ESP EnVision EV-12010 BR User manual

© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com / UM-enVision-Rev-H
User Manual
120 and 208-240 Volt Models

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 1

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 2
I. PRODUCT OVERVIEW.........................................................................................................4
1. MODELS...........................................................................................................................4
2. KEY FEATURES.................................................................................................................4
3. TECHNICAL SUPPORT ........................................................................................................4
II. INSTALLATION INSTRUCTIONS........................................................................................5
1. FILTER INSTALLATION........................................................................................................5
a. TURN OFF EQUIPMENT..................................................................................................5
b. CONNECT MODEM/FAX LINE..........................................................................................5
c. CONNECT 10/100/1000 ETHERNET NETWORK LINE ........................................................5
d. CONNECT EQUIPMENT ..................................................................................................6
e. CONNECT FILTER TO OUTLET.........................................................................................7
III. HARDWARE........................................................................................................................8
1. FILTER.............................................................................................................................8
a. LCD EVENT MONITOR .................................................................................................8
I. NORMAL OPERATION...............................................................................................8
II.WIRING FAULT ......................................................................................................10
III.ABNORMAL VOLTAGE.............................................................................................10
b. CLEARING MEMORY....................................................................................................11
I. BUTTONS .............................................................................................................11
II. DIAGNOSTIC SOFTWARE .......................................................................................11
2. DATA INTERFACE CABLE .................................................................................................12
a. OVERVIEW.................................................................................................................12
b. INSTRUCTIONS FOR DATA RETRIEVAL..........................................................................12
c. INSTRUCTIONS FOR EV-230XX DATA RETRIVIAL..........................................................12
IV. SOFTWARE INSTALLATION ...........................................................................................13
1. COMPUTER REQUIREMENTS ............................................................................................13
2. HARDWARE REQUIREMENTS.............................................................................................13
3. DOWNLOAD AND INSTALL SOFTWARE ...............................................................................13
4. ANDROID APP DOWNLOAD...............................................................................................13
4. INSTALL DATA INTERFACE CABLE .....................................................................................14

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 3
V. USING THE SOFTWARE...................................................................................................14
1. PHYSICAL CONNECTIONS ................................................................................................14
2. START THE SOFTWARE....................................................................................................14
3. CONFIGURE THE DATA INTERFACE CABLE AND COM PORT................................................15
4. SOFTWARE MODES .........................................................................................................17
a. MULTIMETER MODE....................................................................................................18
b. SCOPE MODE.............................................................................................................19
c. CHART MODE.............................................................................................................21
d. OUTLET CONTROL MODE............................................................................................22
e. HISTORICAL DATA MODE ............................................................................................23
f. SETTINGS MODE.........................................................................................................28
g. COMPORT SETUP MODE...........................................................................................30
5. COMMAND LINE OPERATION ............................................................................................30
VI. TROUBLESHOOTING.......................................................................................................31
1. ENVISION PCS FILTER ....................................................................................................31
2. SOFTWARE.....................................................................................................................31
VII. SPECIFICATIONS.............................................................................................................32

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 4
I. PRODUCT OVERVIEW
The enVision PCS is a state-of-the-art, microprocessor-controlled, power filter engineered
with real-time data acquisition and storage.
1. Models: This manual applies to the following enVision models:
2. Key Features:
•Normal and Common Mode EMI Noise Filter
•3-Stage Normal and Common Mode AC Surge Suppressor
•CAT6 Network Line Surge Suppressor
•Modem/Fax Line Surge Suppressor (Note: Not available for EV-230xx)
•Inrush Current Elimination with Zero-Voltage Turn-On and Zero- Current Turn-Off (ICE Zero)
•Wiring Fault Detection
•Catastrophic Over/Under Voltage Shutdown (COUVS®) with selectable thresholds
•Under-Voltage Event Recorder (up to 65535 events)
•Over-Voltage Event Recorder (up to 65535 events)
•Power Outage Event Recorder (up to 65535 events)
•Surge Event Recorder (up to 65535 events)
oRecords surges in all three modes: Line-Neutral, Line-Ground, Neutral-Ground (120V)
oRecords surges in all three modes: Line1-Line 2, Line1-Ground, Line2-Ground
(208-240V)
•Event Timestamp Recorder (up to 512 events)
oRecords actual date and time of events
•Internal logging of measured parameters
oAverage power, maximum power, average voltage, maximum voltage, minimum voltage,
maximum current of 30 minute intervals for up to 138 days
oLine voltage, current, power, NG voltage, frequency, power factor, crest factor, energy
sampled every 10 seconds for up to 2.25 days
•Additional features available when connected to a PC
(detailed in Diagnostic Software User Manual)
3. Technical Support:
•To download software and access further product information, visit www.ametekesp.com
•For enVision PCS technical support, please contact ESP at 1-800-645-9721
Model Number
Voltage (AC RMS)
Current (AC Amps)
Outlet
EV-12010 BR
120
10
EV-12015
120
15
EV-12016 BR
120
16
EV-12020
120
20
EV-20815
208-240
15
EV-20816 BR
208-240
16
EV-20820
208-240
20
EV-20830-630
208-240
30
EV-20830-L630
EV-20830-L630-GNS
208-240
30
EV-23010
230
10
EV-23016
230
16
EV-23016-F
230
16
EV-23030-GNS
230
30

