EMPHASER IQ System Controller User manual

TECHNICAL BRIEF - North America
IQ System Controller RMA Instructions
Table of Contents
IQ System Controller RMA Instructions..........................................................................1
Introduction............................................................................................................................2
Safety Instructions................................................................................................................2
Unboxing the new IQ System Controller unit................................................................3
Delete existing IQ System Controller using Enphase App........................................3
Power Down Sequence........................................................................................................4
Replace IQ System Controller unit...................................................................................4
Power up System..................................................................................................................5
Provision new IQ System Controller using Enphase App..................................................5
Enphase App, Devices & Array......................................................................................................................5
Provisioning the IQ System Controller .......................................................................................................... 5
Confirm new IQ System Controller is operating properly...................................................6
Box up the RMA IQ System Controller.....................................................................................7
Purpose .........................................................................................................................................................7
Material list ...................................................................................................................................................7
Instructions ...................................................................................................................................................7
Return Shipping Instructions.....................................................................................................9
Process .......................................................................................................................................................... 9
Labor Reimbursement..................................................................................................................9

IQ System Controller RMA
Instructions
2
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
Introduction
Follow these instructions to replace IQ System Controller. Enphase App and a login is required that
has accessto the system. Check before going onsite.
1.1
Delete existing RMA IQ System Controller using Enphase App
1.2
Power Down System
1.3
Replace IQ System Controller unit
1.4
Power up System
1.5
Provision new IQ System Controller using Enphase App
1.5.1
Enphase App, Devices & Array:
1.5.2
Provisioning the IQ System Controller
1.6
Confirm new IQ System Controller is operating properly
1.7
Box up and return RMA IQ System Controller
2.1 Packaging instructions for IQ System Controller RMA
3.1 Return Shipping Instructions
Safety Instructions
DANGER: Risk of electric shock. Risk of fire. Only qualifiedelectricians should install, troubleshoot, or replace the
IQ System Controller.
DANGER: Risk of electric shock. Risk of fire. Do not attempt to repair the IQ System Controller. Tampering with or
opening the IQ System Controller will void the warranty. If the IQ System Controller fails, contact Enphase
Customer Support for assistance at enphase.com/en-us/support/contact.
DANGER: Risk of electric shock. Do not use Enphase equipment in a manner not specified by themanufacturer.
Doing so may cause death or injury to persons, or damage to equipment.
DANGER: Risk of electric shock. Do not install the IQ System Controller without first removing AC power from the
photovoltaic system and ensuring that the DC switch on the Enphase IQ Batteries are off. Disconnect the power
coming from the photovoltaics and ensure thatthe DC switchon theIQ Batteries are off before servicing or installing.
DANGER: Risk of electricshock. Risk of fire. Do not work alone. Someone should be in the range of yourvoice or
close enough to come to your aid when you work with or near electrical equipment.
DANGER: Risk of fire. Do not allow or place flammable, sparking, orexplosive items near the IQ System Controller.
DANGER: Risk of electric shock. Inareas where flooding is possible, install the IQ System Controller at a height
that preventswater ingress.
WARNING: Risk of equipment damage. IQ System Controller is shipped and stored on its back.The upright
position is onlyneeded when installed.
WARNING: You must install the IQ System Controller only on a suitable wall using an Enphase wall-mount bracket.
WARNING: Before installing or using the IQ System Controller, read all instructions and cautionary markings in
this guide andon the equipment.
WARNING: Do not install or use the IQ System Controller if it has been damaged inany way.
WARNING: Do not sit on, step on, place objects on, or insert objects into the IQ System Controller.
WARNING: Do not place beverages or liquid containers on top of the IQ System Controller. Do not expose the
IQ System Controller to flooding.
✓
NOTE: Perform installation and wiring, including protection against lightning and resulting voltage surge, in
accordance with all applicable local electrical codes and standards.
✓
NOTE: Because IQ Battery is grid forming, you must install signage in accordance with NEC articles 705,
706,and 710.
✓
NOTE: Using unapproved attachments or accessories could result in damage or injury.
✓
NOTE: Install properly rated overcurrent protection as part of the system installation.

