Ellard Fire Door Control Panel Instruction sheet

PRODUCT INSTRUCTIONS
Fire Door Control Panel (FDCP) Floats Rd, Wythenshawe,
Manchester. M23 9WB
T: +44 (0)161 945 4561
F: +44 (0)161 945 4566
Stock Code Description Doc No: PI-115
00133
00134 Ellard Fire Door Control Panel
Ellard Slave Repeater Unit Iss: 1


FDCP V.1
Contents
1) Specification and Installation ....................................................................................
2) Connection and Indication ...........................................................................................
2.1 Mains Power Supply - In....................................................................................
2.2 Mains Supply - Out.............................................................................................
2.3 Battery...............................................................................................................
2.4 Fire Alarm Signals...............................................................................................
(2.4.1) Zone 1
(2.4.2) Zone 2
2.5 Push Button Connection....................................................................................
2.6 Key Switch Connection......................................................................................
2.7 Panic Button.......................................................................................................
2.8 Photo Beam.......................................................................................................
2.9 Relays................................................................................................................
2.10 Solenoid Release Output .................................................................................
3) Motor Configuration Examples ....................................................................................
3.1 230v AC Tubular Motors
3.2 24v d.c Tubular Motors
3.3 JM Fire shutter Motors
3.4 Volt Free (Other Motors with built on controlers)
4) Smoke and Heat Detector Configurations ...................................................................
5) Programing ...................................................................................................................
6) Repeater Panel...............................................................................................................
6.1 Connection to Repeater Panel
7) Trouble Shooting...........................................................................................................

Power Supply
General
230v - 50Hz
Working Temp
Max Accessories Load
Protection Fuses
1) Specification and Installation
Max Motor Load
Dimensions (mm)
3.0
Weight (Kg)
Batteries 2 x 12V 1.3Ah
Ext 24v d.c: F1 = T4A, Delayed
Mains: F2 = T200mA, Delayed
Relays: F3 = T6.3A, Delayed
236 (w) x 286 (h) x 108 (h)
6.3A @ 230v
4A @ 24v d.c
Cable Entry
The FDCP is designed so the cable entry can be positioned at
the top or bottom of the panel by means of removing the PCB
fixing screws, then rotating either board or box 180° and
refitting (see Fig 1.2)
Mounting
Mount the unit using the fixing holes provided (see Fig 1.1)
BOTTOM CABLE ENTRY
+
-
+
-
+
-
+-
+-
+
-
'A'
'A'
'A'
'A'
Fig 1.1
Enclosure Mounting
TOP CABLE ENTRY
Fig 1.2
Cable entry positions
Remove fixing screws 'A' and rotate
board or box
WARNING
FIRE
SHUTTER
CLOSING
Standards and Conformity
Directive 2004/108/EC
Directive 2006/95/EC
EMC Directive:
Low Voltage Requirements:
and In association with: EN 60204-1: 2006+A1: 2009
EN 61000-6-1: 2007
EN 61000-6-2: 2005
EN 61000-6-3: 2007+A1: 2011
EN 61000-6-4: 2007+A1: 2011
EN 12453:2001
EN 50272-2: 2001
The FDCP complies to the following EMC and Low Voltage
standards and directives
-20 to +70°C

