the blockage or fix the
crushed section.
- Empty the installation, create a
8- DIAGNOSIS (flashing LED s)
Error indication OPERATION
LAMP
TIMER
LAMP
DEFROSTING
LAMP
Indoor fan can’t start after 1 minutes
Evaporator temp sensor fault
Over current on the compressor more than 4 times
EEPROM fault ON
Indoor main PCB fault
Room temperature sensor fault
Flashing at 0.5s / 0.5s
Switched off
ON LED is light