esera automation 1-Wire Gateway 11 Modbus TCP User manual

Art. No. 11336
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 1 of 9
User Guide
1-Wire Gateway 11 Modbus TCP
1-Wire Gateway for autonomous communication between
PLC and a 1-Wire Sensor and Actuator network
Data evaluation of all 1-Wire modules in 2 seconds
increments
Modbus data output as TCP protocol
Processed sensor- and actuator data
Status of each sensor and actuator can be called up
Easy configuration
No extra drivers needed
Data storage in case of loss of communication to the host
system (optional)
Power supply for 1-Wire network
Designed for all dimensions of 1-Wire networks
DIN rail enclosure for switchboard assembly
Wide range of power voltage
Management of all ESERA-Automation 1-Wire modules and
many of standard 1-Wire sensors and actuators (switch-
module)
1 Introduction
Before you start assembling the 1-Wire Gateway 11 Modbus TCP and before you take the device into operation,
please read this assembly and operating instruction carefully to the end, especially the section referring to the
safety notes.
We recommend to use Config-Tool 3 for all kind of setup and configuration tasks. Please find the latest release
on our website at, www.esera.de. Please also refer to the Help/Support section to find the user guide for Config-
Tool 3.
2 Product description
Standard Modbus TCP protocol
You can use your industrial controller, e.g. SPS and standard TCP protocol to connect to the 1-Wire
Gateway 11. Addressing is similar to other Modbus systems and easy to handle. You can use addresses for
system data, sensor data and actuator devices. A complete address list including all available data points is
available for download on our webpage. These addresses are also available within the ESERA configuration
software Config-Tool 3.
3 Auto-E-Connect® Support
The ESERA Auto-E-Connect® 1-Wire Plug and Play system will be used for the
1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors
and actuators on the 1-Wire bus. It is optimized for industrial applications and
enables significant added value beyond the sensor and chip data.
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable
libraries and outputs fully formatted data.

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 2 of 9
The Auto-E-Connect functionality will be available from mid-2020 via 1-Wire Controllers, 1-Wire Gateways and
1-Wire ECO from ESERA available.
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in
the download area for this article in the ESERA Webshop.
4 Product features
Standalone controller
The 1-Wire Gateway 11 Modbus is designed to control 1-Wire Networks. You no longer have to worry about
1-Wire commands or algorithms to analyze sensor data. 1-Wire Gateway 11 Modbus scans 1-Wire Networks
by itself in order to identify new sensors or actuator devices. All data found were automatically provided in a
ready to use Modbus protocol format.
Formatted Data Output
1-Wire Gateway 11 Modbus provides plausibility checked sensor and actuator data in a ready to use format. E.g.
temperature sensor provides values in Celsius degrees with 2 decimal places. You only need to divide this
number by 100. Within the 1-Wire Gateway a product specific transformation table is available for most of our
selling 1-Wire sensor and actuator products.
Designed for all 1-Wire Networks
The 1-Wire interface of the 1-Wire Gateway 11 Modbus is specially designed to securely support all sizes of
1-Wire networks. 1-Wire sensor devices can be operated in parasitic or normal mode at the same time.
The latest available most powerful 1-Wire interface for a maximum level of data security has been used. This
includes complex network structures as well.
1-Wire Gateway 11 Modbus configuration
Free configuration software (Config-Tool 3) is provided. When using Config-Tool 3, the latest documentation
is available at any time hence it automatically updates via internet. This software is available for download on
our webpage. Communication to Modbus TCP is parallel with no switching.
System time / real time clock
No real time clock available in your system? No problem at all. 1-Wire Gateway 11 Modbus is providing time and
date as real time clock including an integrated backup battery. Data plausibility check is possible at any time.
Power supply
Input voltage for 1-Wire Gateway 11 Modbus is 9 –30 VDC. Therefore it can be used for 12 V as well as 24
VDC (industrial applications). Appropriate hat-rail mounted power supplies or power plugs can be found in
our webshop.
Operation
“How-To”-Videos for setup and operation can be found on our website www.esera.de (Service and Support –
How to –Support videos).
Basics and tips for 1-Wire network systems can be found in our webshop (https://www.esera.de/1-wire-
grundlagen/) or in our e-book which is also available in our webshop (https://www.esera.de/service-
support/dokumentation/352/grundlagen-1-wire-bus-ebook?number=11901).
5 Technical data
Data Interface: Modbus TCP and ESERA ASCII text protocol
Ethernet Interface: TCP/IP or UDP
- 10/100 MBit Ethernet Interface (RJ45)
- Auto Negotiation (Full-duplex and Half-duplex)
- Auto MDI/MDIX
- Support for DHCP and fix IP-address
Firmware Update: via ESERA Config-Tool 3
Power supply: 9 –30 VDC
Power consumption: maximum 500 mA
1-Wire interface: 1-Wire bus (5 V, GND and data)
Protective circuits: ESD protection and polarity protection
Connection: Screw terminals (up to 2,5 qmm wire cross section)
Output voltage: 5 V (+/- 10 %), maximum 200 mA, overload-proof and short-circuit-proof
Isolation: Galvanic separation among data and 1-Wire interface

