pressed continuously for 6 times within 10 seconds. The wireless status LED1 flashes at a frequency of
0.5hz to enter the wireless pairing state.
100ms cycle sends the automatically generated synchronization code and address code of the
internal unit (the configured number of internal units plus 1 is the sending address), no reply is received
within 30 seconds, the wireless status light is off, and the pairing fails.
After receiving the reply, the wireless module synchronization code is configured according to the
automatically generated value. After 100MS, the query instruction is sent to the internal unit of the
matching address in a loop. No reply is received within 30 seconds, and the wireless status light is off
and the pairing fails.
After receiving the reply, the pairing is successful, the number of the configured internal unit is
increased by 1, and the negative code is saved, and the wireless status light is lit up.
This cycle pairs multiple internal units, up to 32 internal units.
Reset pairing method:
When the power is on, the LED3 of the power supply lamp is lit up. Press the pairing button (SW1)
for 10 times continuously within 10 seconds to cancel the pairing;
Wireless communication query:
After power on, a pair is detected and the wireless status light is always on. Otherwise, the light
will go out and the module will be in the waiting state
;
When the internal unit requires the pump to be turned on, the pump shall be powered on and the
corresponding indicator LED2 shall be on, otherwise off
;
Internal unit wireless matching (one water pump plate should be matched with one internal unit
plate)
Power on, press the remote control switch button continuously for 6 times within 10 seconds, the
buzzer will sound, and wait for receiving the pairing information. If the pairing fails within 30 seconds,
the pairing failure will be reported, and the digital tube will display "09".
IV. Daily maintenance
1. Cleaning
External cleaning:Cleaning machine must be cut off the power, with a wet cloth dipped in a small
amount of neutral detergent gently wipe. Do not use gasoline or acid solution, alcohol, and dry with
a dry cloth.
Fin heat exchanger cleaning:The evaporator fins can be cleaned with a hard nylon brush. Vacuum
cleaners must be used before scrubbing. If there is compressed air, the fin heat exchanger can be
cleaned with high-pressure air tube.