ENDA EC442 User manual

ENDA EC442 UP/DOWN COUNTER
Thank you for choosing ENDA EC442 COUNTER.
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... +70°C (with no icing)
Rated pollution degree
TECHNICAL SPECIFICATIONS
1/5
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W48xH48xD87mm
Weight Approx. 210g (after packing)
Enclosure material Self extinguishing plastics
Supply 230V AC +10 -20 or 24V AC ±10 , 50/60Hz or optional 9-30V DC / 7-24V AC SMPS module.% % % ±10%
Power consumption Max. 5VA
2.5mm² screw-terminal connections
Wiring
Date retention
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for the EMC standard)
EEPROM (Min. 10 years)
EN 61010-1: 2001 (pollution degree 2, overvoltage category II)
EC442-E-07-R
* 48x48mm sized.
* 2x4 digits display.
* Easy to use by front panel keypad.
* Counting up and down with a 2 channel inputs having a 90° phase shift.
* Input frequency can be selectable.
* Prescaler factor can be adjusted between 0.001 and 9.999.
* Decimal point can be adjusted between 1. and 3. digits.
* Sensor type can be selected as PNP, NPN or Encoder.
* Single set-point control is made by a single relay output.
* Output can be energized continuously or just for a time interval of 0.1
to 999.9 seconds.
* Selectable functional reset input.
* Input offset feature.
* Parameter access protection on 3 levels.
* Easy connection by removable screw terminal.
* CE marked according to European Norms.
Count inpus (CP1, CP2) 2 channels (max. 9999Hz, 5V to 30V pulse)
Frequency (Hz) 25, 500, 1000, 2000, 5000, 7500Hz, 9999Hz (selectable by programming)
Minimum On and Off times
for pulses =25Hz20ms for f
f=500Hz1ms for
250ms for f=2kHz
100ms for f=5kHz
67ms for f=7,5kHz
50ms for f=10kHz
f=1kHz500ms for
INPUTS
OUTPUTS
Control output (OUT) Relay : 250V AC, 2A (for resistive load), NO+NC
Open collector output (S.S. OUT): Max. 30V DC, 100mA
Auxiliary power supply 12V DC, max. 50mA (without regulation)
Mechanical 30.000.000 operation; Electrical 300.000 operation
Life expectancy for relay
Note : Relay and S.S.OUT outputs are in synchronization . When OUT relay is energized S.S. OUT transistor goes into saturation.
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
80 up to 31 decreasing linearly 50 at 40 .% %°C °C
According to EN 60529 Front panel : IP65
Rear panel : IP20
ELECTRICAL CHARACTERISTICS
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Do not use the device in locations subject to corrosive and flammable gases.
PNP: Positive reset (5V to 30V pulse with adjustable pulse time between 2ms and 50ms)
NPN: GND terminal is connected to the RESET IN terminal.
Reset input
Order Code : EC442-
1
Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
PRESET UP/DOWN COUNTER
ENDA
PRESET
SET
EC 442
PV
SV
OUT
RESET

PV display (1) : 7.1mm
SV display (2) : 7.1mm
One red LED
4 digits, seven segment red LED
4 digits, seven segment yellow LED
Micro switch
( 2 ) SV display
Character height
( 3 ) Output LED
( 4 ),( 5 ),( 6 ),( 7 ) Keypad
( 1 ) PV display
2/5 EC442-E-07-R
(1) Counting value during run mode.
Parameter value or mnemonic parameter code during programming mode.
(3) Output LED.
(2) Preset value during run mode.
Parameter value, unit or mnemonic parameter code during programming mode.
(4) Increment key during run and programming modes.
Parameter selection key during programming mode.
(5) Decrement or reset key during run mode.
Parameter selection or decrement key during programming mode.
(6) Used for selecting optionsor digits to be changed.
(7) Used for selecting run or programming modes or for adjusting the parameter.
TERMS
Depth
DIMENSIONS
Panel cut-out
CONNECTION DIAGRAM
184-253V AC
50/60Hz 5VA
SUPPLY:
NOTE :
9
8
Neutral
Line
Fuse
F 100 mA
250V AC
Fuse should
be connected.
Switch
230V AC Supply
Cable size: 1,5mm²
ENDA EC442 is intended for installation in control panels. Make sure that the device is used only for intended purpose.
shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must
be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the
operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as
shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical
connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations.
The
1) Mains supply cords shall meet the requirements of IEC 60227
or IEC 60245.