Art. No. 11336
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 3 of 9
6 Ambient conditions
Temperature, operation -10 °C up to +55 °C (extended temperature range available upon request)
Air humidity: 10 –92 % (non-condensing)
Protection system: IP20
Protection class: III
Dimensions: 35 x 90 x 70mm (WxHxD)
7 Conformity
EN 50090-2-2
EN 61000-4-2 ESD
EN 61000-4-3 HF
EN 61000-4-4 Burst
EN 61000-4-5 Surge
EN 61000-6-1 Fault-free operation
EN 61000-6-3 Stray radiation
RoHS
8 LED indicators
The module status will be displayed by various LEDs. Please refer to the following table for their functions:
LED status
Description
Function
LED Green
PWR
power indicator
LED Green
DATA
LED flashes 3 times after power on
Flashes at 1-Wire activity
Flashes while transferring data by the data interface
Flashes rapidly if "KAL Receive" has been activated no “KAL
messages" received.
LED Green
Data Interface
Network Link LED
Is lit when connected
LED Yellow
Data interface
Network activity LED
Is lit while data submission by data interface

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 4 of 9
9 Wiring diagramm
Module topside (1-Wire Bus)
7 = Ground 1-Wire
8 = 1-Wire Data
9 = + 5 V Output
Module bottom side
(supply voltage 9 –30 VDC)
1 = Negative supply voltage
2 = Positive supply voltage
10 Connection –Example with multisensory

Art. No. 11336
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 5 of 9
11 Connection –Example with 1-Wire Hub III sensors and actuators

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 6 of 9
12 Software
Data interface Modbus TCP and ESERA ASCI Text protocol
To configure the Ethernet interface please use ESERA Config-Tool 3. This software is available for download on
our webpage.
12.1 Configuration and communication with 1-Wire Gateway 11
1-Wire Gateway 11 offers various
configuration and formatting options.
All options can be read out and
controlled by the ESERA Config-Tool
3. 1-Wire Gateway 11 and Config-
Tool 3 communication is based on
an open ESERA ASCII text protocol.
Therefore configuration and data
transfer with any terminal program
(such as Hercules or Putty) by
UDP/TCPIP and 1-Wire Gateway 11
is possible at any time. For detailed
communication commands please
refer to the “Programming Manual”
which is available for download in
our webshop.
13 Firmware-update
A firmware update can be performed
with the Config Tool 3 software under
the "DEBUG/DATA" tab.
The button "DOWNLOAD
FIRMWARE" opens a window to
download new software (firmware) for
the 1-Wire Controller / 1-Wire
Gateway.
The firmware can be used for all
device versions of the 1-Wire
Controller and 1-Wire Gateway. The
corresponding functionality is
released on the installed device
adapted.
As of firmware version V1.18_38, it is
no longer necessary to press the
reset button of the 1-Wire Controller /
1-Wire Gateway to update.
Recovery function Firmware-update
If the update is faulty, e.g. due to a power failure during the update, you can use the
recovery function. To do this, hold down the reset button (located under hole 11 on the
top of the module), start the update in Config Tool 3 and release the reset button in
Config Tool 3 after approx. 1 second after starting. Now the update should start. After
an update we recommend to disconnect the 1-Wire Controller / 1-Wire Gateway from
the power supply for approx. 30 seconds and to restart it. If you have any problems
with the installation, we will be happy to help you. Simply contact our support by e-

