Equipment Control Terminals Operation / Function
R................................................ 24 VAC Transformer
RC.............................................. 24 VAC Cooling Transformer*
RH ............................................. 24 VAC Heating Transformer*
C................................................ 24 V Transformer Common
W/E............................................ Heating Stage 1 HP Aux/Em Heat Stage 1
W2............................................. Heating Stage 2 HP Aux/Em Heat Stage 2
Y................................................ Compressor Stage 1
Y2.............................................. Compressor Stage 2
G................................................ Fan Relay
L Terminal .................................. System Monitor Compatible with
Comfort Alert Diagnostics
O/B Terminal .............................. Changeover Relay Heat Pump
DHM .......................................... Dehumidication Relay / Connection
DHM2........................................ Dehumidication Relay / Connection
HM............................................. Humidication Relay / Connection
HM2........................................... Humidication Relay / Connection
R................................................ 24 VAC to Interface
1................................................. Data to/from Interface
2................................................. Data to/from Interface
C................................................ 24 VAC Common to Interface
RJ11 ........................................... Field conguration hook-up with RJ11
equipped conguration tool
+................................................. Voltage to Outdoor Sensor
S................................................ Outdoor Sensor Temperature Signal
-................................................. Voltage to Outdoor Sensor
Installation
*For 2 transformer systems, cut and tape o one transformer. If transformer
safety circuits are only in one of the systems, remove the transformer of the
system with NO safety circuits. If required, replace remaining transformer
with a 75 VA Class II transformer. After disconnecting one transformer, the
two commons must be jumpered together.