2) In accordance with the safety regulations, the power supply
switch shall bring the identification of the relevant instrument
and it should be easily accessible by the operator.
Note :
Holding screw 0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
Connection
cables
For removing the device from
the panel:
- While pressing both side of
the device in direction 1, push it
in direction 2.
Panel
Note: 1) While panel mounting, additional distance required for
connection cables should be considered.
2) Panel thickness should be maximum 9mm.
3) If there is no 100mm free space at back side of the device,
it would be difficult to remove it from the panel.
Flush mounting
clamp
51mm
80mm
45 mm
+0.6
45 mm
+0.6
1
2
1
PRESET UP/DOWN COUNTER
ENDA
PRESET
SET
EC 442
PV
SV
OUT
RESET
58mm
48mm
PRESET UP/DOWN COUNTER
ENDA
RESET
PRESET
SET
EC 442
PV
SV
OUT
EC442-SM
PRESET UP/DOWN COUNTER
RESET IN
S.S. OUT
CP2 INPUT
CP1 INPUT
GND
+12V 30mA
7
2
3
4
5
6
8
9
10
11
12
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
OUT1
AC 250V 2A
RESISTIVE LOAD
9-30V DC / 7-24V AC
±10 % 5VA
EC442-230VAC
PRESET UP/DOWN COUNTER
EC442-24VAC
PRESET UP/DOWN COUNTER
RESET IN RESET IN
S.S. OUT S.S. OUT
CP2 INPUT CP2 INPUT
CP1 INPUT CP1 INPUT
GND GND
+12V 30mA +12V 30mA
7
2
3
4
5
6
8
9
10
11
12
7
2
3
4
5
6
8
9
10
11
12
ENDA ENDA
INDUSTRIAL ELECTRONICS INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 5VA
SN: XXXXXXXXX SN: XXXXXXXXX
OUT1 OUT1
AC 250V 2A
RESISTIVE LOAD
AC 250V 2A
RESISTIVE LOAD
24V AC
50/60Hz 5VA
±10

SET
PRG
RESET
SET
Run mode
Counting value is on the upper display.
Preset value is on the lower display.
Preset value
See NOTE 1. for adjustment.
OutP.
oPti.
dýsP.
oPti.
SECU.
oPti.
outP.
typE
out
tý.
dEcý.
Pnt.
oFFS.
dAtA
dýsP.
CAL.
Calibration (Prescaler) value can be adjusted between
0.001 and 9.999. Counter multiplies the number of pulses
by the prescaler value and the result is displayed on the
screen
See NOTE 1 for modification.
Decimal point can be adjusted between 1. and 3. digits.
If desired, decimal point is not included.
See NOTE 2 for modification.
Offset value can be adjusted between 0 and 5000.
It means counter starts counting from the offset value when
it is reset.
See NOTE 1 for modification.
ýnP.o
SECU.
out.o.
SECU.
dýs.o.
SECU.
SECU.
codE
Cntr.
r.SEt
def.
SEt
Access code for entering security option menu.
This parameter should be 1111.
See NOTE 2 for modification.
PARAMETER TABLE
25
Hert
500
Hert
1000
Hert
2000
Hert
5000
Hert
7500
Hert
Enco.
0.010
sec.
0.020
sec.
0.050
sec.
PnP
0.005
sec.
nPn
0.002
sec.
dirE. oPPo.
inPt.
typE
SEnS.
tyPE
r.est
puls
inPt.
Frq.
Cntr.
dir.
CP1.U.
CP2.d.
CP1.U.
CP2.U.
CP1.U.
CP2.G.
CP1.U.
CP2.r.
UP
Ph-4
UP.dn.
Ph-1
UP.dn.
Ph-2
ConF.
4
ConF.
1
ConF.
2
ConF.
5
ConF.
6
ConF.
7
ConF.
8
ConF.
9
ConF.
10
outP.
typE
out
ti. 000.0
INPT. oPTi.
OuTP. oPTi.
dEci.
Pnt.
diSP.
CAL.
oFFS.
dAtA
disP. oPTi.
0 0.0
0.001 ......... 9.999
0......... 5000
inP.o
SECU.
diS.o.
SECU.
def.
SEt
Out.o.
SECU.
nonE
Prog.
no
Prog.
yES
nonE
Prog.
no
Prog.
yES
nonE
no
Prog.
no
yes
Prog.
yES
SECU.
codE 1111
no
PAnE.
r.SEt
r.SEt
inP.t.