Connection - TS3A
PE
L
N
Mains power supply - EARTH
Mains power supply - LIVE
Mains power supply - NEUTRAL
Connection - TS3
Mains power supply - EARTH
Mains power supply - LIVE
Mains power supply - NEUTRAL
Ext. Siren
Connection - TS5
Ext. Warning Light
Ext. 24v d.c
1Zone 1 - Main Fire signal +24v d.c (+)
Connection - TS1
11 Push Button - COM
Connection - TS1A
15 + 16
Photo Beam Supply - (+24v)
Photo Beam Contact - ( COM)
Zone 1 - Main Fire signal - N/O, N/C, 8k2
Zone 2 - Local Fire signal +24v d.c (-)
Zone 2 - Local Fire signal N/O, N/C, 8k2
Ext. 24v d.c. Supply (200mA Max)
Push Button - STOP (N/C)
Push Button - OPEN (N/O)
Push Button - CLOSE (N/O)
Panic Button - (N/O)
Photo Beam Supply - (0V)
Photo Beam Contact - ( N/C)
3 + 4
6
7 + 8
9 + 10
1 + 2
3 + 4
5 + 6
12
13
14
17
18
19
20
PE
L
N
1 + 2 Stop Relay (N/C)
Connection - TS6
Open Relay (N/O)
Aux 1 Relay (N/C)
3 + 4
5 + 6
7
Close Relay (N/O)
Aux 1 Relay (COM)
8
Aux 1 Relay (N/O)
9
Aux 2 Relay (N/C)10
Aux 2 Relay (COM)
11
Aux 2 Relay (N/O)
12
Solenoid (0V)
13
Solenoid (+24V)14
+Battery (+)
Connection - TS4
Battery (-)-
2 Zone 1 - Main Fire signal +24v d.c (-)
Zone 2 - Local Fire signal +24v d.c (+)
5
Mains ok
Indication
Fault
Alarm
FDCP v.1 (Software Ver 06)
Multi Function Control System for Roller Shutters and
Smoke curtains
Features
·Large visual warning 'FIRE SHUTTER CLOSING' and
102 dB sounder
·Internal easy read display
·Easy to program using the 'intelligent' dial
·Built in batteries to maintain fire signal activation, and to
operated a 24v brake release device in the even of a
power failure
·Select able fire signal - Normally Open (N/O) or
Normally Closed (N/C) volt free potential (Dry contact)
or 2 -30V d.c direct input
·Low Voltage external push button control
·3 closing options - Solenoid Only, Power Closing or 2
Stage Drop
·Programmable relays
·Automatic reset and optional opening once the fire
signal is removed
·Panic Button option for emergency escape
·Complies with latest EU Directives
·Fully CE compliant
Application
·Whilst maintaining the function of every day use the
FDCP gives advanced warning in the event of a fire
before closing the shutter or curtain, protecting both
personnel and property from the effects of smoke and
fire
·Built in comprehensive diagnostics which include mains
fail and low battery charge
·Can be fully interfaced with building management
systems
Installation
·The enclosure should be mounted vertically and
secured using the provided fixing holes (see fig 1.1)
·Consideration must be given to the incoming cables
and the panel rotated accordingly to give top or bottom
entry (see fig 1.2)
·To protect both motor and personnel, this product must
be connected to a suitable EARTH point
·All electrical work should be undertaken by a suitable
competent person
2) Connections and Indication
GREEN Automatic when mains power applied
RED
RED
Switched on when Alarm Signal applied
Switched on when a fault has occurred
(see display message for more information)
Stop ok RED On if Stop circuit - ok
Photo ok GREEN On if Photo Beam circuit - ok

