Emerson EPW30-48A-E User manual

1
EPW30-48A-E Power Module
User Manual
1 Features
EPW50-48A-E power module (module for short) uses soft-switching
and input / output soft start-up technology. Its output can be
regulated through monitoring. Multiple modules can be paralleled to
share the load.
Dimensions (H × W × D): 88.2mm × 102.8mm (105.5mm with
enclosure) × 242.3mm (excluding socket dimension)
Weight: < 2.8kg
Mechanical stress: ETS300019-2
Safety: meet UL 60950-1,C22.2 NO. 60950-1, EN 60950-1
2 Environment
Operation temperature: -33 to 65°C;
Storage temperature: -40 to 70°C
Humidity: 5 ~ 95% (non-condensing)
Air pressure: 86 ~ 106 kPa
Altitude: < 4000m; Cooling: fan cooling
Vibration: random vibration in 2 ~ 500Hz in three orthogonal axes, 30
minutes in each direction
3 Electrical Specification
Input
Rated input: 200 ~ 240Vac / 115 ~ 130Vac
Input current: Max. 18.5A for single module
Rated frequency: 50 / 60Hz
Power factor: no less than 99% (rated operation condition)
Output
Rated output: 53.5Vdc (output range: 43.2 ~ 57.6Vdc)
Output power: 2900W 176Vdc ~ 300Vdc
1200W 90Vdc ~ 175Vdc
Efficiency: 92% (220Vac input and 53.5V/2900W output)
86% (110Vac input and 53.5V/1200W output)
Line regulation: ± 1%; Load regulation: ± 1%
Mains regulation: ± 0.1%
Psophemetic noise: 2mV
Broadband noise: 100mV (3.4kHz ~ 150kHz)
30mV (150kHz ~ 30MHz)
Output ripple (p-p): 200mV (0 ~ 20MHz bandwidth with load no less
than 1A)
Discrete noise: 5mV (3.4kHz ~ 150kHz)
3mV (150kHz ~ 200kHz)
2mV (200kHz ~ 500kHz)
1mV (500kHz ~ 30MHz)
4 Protection
Refer to Table 1 for the protection functions.
Table 1 Protection functions
Input overvoltage
protection
The module will send alarm and shutdown
when the input is above 305Vac; and recover
when the input drops down 300Vac
Input
undervoltage
protection
The module will send alarm and shutdown
when the input is below 85Vac; and recover
when the input increases above 90Vac
Output
overvoltage
protection
The protection point is 58.5 ~ 60.5Vdc. The
module will shutdown to lock upon the
overvoltage status. Restart the module after
the protection is removed
Current limit
protection
The module has current limit
protection:2900W (176 ~ 220Vac input);
1200W (90 ~ 175Vac input)
Short circuit
protection
The module has short circuit protection. The
module output 61A upon shortcircuit. The
module will recover when the fault is removed
Overtemperature
protection
The module will send alarm and shutdown
when the testing temperature is above 116°C;
and recovery when the temperature is under
110°C
The module will send alarm through alarm indicators upon input
over- and under- voltage, output over-voltage, and module fault.
5 Input And Output Connectors
EPW50-27A-E power module connects to user system through its
interfaces: AC input socket (FCI, 51939-021); DC output socket (FCI,
51939-022), which also serves as the signal interface. Their pin
locations are shown in Figure 1 and pin definitions are listed in
Table 2.
NGND L
DC-Pre-Charge DC+
PIN5
PIN16
PIN1
Figure 1 Pin location
Table 2 Pin definition
Pin Definition Function Contact sequence
AC input (FCI 51939-021)
See Fig.1 L Live line 2
See Fig.1 GND Protect earth 1
See Fig.1 N Neutral line 2
DC output (FCI 51939-022)
Pin1 Address bit 0 Address 3
Pin 2 Address bit 1 Address 3
Pin 3 Load share + Share bus 3
Pin 4 NC Not connected 4(reserved)
Pin 5 Current limit Current limit 3
Pin 6 Current limit Current limit 3
Pin 7 Address bit 2 Address 3
Pin 8 Address bit 3 Address 3
Pin 9 Load share - Share bus 3
Pin 10 +5V RS485 power+ 3
Pin 11 +5VGND RS485 power- 3
Free Datasheet http://www.datasheet4u.com/

