ENSENERGY E09/12ADH User manual

/2 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
SAFETY PRECAUTIONS
⚠DANGER !
•DO NOT ATTEMPT TO INSTALL THIS UNIT YOURSELF. "
•THIS UNIT REQUIRES A QUALIFIED INSTALLER. "
•DO NOT ATTEMPT TO REPAIR THE UNIT YOURSELF. "
•THIS UNIT HAS NO COMPONENTS WHICH YOU CAN REPAIR. "
•OPENING OR REMOVING THE COVER WILL EXPOSE YOU TO DANGEROUS VOLTAGES. "
•TURNING OFF THE POWER SUPPLY WILL PREVENT POTENTIAL ELECTRIC SHOCK. "
⚠WARNING
"
INSTALLATION WARNINGS "
•Be sure to ask a dealer or a store specialized in electrical work to install the Air to Water Heat Pump. "
•The Air to Water Heat Pump should be installed by a suitably qualified installer, if not; this may lead to
problems such as water leaks, electric shock, fire, etc. "
•Ensure the correct grounding procedures are applied when installing the Air to Water Heat Pump. "
•Do not connect the ground wire to gas pipes, water pipes, lightning rods or telephone ground wires. "
•Should the Air to Water Heat Pump be improperly grounded, this could lead to an electric shock. "
•Serious damage can occur if there is water leak. Therefore, the Hydro Unit is recommended to be
installed in a room with waterproof flooring and drainage systems. "
•Products and parts to be used in combination with this product must be specified products and parts
that meet prescribed specifications. If unspecified products or parts are used, a failure, smoke, fire, or
electric shock may be caused. !
"
OPERATION WARNINGS !
•Avoid injury or damage to the outdoor unit by never inserting fingers or sticks into the air outlet or air
inlet of the outdoor unit, during operation the fans run at a high speed. "
•Should you notice something unusual with the Air to Water Heat Pump (such as a burning smell or
weak heating power), immediately turn offthe main switch and circuit breaker from the main power
supply to stop the Air to Water Heat Pump, and contact the dealer. "
•If there is a suspected problem with the operation of the Air to Water Heat Pump, continuous
operation is not recommended, operational failures may lead to machine breakdown, electric shock, a
fire, etc. "
"
WARNINGS AT MOVEMENT AND REPAIR "
•Do not attempt to move or repair the unit yourself. "
•Due to the presence of high voltage, removal of any covers may result in an electric shock. "
•Should there be any requirements for the Air to Water Heat Pump to be moved, always consult the
dealer or qualified installer. "
•Should the Air to Water Heat Pump be improperly installed, it may lead to electric shock or fire. "
•Whenever the Air to Water Heat Pump requires repair, request assistance from the dealer. "
•Should the Air to Water Heat Pump be improperly repaired, the result may lead to electric shock or
fire. "

/3 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Specification !
Notice !
•Save this manual for future reference.!
•In order to use this product better and safer, please read this manual carefully before installation and
initial operation.!
•Children should not play with nor operate this appliance.!
•This appliance must be installed in accordance with Australian wiring regulations.!
•This appliance must be fitted with an isolating switch from the supply mains having a contact
separation in all poles that provides full disconnection under over voltage category III conditions,"
in accordance with Australian electrical wiring regulations.!
•The battery must be removed from this appliance at the end of its operating life and disposed"
of safely.!
•Regular cleaning of the evaporator fin coil is recommended for good air flow.!
•Improper installation of this appliance may cause damage and danger. It should be installed by"
a qualified and experienced technician/s.!
•The installation of this appliance must comply with the power requirements stated on the rating label
or the parameter table in this manual.!
•The power supply should be equipped with separate leakage protection. The power supply cable
should be consistent with the power requirements of this appliance.!
•The unit must be grounded safely in accordance with Australian regulations.!
•The wiring must comply with the wiring chart.!
•Do not install the unit close to flammable or explosive materials, or naked flames.!
•A filter in the water supply inlet is recommended and should be checked/cleaned periodically. !
Model Nomenclature
E
09
A
H
H
M
S
Brand
Capacity
Source Type
Compressor
Type
Unit Type
Structure type
Power Type
E=ENS
09=09*1000W
A=Air source
A= AC on/off
H=Heat pump
M=Monoblock
S=Single phase
W=Water source
D=DC inverter
S=Swimming
pool
SO=Split outdoor
T=Three phase
S=Solar source
E=EVI
D=Dryer
SI=Split indoor
D=Double source
H=Hybrid
A=All in one