(+24)
(-)
(+24)
(-)
Fig 3. Activation by removal of a
Permanent +24v d.c Fire Signal
(Select +24V)
2.4) Fire Signals (Connections and types)
2.4.1) Alarm Zone 1 - Main Fire Alarm Signal
Normally Open (N/O)
Triggers the panel by a N/O volt free signal which CLOSES
when the fire alarm is activated
Note: an 8k2 resistor must be fitted across input
connections
Normally Close (N/C)
Triggers the panel by a N/C volt free signal which OPENS
when the fire alarm is activated
+24v d.c
Triggers the panel by removing a permanently connected +24v
d.c fire signal when the fire alarm is activated
2.4.2) Alarm Zone 2 - Local Fire Alarm Signal
Normally Open (N/O)
Triggers the panel by a N/O volt free signal which CLOSES
when the fire alarm is activated
Note: an 8k2 resistor must be fitted across input
connections
Normally Close (N/C)
Triggers the panel by a N/C volt free signal which OPENS
when the fire alarm is activated
+24v d.c
Triggers the panel by removing a permanently connected +24v
d.c fire signal when the fire alarm is activated l
OFF
Disables Zone 2 Input
TS1
142 5 6 789 103
8k2
RESISTOR 8k2
RESISTOR
Zone
1Zone
2
Fig 1. Activation by a
N/O Fire Signal
(select Normally Open)
Zone
1Zone
2
Fig 2. Activation by a
N/C Fire Signal
(Select Normally Closed)
142 567 8 9 103TS1
142 5 6 7 8 9 103
TS1
Zone
1Zone
2
(+24)
(-)
(+24)
(-)
Fig 4. Activation by
Applying a +24v d.c Fire Signal
(Select N/O)
1 42 5 6 7 8 9 103
TS1
Zone
1Zone
2
8k2
RESISTOR 8k2
RESISTOR
2.1) Mains Power - In (TS3A)
2.2) Mains Power - Out (TS3)
2.3) Battery (TS4)
TS3A
230V AC
50Hz
Mains In
TS3A
230V AC
50Hz
Mains Out
BLACK
RED
WARNING
FIRE
SHUTTER
CLOSING
TS5
TS1 TS1A
TS6
+
-
+
-
+
-
Terminal
Block Positions
and LED
Indicators
TS6
TS3
TS3A
TS4
TS6
-
+
LED
INDICATION

Fit Link
2.8) Photo Beam (optional - see programming)
Stops and re-opens a closing door for a
pre-determined number of operations
in fire condition
2.9) Relays Outputs
The unit is fitted with individual relays to provide different functions as required
All contacts are at a volt free potential (dry contact) and are rated at 230v AC
16A
Typical Reflective
photocell
(style and wiring colours may vary)
(N/C)
(COM)
(-)
(+)
Photo Beam
STOP - Relay (1 + 2)
ANormally Closed contact that will open
circuit when the Stop button is pressed
(Disabled on receipt of a Fire signal)
OPEN - Relay (3 + 4)
ANormally Open contact that will provide a
closed circuit when the Open button is
pressed
(Disabled) on receipt of a Fire signal)
CLOSE - Relay (5 + 6)
ANormally Open contact that will provide a
closed circuit when the Close button is
pressed
(Disabled) on receipt of a Fire signal)
AUX 1 - Relay (7, 8, 9)
ANormally Closed Relay that will change
state when activated
Relay is only switched upon receipt of a fire
signal
AUX 2 - Relay (10, 11, 12)
ANormally Closed Relay that will change
state when activated
Relay is programmable to simulate other
relays or switch upon Low Battery power or
Mains Fail
(N/O) (not used)
2.10) 24v d.c Solenoid Output
A brake release device or solenoid unit can
be activated when connected to the output
provided
This output can operate a brake release unit
rated at 24v d.c
To 24v d.c
Brake Release
Device
11 1412 15 16 17 18 19 20
13
TS1A
11 1412 15 16 17 18 19 2013
TS1A
11 1412 15 16 17 18 19 2013
TS1A
11 1412 15 16 17 18 19 2013
TS1A
OPEN
STOP
CLOSE
CLOSE OPEN
COM
2.5) Push Button (optional)
Connection of a typical 3 push button station to
operate the door under normal conditions
2.6) Key Switch (optional)
Connection of a typical keyswitch to
operate the door under normal condition
2.7) Panic Button (optional)
Connection of a normally open panic button to
re-open the door under an emergency to 75% of
full close time
11 = COM
12 = STOP
13 = OPEN
14 = CLOSE
11 + 12 COM (LINKED)
13 = OPEN
14 = CLOSE
17 = +24V DC
18 = 0V
19 = COM
20 = N/C
Function ( to be used on power closing)
A connected Photo Beam will stopand
re-open a closing door when in firealarm
condition only
It is programmed for a pre-set numberof
attempts to close the shutter if thebeam is
broken
On the final attempt the Photo Beam will
ignore any furtehr obstrutions and close the
shutter as far as possible
(Always active on power and 2 stage closing)