SECU. oPTi.
Cntr.
r.SEt
9999
Hert
.......... 999.9
0.00
Prog.
yES
Prog.
yES
Prog.
yES
= No menu is seen.
= No menu is seen.
= No menu is seen.
= Counter can not be reset.
= Both RESET input and the key can
be used for resetting.
See NOT 2. for modification.
See NOT 2. for modification.
See NOT 2. for modification.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
= Menu is seen but can not be programmed.
= Menu is seen and programming is possible.
nonE
nonE
nonE
no
Prog.
no
Prog.
no
Prog.
no
both
= Counter can be reset by key.
= Counter can be reset by the RESET input.
See NOT 2. for modification.
PAnE.
r.SEt
r.SEt
inP.t.
PARAMETER MODIFICATION DIAGRAM
To modify non-mumerical parameters, hold key and use keys.
1.000
1.000
1.000
1.010
1.000
9999
1000
P.SEt
1000
ýnPt.
typE
Cntr.
dýr.
ýnPt.
Frq.
SEnS.
tyPE
R.set
puls
ýnPt.
oPti.
both
0.000
Selected
numerical
parameter
NOTE 1
NOTE 2
3/5 EC442-E-07-R
While leaving the programming mode,
no = All the modifications are saved.
Yes = Default values are set to parameters.
See NOT 2. for modification.
The minimum pulse duration of the external RESET
input can be selected.
See NOTE 2 for modification.
if key is pressed while holding key, the
programming mode is enabled.
There are seven different
input types. A schematic diagram of
counting modes according to the input
types is at the next page.
See NOTE 2 for modification.
Input frequency can be selected.
See NOTE 2 for modification.
A type of sensor can be selected.
See NOTE 2 for modification.
Counting direction can be
selected dirE. or oPPo. A
schematic diagram of counting
directions according to the
selected input types is at the
next page.
See NOTE 2 for modification.
There are nine different output types. A schematic diagram
of output types is at the next page.
See NOTE 2 for modification.
Output energizing time can be adjusted between 0.1 and
999.9 seconds.
If it is made 0.0, output is energized continuously when
P.SEt value is reached.
See NOTE 1 for modification.
Holding key the value of the selected parameter is seen on the display. While holding key, the value of the selected parameter can be changed by
using keys. In order to reset all the digits, first press and hold key. And then, press both and keys together.
PRESET
PRESET
RESET
RESET
RESET
RESET
RESET
PRESET PRESET PRESET PRESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
RESET
SET
PRESET RESET
SET SET
PRESET
SET
PRESET
SET
SET SET
RESET
RESET
SET
SET
RESET

OUTPUT TYPES
While counter value is equal
to preset value, OUT
becomes active.
While counter value is lower
or equal to the preset value,
OUT is active.
While counter value is
greater or equal to the
preset value, OUT is active.
C o u n t
input CP1
C o u n t
input CP2
C o u n t
input CP2
C o u n t
input CP2
ýnPt.
tyPE
Cntr.
dýr. dýrE.
CP1.U.
CP2.d.
CP1.U.
CP2.U.
UP
Ph-4
UP.dn.
Ph-1
UP.dn.
Ph-2
CP1.U.
CP2.G.
d i r c t i o n
input CP2
CP1.U.
CP2.r.
C o u n t
input CP1
Count
input CP1
Count
input CP1
C o u n t
input CP1
C o u n t
input CP1
H
H
H
H
H
H
H
H
H
H
H
H
L
L
L
L
L
L
L
L
L
L
L
L
n
n
n
n
n
n
n
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+1
n+2
n+2
n+2
n+2
n+2 n+2
n+2
n+2 n+2
n+2 n+2
n+3
n+3
n+3
n+3
n+3 n+3
n+4 n+4
n+5
n+4
n+3 n+3 n+3
n+5
n+5
n+4
n+6
n+6
n+7
n+7
n+8
n+3 n+3
n+3
n+4
n+4
C o u n t
input CP2
Count
input CP2
Count
input CP2
Count
input CP2
Count
input CP2
Ga t e
input CP2
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
Count
input CP1 H
H
L
L
direction
input CP2
DISPLAY
Count
input CP1
Count
input CP1
C o u n t
input CP1
C o u n t
input CP1
C o u n t
input CP1
Count
input CP1
H
H
H
H
H
H
H
H
H
H
H
H
L
L
L
L
L
L
L
L
L
L
L
L
n
n
n-1
n-1
n-1
n-2
n-2
n-2
n-2
n-3
n-3 n-3
n-4 n-4
n-5
C o u n t
input CP2
C o u n t
input CP2
Ga t e
input CP2
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
oPPo.