/5 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Installation
Unit installation positioning !
•This appliance requires good air flow through the fin coils for maximum efficiency. Also, hotter outside
air temperature in cooling mode and colder outside air temperature in heating mode will reduce
performance of the unit. Therefore, the hot/cold discharged air in cooling/heating modes from the unit
should not be allowed to return back to the air inlet. !
Please keep enough space around the unit for repairs and maintenance. !
Installation considerations:
•The installation position should have good ventilation.!
•The installed unit should not make extraneous noises or rattling sounds.!
•Try to minimise direct sunlight onto the unit.!
•Water from rain or defrost mode will be discharged through a drain hole in the base plate. 2.5 The
outlet air position should not face into a prevailing wind direction or this will reduce performance
efficiency.!
•Try to site the unit so the outlet air does not discharge directly onto a fence or towards a neighbour.!
•The installation position should not be located next to flammable or explosive materials, or naked
flames.!
•The unit should be protected from oil (such as engine oil in a plant room), salt (such as sea spay or
salty air) and/or sulphides (that may be present in the air from a thermal spring). !
•The unit should ideally be installed on the ground, preferably on a concrete plinth. Alternately, the unit
can be installed on a balcony, ledge or roof provided there is a suitable load-bearing platform in place
capable of supporting the weight of the unit and not transmitting vibration noise. !

/6 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
•There should be a drainpipe or channel from the unit to take the condensate water.!
•Do not install the control panel in a bathroom because the wet conditions may cause the control panel
to malfunction. !
Side fan type installation space requirements: !
Hot water storage tank and buffer tank installation site selection
•The hot water storage tank and buffer tank can be installed indoors or outdoors.!
•The storage and buffer tanks should be installed on a concrete plinth and comply with local Standard
so the tanks remain upright and cannot fall over.!
•Some building codes require seismic restraint. Consider restraining the storage and buffer tanks with
stainless steel bands. !
The storage tank and buffer tank installation
•Ensure the specification label is visible.!
•A pressure limiting valve must be fitted.!
•A cold water expansion control valve may be fitted.!
•A pressure limiting valve must be fitted to ensure the incoming water is no greater than 500 kPa.!
•A cold water expansion control valve may be required in areas with mineralised water. Check your
local plumbing code or check with your plumber. If required, this should be set at 700 kPa.!
•A pressure and temperature relief valve is supplied with the hot water storage and buffer tanks and is
set at 850 kPa.!
•A tempering valve set at 50 deg C is required by Australian regulations for hot water supply to
bathrooms.!
•A drain must be included to allow full and complete draining of the tank.!
•It is recommended that the hot water outlet pipes are fully insulated with weather proof insulation such
as Armaflex or equivalent.!
•The hot water outlet pipes should be angled down by 15 deg C minimum for the first 250mm after
exiting from the hot water storage or buffer tanks. This will create a heat trap that will avoid any
thermal siphoning from the tanks.!
•Fill the hot water storage tank by opening the hot water taps and opening the cold water inlet valve to
allow air in the water lines to be expelled. Close each hot water tap as the water flow becomes free of
air. Check all pipes for any signs of leaks. Power should not be turned on until the tank is completely
filled with water.!
•Fill the buffer tank and hydronic closed loop system with pure water (eg rainwater) and an inhibitor (eg
Gendex 100ml per 50 litres) to prevent mould. Glycol should be added if there is any likelihood of
freezing conditions. An alkaline treatment to rainwater is recommended to bring the pH level up to 7.0
such as dolomite. Such steps will give the longest life to the components of the hydronic system.
NOTE: Ensure all air is purged. !