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 5
II. INSTALLATION INSTRUCTIONS
1. Filter Installation:
a. Turn off the machine you are connecting to the
Filter, and unplug the machine’s power cord
from wall outlet.
Éteignez la machine que vous connectez au
filtre et débranchez de la prise murale le cordon
d'alimentation de la machine.
Apague la máquina que intenta conectar al filtro
y desconecte el cable de alimentación de la
máquina del tomacorriente.
b. Connect Modem/Fax line: Connect a phone cord from the wall jack to the
“Modem/Fax” modular jack labeled “IN”, and then connect a second phone cord
from the “Modem/Fax” modular jack labeled “OUT” to the machine/equipment to
be protected. The EV-23010 and EV-23016 models do not support a Modem Fax
telco port.
Please Note: The Filter only provides connectivity and protection for a single phone line.
c. Connect “10/100/1000 ETHERNET” network line: Connect a CAT6 network cable
from the wall jack to the “10/100/1000 ETHERNET” modular jack labeled “IN”, and
connect a second CAT6 network cable from the “10/100/1000 ETHERNET”
modular jack labeled “OUT” to the equipment to be protected.
One CAT6 network cable is included with the Filter.
EV-23010
EV-23016
EV-12015/20
EV-20815/20

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 6
d. Connect Equipment
i. Make sure that the total amperage of all equipment plugged into the Filter
does not exceed the maximum branch circuit rating.
Assurez-vous que l'intensité totale de tous les appareils reliés au filtre ne
dépasse pas la tension maximale du circuit de dérivation.
Asegúrese de que el amperaje total del equipo conectado al filtro no
supere la clasificación máxima del circuito de derivación.
ii. Connect the AC power cords of the equipment to be protected into the
short output power cord of the Filter or two convenience receptacles next
to the short output power cord.
Please Note: Exceeding the branch circuit rating will cause the branch circuit breaker
to trip.
EV-20830-L630
EV-23016
EV-12015/20
EV-23010
EV-20815/20
EV-20830-630

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 7
e. Connect Filter to Outlet: Plug the Filter input power cord into a properly grounded
and compatible branch circuit outlet. The plug is used as the disconnect device.
Please Note: Do not plug the Filter into a re-locatable power tap.
i. If the branch circuit outlet is correctly wired and the magnitude of the line
voltage is acceptable (between 105 and 140 VRMS for 120V products, or
between 190 and 260VRMS for 208-240V products), power will be
connected to the outlets of the Filter and the Green “System On” LED will
illuminate. Your equipment is now protected and installed correctly. You
may now turn all connected equipment back on.
ii. If the branch circuit outlet is incorrectly wired, the Red ‘Wiring Fault” LED
will illuminate and the LCD will display specific wiring fault information. If
this occurs, contact a licensed electrician to correct the outlet wiring. Refer
to Section III: Hardware/EnVision PCS Filter, for LCD EVENT MONITOR
display details.
iii. If neither “System On”, nor the “Wiring Fault” LED illuminates, there is
either no voltage at the receptacle or the magnitude of the line voltage is
not acceptable (less than 105 VRMS or above 140 VRMS for 120V products,
or less than 190 VRMS or above 260 VRMS for 208-240V products). If the
magnitude of the line voltage is not acceptable, specific information will be
displayed on the LCD. If this occurs, contact a licensed electrician to
trouble-shoot the abnormal voltage condition. Refer to Section III:
Hardware/EnVision PCS Filter, for LCD EVENT MONITOR display details.
1. You may also need to verify that the Filter is operating properly.
To test, plug the Filter into a known properly functioning outlet. If the “System
On” LED still does not illuminate in the functioning outlet, contact ESP at 1-800-
645-9721.
•Protection against short-circuits and earth
faults shall be provided as part of the building
installation.
•The socket-outlet shall be installed near the
equipment and shall be easily accessible.
•A dedicated Earth Ground (PE) wire is
required in addition to line voltage.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 8
III. HARDWARE
1. Filter
a. LCD Event Monitor
The LCD EVENT MONITOR displays useful
information related to data collection, device
status, and troubleshooting.
i. Normal Operation
1. When the EnVision PCS Filter is plugged into a branch circuit
outlet with correct wiring and acceptable line voltage, the LCD
Event Monitor will display the following information:
Menu
Item
Example Display
Electrical
Parameters
(EP)
Line Voltage
Neutral-Ground Voltage
Load Current Draw
Load Power Draw
Load Energy Usage
Crest Factor
Power Factor
Line Frequency

