manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cooper Notification
  6. •
  7. Fire Alarm
  8. •
  9. Cooper Notification Eluxa ELCH User manual

Cooper Notification Eluxa ELCH User manual

INSTALLATION INSTRUCTIONS
WHEELOCK ELUXA
CHIME AND CHIME STROBES
WITH PRE
-WIRE/PRE-TEST (WALL MOUNT)
273 Branchport Ave.
Long Branch, N.J. 07740
(800) 631-2148
www.coopernotification.com
PN P85864B Copyright 2022 Cooper Wheelock, Inc. dba Cooper Notification Page 1
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
The Wheelock Eluxa series ELCH Chime and ELCHS Chime-Strobe appliances are designed for easy installation with a pre-wire capable
mounting plate. All models are for 24V operation. Series ELCH/ELCHS Eluxa Chime is UL Listed for indoor fire protection service under
Standard UL464 for Private Mode Audible Signal Appliances as well as ULC-S525-2016 (Audible Signaling Devices for Fire Alarm and
Signaling Systems). The Eluxa Chime is designed for low current draw and versatile performance. The Eluxa Chime offers a choice of
1Hz, 2Hz, coded, or temporal code 3 (T3) operation. It has an adjustable sound level, and operates at a frequency of 890Hz. The Low
Profile design incorporates a high efficiency speaker for maximum output at minimum power, and features a sealed back construction for
extra protection and improved audibility. These models are listed for indoor use, wall mount with the backboxes specified in these
instructions (see mounting options). Model ELCH (non-strobe) may be wall or ceiling mounted.
The Wheelock Eluxa Series meets NFPA 2016 20 millisecond light pulse duration code requirements. In addition, the Wheelock Eluxa and
LED3 product lines have been UL/ULC listed as compatible with all Fire Alarm Control Panels (FACP) and accessories that have been
determined to be compatible with Wheelock model RSS Strobe based products including the RSS, CH, E, EH, ET,ST,HS,MT,S8, SA, STH
and Z Series. The maximum number of Eluxa devices per NAC is determined by dividing the maximum current rating of the FACP NAC by
the total current rating of one Eluxa device, with a maximum of 105 Eluxa (or LED3) devices per NAC. Refer to FACP installation instructions
for more detail. The Wheelock Eluxa Series and Exceder LED3 Series strobes may be installed in the same notification zone and field of
view with any RSS Strobe based product.
Wheelock Eluxa Strobe can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP),
or provide a synchronized strobe appliance when used in conjunction with an FACP that incorporates the Wheelock Sync Protocol, a Dual
Sync Module (DSM) or a Wheelock Power Supply.
CAUTION: Do not change factory applied finishes. “DO NOT PAINT”.
ATTENTION: Ne pas modifiez les finitions appliquées en usine. “NE PAS PEINTURER”
IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING
INSTRUCTIONS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN
AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
SPECIFICATIONS:
Table 1: Specifications
Models
E
L
CH
(
Chime
)
,
EL
CHS
(
Chime
-
Strobe
)
Agency Strobe: UL1638, UL1971,CAN/ULC-S526-16
Sounder: UL464,
CAN/ULC
-
S525
-
16
Input Voltage DC or FWR, 24V Regulated, 16 to 33V (All models)
Chime Patterns 1Hz, 2Hz, Coded, T3 (field selectable, Table 4)
Strobe Light Output
Strobe: 15, 30, 75,
110
, 1
35
, 1
85
cd (field selectable)
NAC Characteristics Max. line resistance: 35Ω
Environmental Indoor Use Only. 0°C - 50°C (32°F - 122°F) 93% R.H.
Table 2A: Eluxa Chime – Current and Sound Pressure Level Ratings
Maximum
RMS
Current
Reverberant dBA at 10Ft
per UL464
for Private Mode
Anechoic dBA at 10 Ft
per CAN/ULC-S525-16
for Dwelling Use Only
UL/ULC Voltage
(Amps)
Min
Max
Min
Max
DC 16.0 – 33.0 Vdc 0.022 51 68 61 78
FWR 16.0 – 33.0 Vrms 0.022 51 68 61 78
Table 2B: Directional Characteristics
-3dB +/- 90 Degrees Horizontal, +/- 90 Degrees Vertical (does not reach 3dB)
-
6dB
+/
-
90
Degrees
Horizontal,
+/
-
90
Degrees Vertical
(does not reach 6dB)
Table 3: ELCHS Strobe Current Ratings (AMPS) **
Regulated 24DC (16-33VDC) Regulated 24FWR (16-33VRMS)
Candela Setting 15cd 30cd 75cd 110cd 135cd 185cd
DC
0.022
0.030
0.060
0.086
0.125
0.185
FWR
0.036
0.050
0.092
0.142
0.196
0.274
** Setting will determine the current draw of the product.
When calculating the total currents: Use Table 2A and Table 3 to determine the highest value of “RMS Current” for an individual appliance,
then multiply these values by the total number of appliances; be sure to add the currents for any other appliances powered by the same