NEUTRAL (COM)
EARTH
DIRECTION (L1)
Note:
THIS CIRCUIT IS PROTECTED BY FUSE 'F3' WITH A
MAXIMUM RATING OF 6.3A
THE PANEL MUST THEN BE SET FOR 'POWER CLOSING
(SEE PROGRAMMING INSTRUCTION)
CONSIDERATION MUST BE TAKEN FOR THIS
CONFIGURATION, DOOR WILL ONLY RUN PROVIDING 230V
AC MAINS SUPPLY IS AVAILABLE
A SUITABLE BATTERY BACK UP THEREFORE MAY NEED
PROVIDING IN THE EVENT OF LOSS OF MAINS POWER
DIRECTION (L2)
230V AC
+
-
+
-
+
-
3.1 Typical Connection for 230v AC Tubular Motors
(Use with "Power Closing" or "2 Stage Closing")

(+VE)
(-VE)
Note:
THIS CIRCUIT IS PROTECTED BY FUSE 'F1' WITH A
MAXIMUM RATING OF 4A
THE PANEL MUST THEN BE SET FOR 'POWER CLOSING
WITH AUX 2 SELECTED FOR 'OPEN'
(SEE PROGRAMMING INSTRUCTION)
CONSIDERATION MUST BE TAKEN FOR THIS
CONFIGURATION, DOOR WILL ONLY RUN PROVIDING 230V
AC MAINS SUPPLY IS AVAILABLE
A SUITABLE BATTERY BACK UP THEREFORE MAY NEED
PROVIDING IN THE EVENT OF LOSS OF MAINS POWER
24V d.c
3.2 Typical Connection for 24v d.c Tubular motors
(Use with "Power Closing" or "2 Stage Closing")

R
JM POWER SUPPLY CONNECTION
FOR 3 PHASE OPERATORS, AN
INDEPENDENT SUPPLY (3PH, N, + E)
MUST BE INSTALLED
FOR 1 PHASE OPERATORS THE
MOTOR SUPPLY CAN BE SUPPLIED
VIA AN INDEPENDENT SUPPLY OR
TAKEN DIRECTLY FROM TERMINAL
TS3 -PE, L, N
3.3 Connection for 'JM' series motors
fitted with 24V DC brake release solenoid unit
(Use with "Power Closing" , "2 Stage Closing" and Solenoid Only")

NOTES :-
OPERATOR POWER SUPPLY
3 PHASE OPERATORS MUST BE CONNECTED TO AN INDEPENDENT SUPPLY
(3PH, N, + E) FITTED WITH SUITABLE FUSE PROTECTION
1 PHASE OPERATORS CAN BE CONNECTED TO AN INDEPENDENT SUPPLY
FITTED WITH SUITABLE FUSE PROTECTION
OR TAKEN DIRECTLY FROM TERMINAL TS3 - PE, L, N
3.4 Connection for other motors with built on controllers
(Use with "Power Closing" , "2 Stage Closing" and Solenoid Only")
OPEN
CLOSE
COM
+
-
+
-
+
-
VOLT FREE POTENTIAL OUT PUT
TO DRIVE EXTERNAL
CONTROLS OR OPERATORS
FITTED WITH 'BUILT - ON'
STARTERS

R
L1OUT
EARTH
L1IN
N/O COM N/C
L2
TS1
142 5 6 789 103
8k2
RESISTOR
(N/O)
(COM)
(-)
Program Choice = Solenoid Only or Power closing
Main activation using a Smoke/ Heat Detector with Relay Base
Signal = (Normally Open)
Main Fire Alarm signal - Zone 1
On activation shutter
descends to full closed position
TS6
7 8 9 10 11 12
NC com NO
AUX1 NC com NO
AUX2
(+)
4. Typical Connection for
RELAY BASE Stand Alone Heat and Smoke Detectors
Relay Base
Supplier Apollo
Part No 45681-245 APO
Series 65 Relay Base
Ellard Stock code 04053
Smoke Detector Head
Series 65
Supplier - Apollo
Part No 55000-122 APO
Ellard Stock code 04052
Heat Detector Head
Series 65
Supplier - Apollo
Part No 55000-217 APO
Ellard Stock code 04061