/7 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Installation of indoor heating and cooling equipment
•Indoor heating and cooling equipment such as fan coils, radiator heating or floor heating, should be
installed in accordance with relevant regulatory requirements, engineering design drawings, and the
manufacturer's installation instructions.!
•Use soft connectors to connect the unit with the indoor heating and cooling equipment. !
•Install condensate water drain pipes to the indoor fan coil units with smooth drainage lines for the
condensate water to flow easily. !
Water pipe connections
•Water pipe material should be heat resistant and rust-proof. This can be stainless steel, copper,
aluminium, hot water PPR pipes, etc according to relevant standards.!
•The choice of pipe size should match the heat pump inlet and outlet with the pipework"
of the system, and follow the relevant standards. !
•The hot water storage and buffer tank drain port and pressure and temperature relief valve should be
installed to allow for proper drainage according to relevant standards. !
•The hot water storage and buffer tank must be installed with an isolating valve to allow for
maintenance. !
•The water pipes should be arranged with smooth bends to reduce pressure loss in the system.!
•The water main inlet should be fitted with a one-way valve and isolating valve, or Duo valve. !
•The water main inlet should be fitted with a water filter (note the Duo valve may have a water filter).!
•The water outlet of the unit should be connected to the solar flow port on the hot water storage tank
with solar return port connected to the water inlet of the unit. !
•The hydronic closed loop of the buffer tank should be connected to a manifold that is in turn
connected to the hydronic flow and return ports of the buffer tank. The buffer tank should be
connected to the unit via 3 way valves in the same way as the hot water storage tank is connected
(refer schematic diagrams in Section IV). !
•After the water flow and return pipes are connected to the hot water storage tank and buffer tank, the
system should be tested at water supply pressure to ensure that the system does not leak. If
satisfactory, then insulate all hot water fittings and complete the installation. 6.11 In order to discharge
all air from the hydronic water circuit, an automatic exhaust valve should be installed at the highest
point. !
•An expansion vessel and automatic stop valve should be installed into the hydronic system and
located indoors in areas with sub zero temperatures to prevent possible cracking of the water pipes
and valves when not in use in the winter.!
•It is recommended that a water thermometer and water pressure gauge be installed in the flow and
return lines to the unit to monitor key operational parameters. !
•Note: !
•The water pipes should be subjected to a pressure test before operation of the hydronic system.!
•The water pressure of the hot water and hydronic system should not exceed 500kPa. !
•The Monoblock unit allows for water temperature up to 60 deg C. !
•Water should drain from the pressure and temperature relief valve to a drainage pipe. !
•The pressure and temperature relief valve should be periodically exercised by gently pulling the lever
up. This will help to remove possible accumulation of calcium carbonate, and ensure that the valve is
working properly. !
•Install one-way valves, filters, pressure and temperature relief valves, and any other plumbing fittings
consistently with the marked flow direction and in accord with relevant standards. !

/8 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Installation of the temperature detector
•Firstly, daub heat conductive silicone onto the front of the temperature sensor, then insert it into the
temperature detector.!
•Next, push the temperature sensor with the pin through to the end of the temperature detector, then
mark the level of the pin on the temperature detector. !
•Finally, seal the inlet of the temperature detector with silicone to keep the ambient air isolated so it
does not affect the reading of the sensor. !
Electrical wiring
•The unit should use dedicated power supply with supply voltage and current corresponding with rated
specification on the technical label.!
•The power cable of the unit must support the maximum starting current requirements. !
•The unit power supply circuit must have a grounding wire, which should connect with a reliable and
effective external ground wire!
•Wiring must be installed by qualified technicians with reference to the circuit diagram. !
•The layout of power lines and signal lines should be neat, rational and strong with weak lines
separated so they cannot interfere with each other.!
•When power lines and control lines are parallel, the wires must be placed inside an insulating tube,
with appropriate distance between the lines.!
•For electrical connection of the unit, take the following wiring through the wiring hole set into the
electrical box, then connect to the appropriate terminals in the electrical box according to wiring
diagram: !
· Power line"
· Remote control three core lines"
· Electric heater power line"
· Hydronic circulating water pump control power line"
· Water tank electrical boost element"
· Temperature sensing line"
· Solar collector evacuated tubes temperature sensor line (optional) · Solar collector evacuated
tubes circulating pump (optional)"
· Hydronic application equipment"
· Unit lines !