Art. No. 11336
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 7 of 9
14 Communication
14.1 ESERA ASCII text protocol
The 1-Wire Gateway 11 Modbus provides two protocols. The ESERA text protocol in ASCII format can easily be
used for configuration and analysis. Particular importance was attached here to good legibility and traceability.
The ESERA text protocol works with "GET" and "SET" commands, which probably every programmer has already
used in his own projects.
The ESERA text protocol is completely disclosed and documented. The current version of the ESERA protocol
description can be found on our website,
https://www.esera.de/shop/software/downloads-firmware-1-wire-controller-1-wire-gateway/
and within the ESERA Config Tool 3 software.
14.2 Modbus TCP protocol
1-Wire Gateway 11 Modbus communication to ESERA text protocol or Modbus TCP protocol is parallel with no
switching. For communication any IP address and any port can be chosen. Default is set to port 5000 and CHCP
mode.
The Modbus protocol is standardized configured. Please refer to the following table for a partial address-
overview. A complete address overview is available for download at the “Programming Manual”at the download
area of the 1-Wire Gateway 11 Modbus.
Partial Modbus address specification
Specification
reading address
number of words
type of data
Gateway No.
60000
1
Word
Article-No.
60001
1
Word
Firmware Version
61000
4
String
Hardware
61010
3
String
Serial number
61020
9
String
Time
61030
4
String
Date
61035
4
String
…
1-Wire bus sensors and
actuators
OWD 1 / 1-Wire module
40100
1
Integer
40101, 40102
2
DWord1
40103, 40104
2
DWord2
40105, 40106
2
DWord3
40107, 40108
2
DWord4
40109, 40110
2
DWord5
40111, 40112
2
DWord6
40113, 40114
2
DWord7
40115, 40116
2
DWord8
OWD 2 / 1-Wire module
40200
1
Integer
40201, 40202
2
DWord1
40203, 40204
2
DWord2
…
15 Operating conditions
The operation of the assembly group can take place only on condition of observing the required voltage and
the ambient conditions. The operating position of the device is irrelevant. The device is meant to be used in
dry and dust-free areas. Should condensed water build up, an acclimatization period of at least 2 hours must
pass. Assembly groups and components do not belong into the hands of children!
The building group can be operated only under the supervision of an electrically skilled person.