source and include any required safety factors.
Make sure that the total RMS current required required by all appliances that are connected to the system’s PRIMARY and SECONDARY
power sources, NAC circuits, DSM Sync Modules or Wheelock Power Supplies does not exceed the power sources’ rated capacity or the
current ratings of any fuses on the circuits to which these appliances are wired.
Check the minimum and maximum output of the power supply and standby battery, and subtract the voltage drop from the circuit wiring
resistance to determine the applied voltage to the appliance.
WIRING DIAGRAMS:
Figure 1A: One Circuit. ELCH Chime
+
-
- + +
FROM PRECEDING APPLIANCE
FACP, POWER SUPPLY
OR SYNC MODULE
TO NEXT
OR E.O.L.R.
APPLIANCE
+
-
Figure 1B: One circuit.
ELCHS Chime and Strobe activate in unison.
Figure 1C: Two Circuits (Chime may be Coded)
ELCHS Chime and Strobe will operate independently
FROM PRECEDING APPLIANCE
FACP, POWER SUPPLY
- + +
- + +
OR SYNC MODULE
TO NEXT
OR E.O.L.R.
APPLIANCE
+
-
+
-
FROM PRECEDING APPLIANCE
FACP, POWER SUPPLY
TO NEXT
OR E.O.L.R.
- + +
- + +
OR SYNC MODULE
FROM PRECEDING APPLIANCE
FACP, POWER SUPPLY
OR SYNC MODULE
APPLIANCE
TO NEXT
OR E.O.L.R.
APPLIANCE
+
-
+
-
+
-
+
-
*Refer to Dual Sync Module instruction sheets DSM (P83177) or Wheelock’s Power Supplies for additional information.
Figure 2:
1. This model has in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at
each screw terminal. Strip leads 3/8 inches and connect to screw terminals.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown in
Figure 2. The polarity shown in the wiring diagrams is for operation of the appliances. The polarity is
reversed by the FACP during supervision.
NOTES:
1. The strobe will produce 1 flash per second over the "Regulated Voltage" range.
2. Strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
3. The maximum number of Eluxa or LED3 strobes on a single notification appliance circuit shall not exceed 105.
4. These appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed
as “Regulated.” Refer to the FACP instructions or the Wheelock Strobe Compatibility Data Sheet (P85328) for special application
and strobe synchronization compatibility.
5. These appliances were tested to the regulated voltage limits of 16.0-33.0 Volts. Do not apply voltage outside of this range. Check
the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring
resistance to determine the applied voltage to the strobes. The max wire impedance between strobes shall not exceed 35 ohms.
6. Make sure that the total RMS current required by all appliances that are connected to the system’s primary and secondary power
sources, notification appliance circuits, DSM sync modules, or Wheelock power supplies does not exceed the power sources rated
capacity or the current ratings of any fuses on the circuits to which these appliances are wired.
7. The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is
specified by ANSI and NFPA 72 for standard emergency evacuation signaling. Code 3 shall be used only for fire evacuation signaling
and not for any other purpose.
8. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the
original cartons and not subjected to misuse or abuse.
PN P85864B Page 2
SETTINGS:
Figure 3A: Chime Setting
MAX
MIN
SW1
ON
VOLUME
TONE
Table 4: Chime Tone Settings SW1
DIP
Position
MODE Circuits
Required
1
2
OFF OFF 2Hz One or Two
OFF
ON
T3 (Code 3)
One or Two
ON
OFF
1Hz
One or Two
ON ON Coded Two
Factory setting is T3 (Code 3) with Volume at Maximum.
Tone may be changed with the DIP switch , SW1.
Refer to Figure 3 for location of SW1 and Volume Control.
Synchronized Mode Settings: The chime will produce temporal Code 3 (T3) “Chime Tone” on 1Hz, 2Hz (and T3) settings. Coded setting
is not compatible with synchronization, and should not be used.
Continuous Mode Settings: T3 (Code 3), 1Hz, and 2Hz: Continuous input voltage must be applied to operate the chime in these modes.
Coded Operating Mode: Set SW1 to “Coded” setting. See Table 4, and Figure 3A. The minimum input pulse duration required is 160 milli-
seconds “ON” time, and 160 milli-seconds “OFF” time. The chime will operate once for each input pulse. This mode is recommended for
coded systems where voltage is not continuous. Requires two circuits, since strobes are not compatible with Coded Systems.
SETTINGS: To set candela, slide the selector switch to the desired setting. See Figure 3B.
Figure 3B: Candela