/9 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Electrical Wire Selection - Warning
•The internal motor protector does not protect the compressor against all possible conditions. Please
be sure that the system is properly earthed when installed in the field. !
•To avoid fire, electric shock and other accidents, only use power supply voltage indicated on the label.!
•To protect the power lines, they should be fixed appropriately so that they cannot become damaged
and people cannot trip over them. Pay particular attention to the positioning and operation of electrical
plugs, which should be easily plugged into the socket.!
•Do not overload wall plugs or the power cable line. Overloading may cause fire or electric shock.!
•Check to ensure your electrical socket is appropriate for the power load and is properly grounded.!
•Specification Table of Power Code (single unit): !
E09/12/15-ADH
E18/21/24-ADH
Note:"
(1) Use H05RN-F or H07RN-F insulated copper wire for above wiring."
(2) If the power cord required is longer than the maximum line length provided, please check with your
supplier."
(3) If the power supply cord is damaged, it shhould be replaced by the manufacturer, its authorized
service agent or a delegated qualified person in order to avoid a hazard. !
Trial operation by qualified installer
-Pre-start-up checks:"
· Check the whole pipe system. Ensure the water volume in the system is full and the air is exhausted
completely. Check whether the water valves are open throughout the system."
· Check the thermal insulation of the pipe work, make sure relevant pipes are appropriately lagged."
· Check the power supply and distribution system. Check whether the power supply voltage is normal,
the power distribution accessory screws are tight, supply power complies with"
the wiring diagram and unit specifications and the wiring is properly grounded."
· Check the air cooled water chiller. Make sure all screws are tight. Check that the signal indicator light
(green) of the unit control panel is illuminated normally and the fault indicating lamp (red) is illuminated."
· Connect pressure gauges to the suction Schrader valves in preparation for checking the refrigerant
pressure during operation. Disconnect them when testing is satisfactory.!
-Trial operation"
· Press on/offon the remote controller, the water pump and fan should start immediately. The
compressor should start shortly after. Observe and determine if there is any abnormal sound during
operation. Stop to check the unit if there is abnormal sound. The unit should continue to run only when
there is no abnormal sound."
· Check whether the cooling system pressure is normal."
· Check whether the input power and current of the unit are within the parameters set out"
in this manual. If not, stop the unit and check it."
· Observe whether the outlet water temperature is normal. !
-The parameters of the remote controller have been pre-set at the factory. We recommend that you
leave these parameters as set. !

/12 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
D: Heating and cooling mode plus domestic hot water installation drawing !
Note: !
Some models include the circulating pump and electrical 3-way valve inside already
Some models include water pump and 3-way
valve inside the main unit already
COLD WATER IN
WATER TANK
HOT WATER OUT
Mainfold
Connect to floor heating
Hot water supply to water tank and room heating system
Return water from room heating system
Return water from water tank
The connection sequences in this drawing maybe
different than the real unit, please follow the label of
the real unit to finish the connection

/13 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Maintenance and repair
-Note !
•The water filter should be cleaned periodically. Clean it after the first 3 months to check for sediment
build-up and depending on the mineral content of your water determine how often the filter should be
cleaned. Regions with pure mountain water will require less maintenance than those with mineralised
water. !
•Try to maintain a dry, clean and well vented environment for the outdoor unit. Check the fin coils after
the first 3 months for dirt build-up and depending on the air environment, determine how often the
evaporator coils should be cleaned to maintain high exchange efficiency.!
•Check whether the working pressure of the refrigerant system is normal. Repair and change the parts
if there's any abnormality.!
•Check whether the electrical parts are performing normally or if there is any unusual odour. Repair and
change the parts if there's any abnormality.!
•Inspect the unit if it stops for a long time. Discharge all the water in the pump and throughout the pipe
route in case of breakdown to the water pump and pipe caused by frost and ice. Discharge the water
from the water pump and heat exchanger. Refill water into the system before the unit is powered on
again.!
•Cut power to the outdoor unit before any maintenance is undertaken. !
Fault Code
•If the failure occurs, the related fault code will be displayed on the panel. The unit could be stopped
automatically or cannot be started again to avoid making any danger or personal injury. !
•⚠Please call your local service provider or contact the factory telling them the fault code. The fault
need to be handled by professional technicians, The personal injury would be caused by any
Er00
Normal
Er01
IPM module failure
Er02
IPM module loading parameters failure
Er03
IPM module over current
Er04
DC bus over voltage
Er05
DC bus over voltage 1
Er06
DC bus under voltage
Er07
Motor over speed
Er08
Motor zero speed abnormal
Er09
Motor phase loss
Er10
Motor start failure
Er11
MCE abnormal
Er12
Motor over speed 1
Er13
MCE abnormal 1
Er14
PFC module abnormal
Er15
ADC compensation abnormal
Er16
Start failure 1
Er17
IPM module communication abnormal
Er18
Motor parameters abnormal
Er19
Soft start abnormal
Er20
IPM module temperature sensor abnormal
Er21
IPM module temperature is too high
Er22
Electrolytic capacitor of power board abnormal
Er30
Save controller parameters abnormal
Er31
HMI communication failure
Er32
IPM module communication failure
Er33
Ambient temperature sensor failure
Er34
Storage tank temperature sensor failure
Er35
User side inlet temperature sensor failure
Er36
User side outlet temperature sensor failure
Er37
Compressor exhaust temperature sensor
failure