R
L1OUT
EARTH
L1IN
N/O COM N/C
L2
TS1
142 5 6 789 103
8k2
RESISTOR
Program Choice = 2 Stage Closing
Main activation for 2 stage closing using a Smoke/ Heat
Detector with Relay Base
(Signal shown = Normally Open)
R
L1OUT
EARTH
L1IN
N/O COM N/C
L2
TS1
142 5 6 7 8 9 103
8k2
RESISTOR
Main Fire Alarm
signal - Zone 2
Shutter descends to
part close position
(1st Stage)
Program Choice = 2 Stage Closing
2nd stage activation using a Smoke/ Heat Detector with Relay Base
Signal Shown = Normally Open
(N/O)
(COM)
(-)
(N/O)
(COM)
(-)
8k2
RESISTOR
Used as Local Fire Alarm
signal - Zone 1
Shutter descends to full
close position
(2nd Stage)
Main Fire Alarm signal - Zone 1
On activation shutter
descends to part close position
If signal still present
Pauses for selected time
Then shutter descends to fully
closed position
TS6
7 8 9 10 11 12
NC com NO
AUX1 NC com NO
AUX2
(+)
(+)
TS6
7 8 9 10 11 12
NC com NO
AUX1 NC com NO
AUX2

USER
PROGRAM DEMO
PRESS
ONCE
ROTATE TO
CHANGE
PRESS AND HOLD
3 SEC TO ENTER
MENU
ALARM ZONE 1
(Normally Open)
ALARM ZONE 2
(Normally Open)
ROTATE TO
CHANGE
NORMALLY OPEN
NORMALLY CLOSED
+24V
TEST DELAY TIMER
(0:00) 0 - 30 SECS
ALARM DELAY TIME
(0:01) 1 SEC - 10 MINS
F. CLOSE RUN TIME
(0:03) 3 SEC - 5 MINS
PART CLOSE TIME
(0:00) 0 - 10 MINS
PART CLOSE PAUSE
(0:00) 0 - 5 MINS
ALARM ZONE 1
This is Main fire alarm input
The panel will activate upon receipt of either of following signal types
N/O, N/C, +24v DC
(See content 2.4.1)
ALARM ZONE 2
This is Local fire alarm input
The panel will activate upon receipt of either of following signal types
N/O, N/C, +24v DC
(See content 2.4.2)
TEST DELAY TIMER
This automatically delays any shutter movement for the selected time
Generally used for for fire alarm test purposes
When the fire alarm is under test, the panel will sound and flash without fully
activating the motor or break release device
Note: To prevent full activation of panel and shutter, the Fire alarm
signal must be removed before the test delay time expires
ALARM DELAY TIME
Upon receipt of a fire signal the panel will sound and flash for the selected
time
No shutter movement will be happen during this countdown period
F. CLOSE RUN TIME
This is the total time the shutter will take to run from from fully open to
fully close position
PART CLOSE TIME (Only displayed if 2 stage closing selected )
This is the length of travel at the first stage of closing after the Alarm Delay
Time has expired
The shutter will run for the selected time to a predetermined height, where
upon it will pause and wait for activation from second or continuing signal
The Audio - Visual remains activated until all fire signals are removed, where
upon the shutter can then be reopened manually or automatically if selected
PART CLOSE PAUSE (Only available if 2 stage closing selected )
This is the pause time after the shutter has driven to its first stage
The Audio Visual will continue until receipt of a second or continuing
signal
No shutter movement will be happen during this countdown period
Should all fire signals be removed the audio visual will cease and shutter can
then be reopened
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
ALARM DOOR TYPE
ROTATE TO
CHANGE
POWER CLOSING,
2 STAGE CLOSING
SOLENOID ONLY
ROTATE TO
ADVANCE
MENU
PRESS
ONCE
USER
Allows panel to be programmed with all audio / visual warnings active
DEMO
Allows panel to be programmed but disabling the sounder (for demonstration
purposes)
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
ALARM DOOR TYPE
This is how the how the shutter will close upon receipt of a fire signal:
Power Closing - Shutter Drives Down under mains power
2 stage closing - Shutter closes in 2 stages under mains power
Solenoid only - Shutter closes by a gravity controlled descent
NORMALLY OPEN
NORMALLY CLOSED
+24V, ZONE 2 OFF
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
INTELLIGENT
DIAL
BATTERY VOLTAGE
27.26v
After installation the FDCP must be programmed to operate upon receipt of a fire signal, the shutter will close
by the method selected in 'ALARM DOOR TYPE'
To access set up, press and hold the 'Intelligent Dial' for 3 seconds, the display will change from battery
condition to USER menu
To move through the features, rotate the 'Intelligent Dial'
To change a value within the feature press the 'Intelligent Dial' once - the display will flash, rotate to change,
then press once to store
To EXIT set up at any time press and hold program button for 3 seconds
5) Programming