Set from
side or
rear.
Factory Setting is
15
cd
.
Figure 4: ELCHS Light Distribution
CANDELA
WINDOW
CANDELA
INDICATOR
CANDELA
SELECTOR
15
Strobe device has only one mounting orientation. LED light element should be oriented toward the floor
NFPA 72/ANSI 117.1 provide means for determining equivalent illumination using fewer, higher intensity strobes within the same protected
area.
Figure 5: Grille Removal ** Figure 6: Surface BackBox – ELSPKBB
1
2
SURFACE BACKBOX
BREAK OFF WHEN 3/4"
CONDUIT IS USED
(2)#10 WOOD SCREW
METAL STRAP
(2)MOUNTING TAB
** Grille removal: (Figure 5) 1) Insert Screwdriver into slot, and push to release snap. 2) Lift Up to remove the grille.
MOUNTING OPTIONS:
The following figures (A and B) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting
option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the
wires could damage the product.
Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if
sheathed multiconductor cable or 3/4" conduit fittings are used.
Figure A: Flush Mount
DBB or 4”SQ x 2 1/8” Box
Figure B: Surface Mount
ELSPKBB-R (Red); ELSPKBB-W (White).
(2)#8-32 THREAD CUTTING SCREW
(2)#8-32 THREAD CUTTING SCREW
Maximum Number of Conductors
AWG #18 #16 #14 #12
ELCHS 8 8 8 8
ELCH 4 4 4 4
Maximum Number of Conductors
AWG #18 #16 #14 #12
ELCHS 8 8 8 8
ELCH 4 4 4 4
All installations shall be in accordance with:
1) In the United States, the National Electrical Code, NFPA 70, and the National Fire Alarm and Signaling Code, NFPA 72.
2) In Canada, CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, Section 32; and the Canadian
Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524.
MOUNTING PROCEDURES:
1. Select a mounting option and install the backbox. ELSPKBB requires 5 1/8” spacing for surface mounting. Screws are provided.
Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. Do not pass
additional wires (used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient
wiring space for the signaling appliance.
2. Install the Mounting Plate on the backbox. Use 8-32 screws for 4” back-box or hi-lo screws for the ELSPKBB.
3. Pre-Wire: Connect field wires to terminals on mounting plate (reference Figure 1 and 2). Use care and proper techniques to position
the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially
important for stiff, heavy gauge wires and wires with thick insulation or sheathing. When terminating field wires, do not use more
lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
4. Pre-Test: Mounting Plate contains a SHUNT between adjacent “+” terminals to facilittate testing before device is attached.
Note: Shunt will open permanently when device is installed on mounting plate.
5. Verify appliance settings are correct for your application. Settings are shown in Fig. 3A, 3B. Factory settings are T3 (Code 3), 15cd.
6. Place the Eluxa appliance over the mounting plate. Engage TOP hook on mounting plate, then secure with screw at the bottom.
Use care to prevent speaker cone damage when driving the screw.
7. Align cover to the Eluxa appliance with strobe opening over LED lens. Then, snap the cover in place.
8. To remove the appliance, insert a small flat-bladed screwdriver into the bottom opening ½” as shown in Figure 5. Then lift off grille.
9. Accessories for Eluxa surface back box (Ceiling): ELSPKBB-R (Red); ELSPKBB-W (White).
Important: Do not fully back out terminal screws. Do not over tighten screws or terminals. Excessive torque may affect
operation. When using power tools, ensure the torque is set to the lowest setting available.
NOTE: Final acceptance is subject to Authorities Having Jurisdiction.
Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring
and/or locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits,
for example, may require special precautions to assure immunity from electrical noise (e.g. audio crosstalk).
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil
numérique de la classe A respecte toutes les exigences du Réglement sur le matériel brouilleur du Canada.
Any material extrapolated from this document or from Cooper Wheelock manuals or other documents describing the product for use in
promotional or advertising claims, or for any other use,including description of the product’s application, operation, installation and testing
is used at the sole risk of the user and Cooper Wheelock will not have any liability for such use. IN NO CASE WILL SELLER’S LIABILITY
EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
3/22