Pin Definition Function Contact sequence
Pin 12 RS485- RS485- 3
Pin 13 Address bit 4 Address 3
Pin 14 NC Not connected 3 (reserved)
Pin 15 RS485+ RS485+ 3
Pin 16 Address GND Address GND 3
See Fig.1 Pre-charge Precharge 1
See Fig.1 DC+ Output 48V+ 2
See Fig.1 DC+ Output 48V + 2
See Fig.1 DC- Output 48V - 2
See Fig.1 DC- Output 48V - 1
Explanations:
1. Load share+ and Load share- are load-sharing signal cables when
multiple modules work in parallel. They should be well grounded and
shorter than 0.5m.
2. Pre-charge is the signal cable protecting pins upon online
removal/insertion.
3. GND is the module terminal connecting ground. Use yellow-green
bicolor cable with sectional area of 4mm2 or more. Connect it to the
ground reliably.
4. L and N are the live line and neutral line of AC input.
5. Address explanation: The address range of the module is within 0
~ 31. Address bit 0 ~ address bit 4 can be suspended or connect to
GND outside module. Suspending presents 0, and short to GND
presents 1. For example, if Address bit 0 is shorted with GND
outside the module and other addresses are suspending, the module
address is 1.
6. Pin5 and Pin6 are used to limit the output current and report
module model. The module will output according to the external
characteristic of EPW50-48A module and send 0x02 (EPW50-48A)
to the monitoring module when the pin5 and pin6 are shorted from
the back board on the subrack. Otherwise, the module will output
according to the external characteristic of EPW30-48A module and
send 0x01 (EPW30-48A) to the monitoring module.
6 Installation And Operation
The installation dimensions refer to Figure 2. Install the module using
the following procedures:
1. Make sure the handle of the module is open.
2. Put the module into the corresponding slot.
3. Push the module until the module interfaces contact the interfaces
on the backboard.
4. Push the handle until the module is completely inserted into the
subrack. At this point, the handle tilts up slightly locking the module
into the subrack.
5. Fix the screws on the handle using a screwdriver to finish the
module installation.
17.7 0.2
39.8 0.3 12.9 0.2
Positioring screw
7
7
5.6
230 0.3
Figure 2 Installation dimensions (mm)
Where a single module cannot meet the load demand, multiple
modules can be connected in parallel to share the load. In this case,
just connect all the output connectors and load sharing cables of the
modules respectively in parallel.
7 Maintenance
The module is hot-swappable. The damaged module can be
replaced during the system operation. Locate the module pins in the
backboard socket when replacing the module. Check whether the
pins are bent or skew when the module can not be inserted into the
socket properly.
Replacing the module: the module has a lock structure matching the
external chassis to lock the module in place. When taking out the
module, just pull up the handle on the bottom of the module front
panel and pull it out. When installing the module, insert the module
along the slot smoothly until the lock structure locks the module.
The whole unit should be replaced if maintenance is needed.
8 Troubleshooting
You may contact the nearest Emerson local sales office or service
center if the unit is faulty. Do not manage by yourself. Please return
the faulty unit to Emerson directly for repair. Table 3 is
troubleshooting of simple problems.
Table 3 Troubleshooting
Indicator Normal Abnormal Reason for
abnormal Actions
Green
LED On Off
No AC input, or input
fuse damaged, or
module failure, or all
protections
Red LED Off On Module shutdown
fault
Yellow
LED Off On
Module temperature
pre-alarm or the
monitoring module
controls the module
to switch off
Check loads,
input voltage,
input fuse, and
the fan of the
module;
Remove the
conditions
raising
protections
Caution
1. For continued protection against risk of fire, replace only with
same type and rating of fuse.
2. Double pole / neutral fusing.
3.An air breaker, advisably of 220V/32A or higher rating, should be
installed upstream the module.
4. Specifications are subject to change without notice.
5. Warranty period: 1 year.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District
518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn
Copyright © 2009 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to
change without notice.
Version V1.0
Revision date February 23, 2009
BOM 31012061
2
Free Datasheet http://www.datasheet4u.com/
Other Emerson Portable Generator manuals
Popular Portable Generator manuals by other brands

Gude
Gude GSE 5500 DSG Translation of the original instructions

Generac Power Systems
Generac Power Systems PowerPact 6561 Installation notes

Winco
Winco Home power HPS12000HE Installation and operator's manual

Gentech
Gentech GP6500I Operator's manual

Ingersoll-Rand
Ingersoll-Rand M 50 Users guide and maintenance manual

DUROMAX
DUROMAX DUROSTAR DS11000DX user manual

Hyundai
Hyundai HY3500Ei user manual

KFSSI
KFSSI Magravs 1-2016 user guide

MMD Equipment
MMD Equipment AirMan SDG125S-6A6 Instructional manual

Winco
Winco UL2FS2MP-1 Installation and operator's manual

DuroStar
DuroStar DS7000Q user manual

Generac Power Systems
Generac Power Systems 7 kW NG Installation guidelines