Electro Detectors EDA-Q995 User manual

EDA-Q995 Detector Programmer Page: 1 of 4
Ref:Q995v120.DOC Electro-Detectors
EDA-Q995 – Detector Programmer
The EDA-Q995 is a Millennium detector programming unit, used to program both conventional
and analogue detectors. (i.e. the 300 and 500 range of detectors.)
To Switch On
Press and hold the On/Enter button for 1 second. An initial start up screen will be displayed.
The device will automatically switch off one hour after the last key was pressed.
Battery Test
The battery level is indicated to the right hand side of the start up screen as detailed below. A
fully charged battery has all boxes shaded. Should only the bottom box ‘-‘ be shaded then the
batteries should be changed. The battery is a standard Millennium detector battery pack (Part
no. EDA-Q660). The programming device uses very little power and so a battery life in the order
of five years can be expected.
EDA PROGRAMMER +
Version V1.0
Press Any Key
* -
Figure 1. Start Up Screen
To Select the Required Operation
Once the start up screen has been displayed, press any key to display the device programming
screen as shown in figure 2.
Unit No. :0023
System No. : 04
Agent No. : 01
Sensitivity: MED ⇓
Figure 2. Programming Screen
Programmable Options
The programmer allows certain values to be altered on the detector. These are listed below.
Unit Number Each device on a system should have a unique number ranging from 1 to
3000. To maximise performance of the system, device numbers should be
programmed as low as possible. Check with the control panel being used
as to its maximum device capability.
System No. All panels and devices on a system should have this number set to the
same value. Before installing the system, tests should be performed to
ensure other buildings close by are not using the same system number.
The value can range from 1 to 15.
Agent No. Each agent has a unique ID number and each system installed by an agent
should be programmed using this ID number. This avoids cross talk
between two systems on the same system number. This option has only
been implemented in conventional heads from V1.1 and all analogue
heads. The value can range from 1 to 31. A list of agent numbers is
detailed in the Millennium panel manual.
Sensitivity The sensitivity of the sensing head for either heat or smoke detectors. For
numeric values please refer to the detector manual. The sensitivity can be
programmed as Low, Medium and High. Medium is set as default.

EDA-Q995 Detector Programmer Page: 2 of 4
Ref:Q995v120.DOC Electro-Detectors
Verify Time The time between successive verify transmissions. On a small system (i.e.
less than 250 heads) this should be set as approximately 7 minutes. On
larger systems this should be set to approximately 14 minutes and the
verify failure time set on the main control panel should be adjusted. The
range is from 1 to 20 minutes
Alarm Verify Time This is the time in seconds that a device must remain in an alarm condition
before transmitting the fire condition. The default is 2 seconds. It is
recommended that for a detector with a medium sensitivity the default is
used. If the sensitivity is increased then the alarm verification should be
increased to avoid nuisance alarms. The range is from 0 to 10 seconds.
Volume Only required for combined sounder detectors.0 is off 10 is maximium
volume
Sound Area If sector sounding is used then sounders that are required to sound at the
same time should be programmed in the same area. Units in area 0 will
always sound in an alarm condition.
Mess Format Should always be set as ‘OLD’ unless analogue devices are used. It is not
recommended that this value be changed as to what the unit was supplied
as.
To Read or Program a Device
1. Ensure the protection base has been removed from the programmer by lifting the plate
without rotating it. Be careful not to damage the pins.
2. Remove the base and power link from the detector to be programmed.
3. Place the detector onto the programming base. Do not rotate the detector. The LED
should face upwards towards the red mark on the programming base. The detector will
initially beep and the LED will continue to flash.
4. Select the programming screen, if not already selected. A similar screen to figure 3 will
be displayed.
Unit No. :0023
System No. : 04
Agent No. : 01
Sensitivity: MED ⇓
Figure 3. Programming Screen
5. Press the Read/Cancel button to read the current values for the detector. It is always
safer to read values before programming a device, as any previously set special values
will remain programmed. However, if programming new detectors, provided that the first
of a batch is read in to the programmer, then subsequent detectors of the same type can
be programmed without first reading the details. If in doubt always read the devices first.
If the device type changes or the programmer is switched off then the next device must
be read into the programmer before altering values and programming. The programmer
will indicate when the information has successfully been read into the programmer.
Failure will also be indicated.
6. To view the values pressing the ↑and ↓keys will cause the screen to scroll up and
down displaying all values.
7. To change values, select the value to be changed by pressing the ↑and ↓keys until the
flashing cursor appears to the right hand side of the value. Either, press Enter to
increment / scroll the value, or, type the required value and press Enter. A description
and range of each option is detailed previously.
8. If you need to change the verify time or the alarm verify time or any of the other
advanced features, then select Advanced M(enu) and press Enter. You will now be
able to scroll down the screen and view/change the displayed values. To return to the

EDA-Q995 Detector Programmer Page: 3 of 4
Ref:Q995v120.DOC Electro-Detectors
normal simple menu, select Simple Menu and press Enter. The extra options will now
be removed from the screen.
9. Once all information is correct, press Prog to send the details to the detector.
Successful completion will be displayed.
10. Remove the detector from the programmer and refit the power link.
11. Ensure that the device is programmed correctly using a control panel.
To Switch the Unit Off
From the programming menu move the cursor until it is positioned to the right hand side of the
Power Off option and press enter. If the device is left on for more than 60 minutes, the device
will automatically switch off.
To Change the Batteries
The batteries fitted to the programmer are the same as the standard Millennium detector battery
pack (part no EDA-Q660). Unscrew the four retaining screws on the reverse of the programmer
and pull the front away. The battery pack can now be removed. When replacing the battery
ensure it is pressed home fully and that the packing is re-fitted. Ensure that the ribbon cable, if
fitted, is not loose.
Common Problems
1. Will not switch on – Check Batteries Fitted and OK
2. Will not read or program devices – check and clean contacts on both detector and
programmer and ensure power link is removed
3. Menu option not available – Only available on survey modes
4. Will not accept typed changes on the screen – Enter must be pressed once values have
been typed