DOOR CLOSED ALARM
VISUAL + SOUND
OFF ON - OFF
PRESS
ONCE
PRESS
ONCE
DOOR CLOSED ALARM - VISUAL AND SOUND
·With the shutter fully closed and the fire alarm signal still present, the
Audio Visual warning can either continue or be switched OFF
AUX 1 RELAY
AFTER CLOSE
(ON) ON - OFF
PRESS
ONCE
ROTATE TO
CHANGE
PHOTO BEAM
OPERATION IN ALARM
(OFF)
PHOTO BEAM
ALARM DELAY
(0:00)
ROTATE TO
CHANGE
ON - OFF
0 -10 MINS
PHOTO REOPEN TIME
(0:00) 0 - 10 MINS
PHOTO BEAM
RETRIES
(0.00) 0 - 10
PHOTO BEAM PAUSE
(0.01) 0 - 30 SECS
RE-OPEN TIME
(0.00) 0 - 10 MINS
FACTORY RESET
PRESS FOR 10 SEC'S?
AUX 2
·This relay is switched in both normal and fire condition, and will
simulate any other another relay or be activate depending on its
selected function
In Fire condition the STOP relay is disabled
PHOTO BEAM OPERATION IN ALARM
(Feature disabled in SOLENOID ONLY mode)
·Enables a connected photocell to stop and reopen a closing door when
the beam is broken
Only Active in fire condition and when turned ON in menu
PHOTO BEAM ALARM DELAY
(Feature disabled in SOLENOID ONLY mode)
·Should the photo beam become obstructed an
audible obstruction warning will sound after a selected time
PHOTO REOPEN TIME
(Feature disabled in SOLENOID ONLY mode)
·Upon breaking the photo beam the door will stop and reopen
for the selected time
This is typically set for the same time as F.Close Run time
PHOTO BEAM RETRIES
(Feature disabled in SOLENOID ONLY mode)
Should the photo beam become triggered, the shutter will stop then
reopen for the time set in PHOTO REOPEN TIME
If the photo beam remains blocked another attempt will be made to
close the shutter, this will continue for the selected number of times
If the obstruction is removed before this count is reached, the shutter
will continue and close
If on the final attempt the photo beam remains blocked, the photo
beam will be ignored and the shutter will close as far as possible
PHOTO BEAM PAUSE
(Feature disabled in SOLENOID ONLY mode)
·This is the delay time before the next command is carried out
after the photo beam has been broken
RE-OPEN TIME
·Automatically reopens a closed shutter for the time
selected upon removal of all active fire signals
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS AND HOLD
FOR 10 SECS
AUX 2 RELAY
(STOP)
ROTATE TO
CHANGE
STOP, OPEN CLOSE,
MAINS FAIL
LOW BATTERY
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
PRESS
ONCE
AUX 1 (AFTER CLOSE)
·This relay is only switched ON, upon receipt of a fire signal
With the shutter fully closed and the fire alarm signal still present,
Aux 1 can either remain ON or be switched OFF
FACTORY RESET
·Clears all previous selected times and then restores the
unit back to factory default settings
This is done by pressing and holding the program
button for 10 seconds
PRESS AND HOLD
3 SEC TO EXIT USER PROGRAM
MODE
ROTATE TO
ADVANCE
MENU
ROTATE TO
CHANGE
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
ADVANCE
MENU
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
CHANGE
ROTATE TO
ADVANCE
MENU
Factory Reset
*OFF **ON