C o u n t
input CP1 H
H
L
L
DISPLAY
n
n
n
n
n
n-1
n-1
n-1
n-1
n-1
n-2
n-2
n-2
n-2 n-2
n-2 n-2
n-3
n-3
n-3
n-4
n-3 n-3 n-3
n-4
n-5
n-5
n-6
n-6
n-7
n-7
n-8
n-3
n-4
n-3
n-4
INPUT TYPES
Cntr.
dir. Cntr.
dir.
= , , = , ,
==
dirE. oppo.
= , , ,
Conf.
1
Reset
9,999
Preset
0
Out
Conf.
2
Reset
9,999
Preset
0
Out
Conf.
4
Reset
9,999
Preset
0
Out
Conf.
5
Reset
9,999
Preset
0
Out
Conf.
6
Reset
9,999
Preset
0
Out
Conf.
7
Reset
9,999
Preset
0
Out
Conf.
8
Conf.
9
Conf.
10
Reset
9,999
Preset
0
Out
-999
Reset
9,999
Preset
0
Out
-999
Reset
9,999
Preset
0
Out
-999
4/5 EC442-E-07-R
inPt.
typE
inPt.
typE
inPt.
typE CP1.U.
CP2.d.
CP1.U.
CP2.U.
CP1.U.
CP2.U.
CP1.U.
CP2.G.
CP1.U.
CP2.G. CP1.U.
CP2.r.
UP
Ph-4
UP
Ph-4UP.dn.
Ph-1
UP.dn.
Ph-2
= , , ,
inPt.
typE
CP1.U.
CP2.d.
CP1.U.
CP2.r.
UP.dn.
Ph-1
UP.dn.
Ph-2
Adjusting to a value between 0.1 and 999.9 seconds, a pulse output is obtained.
Adjusting to 0.0, a continuous output is obtained.
out
ti.
out
ti.
UP COUNTER DOWN COUNTER UP / DOWN COUNTER
(Autoreset and
Display hold)
(Delayed
Autoreset
and HOLD)
(Delayed
Autoreset )
(Autoreset )
(HOLD )
For PNP sensor, counter is triggered at the rising edge of the pulses.
For NPN sensor, if you select
above diagram for Cntr.dýr. DýrE replaces with Cntr.dýr OPPo. .
ýnPt.tyPE CP1.U. CP2.r. ,
NOTE :
For NPN sensor counter is triggered at the falling edge of the pulses.
1)
2)

TERMINAL CONNECTIONS
NOTE: NPN PROXIMITY SWITCH connection is the same as PNP PROXIMITY SWITCH connection.
TYPICAL SENSOR CONNECTIONS
PNP PROXIMITY SWITCH
PNP PROXIMITY SWITCH GND
+ 12V
+ 12V
GND
OUT
OUT
2
3
4
5
6
7
8
9
10
11
12
PNP PROXIMITY SWITCH
GND
OUT
+ 12V
2
3
4
5
6
7
8
9
10
11
12
GND
+ 12V
A OUT
B OUT
ENCODER
2
3
4
5
6
7
8
9
10
11
12
Terminal descriptions
2 : Solid state out (Max 30V 100mA, open collector NPN).
3 : Reset input.
4 : Input for clock pulse 2 (Max 30V 7.5kHz).
5 : Input for clock pulse 1 (Max 30V 7.5kHz).
6 : GND.
7 : +12V 30mA auxiliary power supply output for sensors.
8,9 : SUPPLY inputs.
10,11,12 : Relay contacts (Max 2A 250V AC).
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.
Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL-TÜRKÝYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr 5/5 EC442-E-07-R
EC442-230VAC
PRESET UP/DOWN COUNTER
INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 5VA
OUT
AC 250V 2A
RESISTIVE LOAD
RESET IN
S.S. OUT
CP2 INPUT
CP1 INPUT
GND
+12V 30mA
7
2
3
4
5
6
8
9
10
11
12
ENDA
SN: XXXXXXXXX
230V AC supply
230V AC supply
230V AC supply
Switch
Switch
Switch
Cable size: 1,5mm²
Cable size: 1,5mm²
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse
F 100 mA
250V AC
Fuse
F 100 mA
250V AC