IQ System Controller RMA
Instructions
3
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
✓
NOTE: To ensure optimal reliability and to meet warranty requirements, the IQ System Controller must be
installed and/or stored according to the instructions in this guide.
✓
NOTE: The IQ System Controller is compatible only with the IQ Gateway or Envoy S-metered communications
gateway properly fitted with USB hub, USB radios, and production and Consumption/PCS CTs. The IQ Gateway
is required for operation of the IQ System Controller. Earlier versions of the Enphase IQ Gateway
communications gateway are incompatible.
✓
NOTE: The Enphase IQ System Controller is intended to operate with an Internet connection through the IQ
Gateway. Failure to maintain an Internet connection may have an impact on the warranty. See Limited
Warranty for full terms and services (enphase.com/warranty).
✓
NOTE: When replacing an Enphase IQ System Controller, you must replace it with an IQ System Controller of
the same type, with the same AC current rating.
✓
NOTE: Properly mount the IQ System Controller. Ensure that the mounting location is structurally suited to
bearing theweight of the IQ System Controller.
✓
NOTE: During use, storage, and transport, keep the IQ System Controller:
•Properly ventilated
•Away from water, other liquids, heat, sparks, and direct sunlight
•Away from excessive dust, corrosive and explosive gases, and oil smoke
•Away from direct exposure to gas exhaust, such as from motor vehicles
•Away from falling or moving objects, including motor vehicles. If mounted in the path of a motor vehicle, we
recommend a 91cm (36-inch) minimum mounting height.
•In a location compliant with fire safety regulations
•In a location compliant with local building codes and standards
✓
NOTE: While IQ System Controller provides capability for connection of a generator, it does not presently
support use withgenerators. Do not attempt to connect a generator until IQ System Controller is ready to
support a generator. This functionality is reserved for future use and will require an upgrade process to be
followed by a qualified electrician.
✓
NOTE: IQ System Controller is not suitable for use as service equipment in Canada.
Unboxing the new IQ System Controller unit
WARNING: Risk of injury. Take care when lifting. The IQ System Controller is heavy 38.5
kg (85 lbs). WARNING: Risk of injury and equipment damage. Avoid dropping the IQ
System Controller. Doing so may create a hazard, cause serious injury, and/or damage
the equipment.
When unboxing the new IQ System Controller unit, follow the instructions in the QIG to carefully
unbox the unit from the carton box without damaging it since the same box should be reused for
shipping back theold RMA’d IQ System Controller unit to Enphase.
Delete existing IQ System Controller using Enphase Installer App
When replacing an IQ System Controller on site (RMA) the old IQ System Controller must be deleted
using Enphase Installer App. There would be a Serial Number of IQ System Controller based on
which the RMA request is raised. Use theSerial No. to identify the IQ System Controller at site.
1. Don’t power down system until instructed later in the process.
2. Confirm that all the devices are powered ON.
3. Install Installer Enphase App using the below links:
oiOS
oAndroid
4. Log in to the application using Enphase Installer credentials.
5. Search for the system in the Enphase App.
6. Tap on the system and make sure the IQ System Controller to be deleted is part of the system.
7. Connect to the IQ Gateway using AP mode and Go to Step 4 (IQ Gateway Connectivity) to
confirm thedevice is connected to the IQ Gateway. Also make sure IQ Gateway is
connected to Enphase App either through Wi-Fi, Ethernet or Cellular.
8. Go to Devices and Array (Step 2) and select and delete IQ System Controller as
shown in images below. The device will be removed from Enphase App and will be
synced to ITK after IQ Gatewayreports the deletion.

IQ System Controller RMA
Instructions
4
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
Power Down Sequence
1. Turn off DC switches on all IQ Batteries.
2. Open IQ Battery breaker in IQ System Controller.
3. Open PV breaker in IQ System Controller.
4. Open the mains breaker.
5. Disconnect the grid source power supply (breaker in main panel).
6. Open Generator (reserved for future use) breaker.
7. Measure AC voltage on all the following terminals - PV/IQ Battery/Grid/Generator. It is safe
towork on IQ System Controller only when no voltage is detected on any of these terminals,
and you have ensured that all IQ Battery units have DC powered off.
Replace IQ System Controller unit
DANGER! Risk of electric shock. Check that all circuits connecting to the IQ System
Controller are de-energized before wiring. Follow below instructions in the sequence
mentioned.
1. To install the new IQ System Controller, the old IQ System Controller that was deleted
using ITK must be replaced.Follow the below steps to replace the IQ System Controller
unit.
a)
Disconnect all wires in a safe manner (the “AC power wires” shown in the figure
below need to be disconnected).
b)
Use handles (recommended) to remove old IQ System Controller from the wall.
c)
Remove the PV, IQ Battery, and Gen breakers, as well as CTs if installed in IQ
System Controller,to keep them for the new IQ System Controller.
2. Follow the steps in IQ System Controller Quick Install Guide to install the new IQ System Controller.
IQ System Controller
IQ Battery
IQ Gateway
IQ Gateway
IQ System Controller
IQ System Controller
IQ System Controller