/14 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Er38
Compressor suction temperature sensor failure
Er39
Evaporating temperature sensor failure in
heating mode
Er40
Condensing temperature sensor failure in
heating mode
Er41
Storage tank inlet temperature sensor failure
(Into water tank)
Er42
Storage tank outlet temperature sensor failure
(Into heat pump)
Er43
Ground source outlet temperature sensor
failure (into heat pump)
Er44
Ground source inlet temperature sensor failure
(into ground)
Er45
Before EEV temperature sensor failure
Er46
Coil gas inlet temperature sensor failure
Er47
Economizer gas inlet temperature sensor
failure
Er48
Economizer gas outlet temperature sensor
failure
Er49
Temperature sensor failure
Er50
Temperature sensor failure
Er51
Temperature sensor failure
Er52
Temperature sensor failure
Er53
IPM module temperature is too high
Er54
System exhaust pressure is over load
Er55
System suction pressure is too low
Er56
System exhaust temperature is too high
Er57
Condensing temperature is too high
Er58
Compressor is over load
Er59
Reserved
Er60
Reserved
Er61
Reserved
Er62
Reserved
Er63
Reserved
Er64
Water flow is not enough (Flow switch is
opened)
Er65
User side outlet temperature abnormal
Er66
Floor pipe outlet temperature abnormal
Er67
Ambient temperature is too low
Er68
RTC abnormal
Er69
WIFI communication failure
Er70
WIFI communication failure 2
Er71
IPM module configuration abnormal
Er72
DC outdoor fan abnormal
Er73
Inlet temperature is too low
Er74
Defrosting abnormal
Er75
Pressure transducer PT0 abnormal
Er76
Pressure transducer PT1 abnormal
Er77
System pressure abnormal
Er78
User side inlet temperature sensor is fall out
Er79
Cooling low temperature abnormal
Er80
Water flow of storage tank abnormal
Er81
Water flow of ground source abnormal
Er82
Ground source temperature is too low
Er83
Water is overflow in drainage plate

/17 17
FOSHAN SHUNDE ENS ELECTRIC CO LTD
www.ens-energy.com
Specifications, designs and other content appearing in this brochure are current as of Aug 2020 but subject to change without notice.
FOSHAN SHUNDE ENS ELECTRIC CO LTD
Head Office!
NO419, Green Land Commercial Center, Daliang 528300,
Shunde, Foshan, Guangdong, China!
Factory!
Yongfeng Industrial Zone, Lunjiao, Shunde, Foshan, Guangdong,
China !
Email: info@ens-energy.tech evan@ens-energy.tech !
Web: www.ens-energy.com !
Dealer
This manual suits for next models
2
Table of contents
Popular Heat Pump manuals by other brands

Viessmann
Viessmann VITOCAL 222-G Installation and service instructions

GRE
GRE HPM20 instruction manual

Raypak
Raypak 3450 Series Installation and operation manual

Crystal
Crystal Vertical 120 Installation and user manual

Dimplex
Dimplex WI 9ME Installation and operating instructions

Samsung
Samsung AE CXYD Series installation manual