WARNING
FIRE
SHUTTER
CLOSING
2 x M16 Glands
BOTTOM CABLE ENTRY
TOP CABLE ENTRY
Power Supply
General
24v d.c.
Working Temp
6) Repeater Panel Specification
Dimensions (mm)
Weight (Kg)
236 (w) x 286 (h) x 108 (h)
Cable Entry
The FDCP Repeater Panel is designed so the cable entry
can be via the top or bottom of the panel by means of
removing the PCB fixing screws, then rotating either board or
box 180° and re-fitting (see Fig 1.2)
Mounting
Mount the unit using the fixing holes provided (see Fig 1.1)
Fig 1.1
Enclosure Mounting
Fig 1.2
Cable entry positions
Remove fixing screws 'A' and rotate
board or box
TOP CABLE ENTRY
'A''A'
'A''A'
3.0
-20 to +70°C

+
-
6.1 Connection detail for repeater panel
+
-
+
-
+
-
+
-
+
-

Alarm Zone 1
Message shown in Display Cause and possible solution
Input to ZONE 1 is activated - Check If Fire Alarm Signal is still present
Alarm Zone 2
Setup Fault
Part close runt. Part close run time is longer than full close run time
Full close runtime must be longer than Part close runtime
EEPROM parameter values have become changed, unaided from saved
values
(all values in EEPROM are checked on each power up)
Try entering programming mode then exit back to normal mode again
Switch off, disconnect batteries - reconnect batteries and power up again
If problem persists replace the unit
EEPROM failure
Service required
Photo Beam inputs and Fire Alarm inputs are tested each hour in normal
mode and after each manual operation of the door
Check condition of these signals and that the programming set up is correct
Circuit fail
Service required
Batt.Not Charged
Check mains Measured battery voltage is low. Check if mains supply is ok
Batt.test failed
Replace batt
Battery load is tested 1.5 sec, 2mins after power up and then each 12 hours
Check if battery is connected before powering up
Battery has deteriorated
Photo Beam Break Check for obstruction
Check for allignment
Check N/C circuit
Batt. Charger OFF
Check mains Check Mains supply
Batt. Info
Batt. Voltage <24v Battery not fully charged
Batt. Voltage
xx.x Volt This is not a fault - Battery voltage monitoring only
FDCP V.1
7. Troubleshooting Guide
Mains ok
LED Indication
Fault
Alarm
GREEN Automatic when mains power applied
RED
RED
Switched on when Alarm Signal applied
Switched on when a fault has occurred
(see display message for more information)
Stop ok RED On if Stop circuit - ok
Photo ok GREEN On if Photo Beam circuit - ok
No Display Check power supply
Check batteries
Check contrast pot is turned up
Panel or Fire Alarm will not function
No Display or LED's present Check unit has not been left in programming mode and that dispaly is
showing battery voltage
5v Regulator Fail
Input to ZONE 2 is activated - Check If Fire Alarm Signal is still present


Table of contents
Other Ellard Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Simplex
Simplex 49SVC-CWFIRE installation instructions

Fire Burglary Instruments
Fire Burglary Instruments XL 1219 Programming instructions

Cooper Notification
Cooper Notification ST-C installation instructions

Tecnoalarm
Tecnoalarm Tecnofire TFA2-596 Installation

ADEMCO
ADEMCO 744 installation instructions

Tyco
Tyco RC-1 manual