This manual suits for next models

1

Other Cooper Notification Fire Alarm manuals

Cooper Notification RSS-241575W User manual

Cooper Notification

Cooper Notification RSS-241575W User manual

Cooper Notification ST-C User manual

Cooper Notification

Cooper Notification ST-C User manual

Cooper Notification E60H-24MCCH User manual

Cooper Notification

Cooper Notification E60H-24MCCH User manual

Cooper Notification RSS-24MCC User manual

Cooper Notification

Cooper Notification RSS-24MCC User manual

Cooper Notification HS4 Series User manual

Cooper Notification

Cooper Notification HS4 Series User manual

Cooper Notification RSSR-2415C User manual

Cooper Notification

Cooper Notification RSSR-2415C User manual

Cooper Notification E70-24MCC Series User manual

Cooper Notification

Cooper Notification E70-24MCC Series User manual

Cooper Notification Wheelock Eluxa ELSTC-B User manual

Cooper Notification

Cooper Notification Wheelock Eluxa ELSTC-B User manual

Cooper Notification E70-24MCW Series User manual

Cooper Notification

Cooper Notification E70-24MCW Series User manual

Cooper Notification ET90-24MCWH Series User manual

Cooper Notification

Cooper Notification ET90-24MCWH Series User manual

Cooper Notification Wheelock MPS Series User manual

Cooper Notification

Cooper Notification Wheelock MPS Series User manual

Cooper Notification ET70-24MCCH Series User manual

Cooper Notification

Cooper Notification ET70-24MCCH Series User manual

Popular Fire Alarm manuals by other brands

Zeta ID2/4 installation manual

Zeta

Zeta ID2/4 installation manual

Brooks Firetracker FT420 Technical manual

Brooks

Brooks Firetracker FT420 Technical manual

NIBBLE NURIA user manual

NIBBLE

NIBBLE NURIA user manual

Simplex 4010 installation instructions

Simplex

Simplex 4010 installation instructions

FireClass FC421CP-I Fixing instructions

FireClass

FireClass FC421CP-I Fixing instructions

Simplex SafeLINC 4100 Operator's manual

Simplex

Simplex SafeLINC 4100 Operator's manual

VES Elite-RS H-Series installation manual

VES

VES Elite-RS H-Series installation manual

Elkron HPA700F installation manual

Elkron

Elkron HPA700F installation manual

FireClass FC503 user manual

FireClass

FireClass FC503 user manual

Siemens FC901 System Installation Instructions

Siemens

Siemens FC901 System Installation Instructions

Comelit 41CPE118 Technical manual

Comelit

Comelit 41CPE118 Technical manual

Radionics D7024 operating instructions

Radionics

Radionics D7024 operating instructions

System Sensor PS12/24ADA Series Installation and maintenance instructions

System Sensor

System Sensor PS12/24ADA Series Installation and maintenance instructions

Simplex 4100-1314 installation instructions

Simplex

Simplex 4100-1314 installation instructions

Global Fire JUNO NET installation manual

Global Fire

Global Fire JUNO NET installation manual

Panasonic EBL128 4550 overview

Panasonic

Panasonic EBL128 4550 overview

Teletek electronics SensoIRIS T110 IS Installation instruction

Teletek electronics

Teletek electronics SensoIRIS T110 IS Installation instruction

GE Interlogix NetworX NX-8 Installation and startup

GE Interlogix

GE Interlogix NetworX NX-8 Installation and startup

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.