IQ System Controller RMA
Instructions
5
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
Power up System
WARNING: Before energizing IQ System Controller, make sure that ALL IQ System
Controller connections areproperly installed, and conductors terminated.
1. Secure the deadfront to the IQ System Controller using the six reserved screws.
2. Ensure that all electrical circuits external to IQ System Controller are completed and
safe beforeenergizing IQ System Controller.
3. To commission the system, follow the instructions in the Enphase Installer Applicationand
the Commissioning Guide for energizing IQ System Controller. Key steps are also outlined in
section
1.5 below.
4. Energize the circuit feeding the IQ System Controller. If installed, turn the breaker feeding the
IQ System Controller tothe ON position.
5. Close and secure the door of the IQ System Controller.
Provision new IQ System Controller using Enphase App
1. Add and provision the new IQ System Controller as written in below steps.
Enphase App, Devices & Array
1. Go to ‘Devices and Array’ (step 2). Select ‘Add Device’ and enter the total count of IQ
System Controllerto be added in the system and Select ‘Done’.
2. Tap on ‘IQ System Controller’ and then manually scan the serial numbers of IQ
System Controller into Enphase App.
Provisioning the IQ System Controller
1. Ensure that the Enphase Energy System communications kit or COMMS-KIT-01 is plugged
into IQ Gateway USBports.
2. Ensure that the Enphase Mobile Connect Cell Modem is plugged into the IQ Gateway USB port.
3. Make sure you are still connected to IQ Gateway in AP mode. Go to ‘Provisioning Devices -
Step 5’and tap on ‘Provision Devices’.

IQ System Controller RMA
Instructions
6
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
4. Device provisioning will not be successful if both the COMMS-KIT-01 and cell modem are
missing or not plugged in.
5. Enphase App will begin provisioning the replaced IQ System Controller:
a. It will show the status of grid profile whether it is updated or not.
b. Only replaced IQ System Controller will be provisioned.
•During provisioning, the status flows as follows:
•Discovered / not discovered (Enphase App is able to discover the device using
Bluetooth Low Energy (BLE).
•Waiting for provisioning (The initial communication is being established.
Enphase App is sending network information to IQ System Controller using
BLE).
•Waiting for acknowledgement (IQ Gateway is trying to communicate to the IQ
System Controller usingthe wireless 2.4 GHz radio).
•Provisioned (IQ Gateway can communicate with the IQ System Controller).
•Once provisioning is complete, click Done.
Confirm new IQ System Controller is operating properly
1. Confirm that the IQ System Controller is communicating with the IQ Gateway by checking
Enphase App Step2: Devices & Array. IQ System Controller should display
“communicating” as follows:
The above step ensures that IQ System Controller is added successfully and is communicating.
IQ System Controller
IQ System Controller
IQ Battery
IQ Gateway
IQ Gateway
IQ Gateway Connectivity

IQ System Controller RMA
Instructions
7
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
Box up the RMA IQ System Controller
Repack the old RMA’d unit per the instructions below.
Purpose
This instruction is to be used to guide how to pack the IQ System Controller unit into the box.
Material list
Description
QTY
Carton box Packaging IQ System Controller 200G
1
Corrugated Bot tray Packaging IQ System Controller 200G
1
Central U Card IQ System Controller Packing
1
Bottom foam EPE Packaging IQ System Controller 200G
1
EPE_Top Foam Packaging IQ System Controller 200G
2
EPE_Solar Shield Foam Packaging IQ System
Controller200G
2
Paper corner guard Packaging IQ System Controller 200G
4
Instructions
1. Put the Bottom foam in the corrugated bottom tray as shown in the picture below:
2. Use the handles to put the IQ System Controller unit in the bottom Foam, as shown in the picture below:
3. Remove the two handles from the unit.

IQ System Controller RMA
Instructions
8
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
4. Put the two Solar Shield Foam under the two ends of solar shield as shown in the picture
below:
5. Put the two top foams on the top cover.
6. Cover the U-card and put the 4 corner guards at the 4 corners as shown in the picture below:
7. Cover the carton box, seal the box with tape and wrap with strap as shown in the picture
below:

IQ System Controller RMA
Instructions
9
© 2021 Enphase Energy Inc. All rights reserved.
October 25, 2021
Return Shipping Instructions
Process
1. Once the unit is back to the warehouse, contact Enphase Energy System support line 877-
797-4743 aboutthe IQ System Controller RMA issue. When given a menu of operations
during the call, select Option 4 and then Option 1 to get to the Enphase Energy System
Support team.
2. Enphase Energy System support team will ask customer the information shown in the table below.
3. The freight carrier will contact customer and set up an appointment for pickup.
4. The freight carrier will pick up the IQ System Controller RMA unit.
CONTACT INFORMATION
* Name
* Phone
* Email
PICKUP INFORMATION
* Company Name
* Address
* City/State
Shipping Date:
Shipping Hours
* Warehouse Phone:
Labor Reimbursement
Standard labour reimbursement rates apply.
Follow this link for more information on labor reimbursement.