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 8 of 9
In industrial facilities, the accident prevention regulations of the federation of industrial professional
associations for electrical installations and equipments must be observed.
Do not operate the assembly group in an environment with inflammable gases, vapours or dusts or in an
environment where such gases, vapours or dusts may be found.
16 Assembly
The location of the assembly must be protected against humidity. The device may be used only in dry inside
spaces and protected outside areas. The device is designed to be assembled as a fixed device within a
switchboard.
17 Disposal note
Do not dispose of the device within the household waste!
According to the directive concerning old electrical and electronic appliances,
electronic devices must be disposed of via the collecting points for old electronic
appliances!
18 Safety instructions
When using products that come into contact with electrical voltage, the valid VDE regulations must be observed, especially
VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711 and VDE 0860
All final or wiring work must be carried out with the power turned off.
Before opening the device, always unplug or make sure that the unit is disconnected from the mains.
Components, modules or devices may only be put into service if they are mounted in a contact proof housing.
During installation they must not have power applied.
Tools may only be used on devices, components or assemblies when it is certain that the devices are disconnected
from the power supply and electrical charges stored in the components inside the device have been discharged.
Live cables or wires to which the device or an assembly is connected, must always be tested for insulation faults or
breaks.
If an error is detected in the supply line, the device must be immediately taken out of operation until the faulty cable
has been replaced.
When using components or modules it is absolutely necessary to comply with the requirements set out in the
accompanying description specifications for electrical quantities.
If the available description is not clear to the non-commercial end-user what the applicable electrical characteristics
for a part or assembly are, how to connect an external circuit, which external components or additional devices can
be connected or which values these external components may have, a qualified electrician must be consulted.
It must be examined generally before the commissioning of a device, whether this device or module is basically
suitable for the application in which it is to be used.
In case of doubt, consultation with experts or the manufacturer of the components used is absolutely necessary.
For operational and connection errors outside of our control, we assume no liability of any kind for any resulting
damage.
Kits should be returned without their housing when not functional with an exact error description and the
accompanying instructions. Without an error description it is not possible to repair. For time-consuming assembly or
disassembly of cases charges will be invoiced.
During installation and handling of components which later have mains potential on their parts, the relevant VDE
regulations must be observed.
Devices that are to be operated at a voltage greater than 35 VDC / 12mA, may only be connected by a qualified
electrician and put into operation.
Commissioning may only be realized if the circuit is built into a contact proof housing.
If measurements with an open housing are unavoidable, for safety reasons an isolating transformer must be
installed upstream or a suitable power supply can be used.
After installing the required tests according to DGUV / regulation 3 (German statutory accident insurance,
https://en.wikipedia.org/wiki/German_Statutory_Accident_Insurance) must be carried out.
19 Warranty
ESERA GmbH guarantees that the goods sold at the time of transfer of risk to be free from material and workmanship
defects and have the contractually assured characteristics. The statutory warranty period of two years begins from date of
invoice. The warranty does not extend to the normal operational wear and normal wear and tear. Customer claims for
damages, for example, for non-performance, fault in contracting, breach of secondary contractual obligations,
consequential damages, damages resulting from unauthorized usage and other legal grounds are excluded. Excepting to
this, ESERA GmbH accepts liability for the absence of a guaranteed quality resulting from intent or gross negligence.
Claims made under the Product Liability Act are not affected.

Art. No. 11336
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de 11336 V2.0 R1.0 Manual Page 9 of 9
If defects occur for which ESERA GmbH is responsible, and in the case of replacement goods, the replacement is faulty,
the buyer has the right to have the original purchase price refunded or a reduction of the purchase price. ESERA GmbH
accepts liability neither for the constant and uninterrupted availability of the ESERA GmbH or for technical or electronic
errors in the online offer.
We develop our products further and we reserve the right to make changes and improvements to any of the products
described in this documentation without prior notice. If you need documentation or information about older product
versions, contact us by email at info@esera.de.
20 Trademarks
All mentioned designations, logos, names and trademarks (including those which are not explicitly marked) are
trademarks, registered trademarks or other copyright or trademarks or titles or legally protected designations of their
respective owners and are hereby expressly recognized as such by us. The mention of these designations, logos, names
and trademarks is made for identification purposes only and does not represent a claim of any kind on the part of
ESERA GmbH on these designations, logos, names and trademarks. Moreover, from their appearance on ESERA GmbH
webpages it cannot be concluded that designations, logos, names and trademarks are free of commercial property rights.
ESERA and Auto-E-Connect are registered trademarks of ESERA GmbH.
21 Contact
ESERA GmbH
Adelindastrasse 20
87600 Kaufbeuren
GERMANY
Tel.: +49 8341 999 80-0
Fax: +49 8341 999 80-10
www.esera.de
WEEE-Number: DE30249510
This manual suits for next models
1
Table of contents
Other esera automation Gateway manuals