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 9
Power
Disturbances
(Pd)
Power Outages
Under Voltages (Off)
Under Voltages
(Record)
Over Voltages (Record)
Over Voltages (Off)
Surges
Overload
Last Recorded Event
Outlet State (OS)
On / Off
User Control
(UC)
Press and hold
Menu and Scroll
buttons to
perform control
action.
Turn Outlets On / Off
Memory All Clear (ALC)
Disturbance History
Clear (dhC)
Power Usage Clear
(PUC)
Disturbance Count
Clear (dcC)
Energy Display Clear
(EdC)
Chart Data Start (cdS)

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 10
ii. Wiring Fault
When connected to an incorrectly wired branch circuit outlet, in addition to
the illumination of the Red LED, the LCD Event Monitor will display the
following information:
iii. Abnormal Voltage
When the magnitude of the branch circuit outlet voltage is not acceptable*,
the Filter will disconnect power to its outlets and display the following
information on the LCD Event Monitor (*above the over-voltage shutdown
threshold or below the under-voltage shutdown threshold; refer to Section
IV: Diagnostic Software for more information):
Wiring Fault Condition
Display
Example Display
Line (Hot) / Neutral
Reversed
(120V products only)
rP (Reverse
Polarity)
Missing Ground
gnd (no Ground)
Voltage Condition
Display
Example Display
Over-Voltage
OFF + ▲ + Voltage
Under-Voltage
OFF + ▼ + Voltage

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 11
b. Clearing Memory:
The memory contents of the Filter can be cleared at any time by following one of
these two methods:
i. Buttons:
Follow these steps to clear the device memory:
1. Press the Menu button until “UC”(User Control) is displayed.
2. Next, press the Scroll Button to select which memory record to
erase:
Memory All Clear (ALC)
Disturbance History Clear
(dhC)
Power Usage Clear
(PUC)
Disturbance Count Clear
(dcC)
Energy Display Clear
(EdC)
3. Finally, press and hold both Menu and Scroll buttons at the same
time until “Clr” is displayed, and then release.
ii. Diagnostic Software:
The device memory may alternately be cleared from within the Diagnostic
Software. See “Using the Software” in this manual for details.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 12
2. Data Interface Cable
a. Overview
i. The Data Interface Cable consists of a USB
connection on one end, and a RJ-11 connection on
the opposite end.
ii. The USB connection plugs into an available USB port
on your PC. The RJ-11 connection plugs into the RJ-
11 “OUT” Jack (labeled “Data Port”) on the enVision
Filter, which is the jack closest to the LCD and buttons.
b. Instructions for Data Retrieval
i. Disconnect any protected Modem/Fax
lines connected to the “IN” and “Out”
RJ-11 modular jacks on the Filter.
Ethernet connections (RJ-45) may
remain in place.
ii. Connect the Data Interface Cable into
the USB port on your PC.
iii. Connect the Data Interface Cable into the RJ-11 “OUT” Jack (labeled “Data
Port”) on the Filter. It is the jack closest to the LCD and buttons.
iv. Open the Diagnostic Software.
v. When you are finished, be sure to re-connect the Modem/Fax lines to the “IN”
and “Out” RJ-11 modular jacks on the Filter.
c. Instructions for EV-23010/EV-23016 Data Retrieval
i. Ethernet connections (RJ-45) may
remain in place.
ii. Connect the Data Interface Cable into
the USB port on your PC.
iii. Connect the Data Interface Cable into
the RJ-11 Jack (labeled “Data Port”).
It is the jack closest to the LCD and
buttons.
iv. Open the Diagnostic Software.
v. When you are finished, remove the Data Interface Cable from the RJ-11 Jack.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 13
IV. SOFTWARE INSTALLATION
1. Computer Requirements
a. Minimum 133MHz Pentium processor (or equivalent), minimum 64MB of
RAM, minimum 10MB free hard drive space, VGA or higher resolution
monitor, keyboard, mouse, CD or DVD drive, minimum screen resolution of
1024x768, MicrosoftWindows XP/Vista/7/8.
2. Hardware Requirements
a. For use with enVision enabled products and Data Interface Cable (XG-PCS-1C-1)
3. Download and Install Software
a. Download the Software Installer from
www.amatekesp.com/esp/envision/envision-
120-208v
b. Unzip and run the installation utility.
c. Follow the on-screen instructions to
complete installation of the software.
4. Android App Download
a. The App can be used to view the enVision’s analytical software from an Android
device
b. Visit the Google Play store at https://play.google.com/store and search for ESP
enVison to download the App. It can also be downloaded directly at
https://play.google.com/store/apps/details?id=com.espsurgex.envison.
c. Requires USB OTG (On The Go) adapter, Android device with USB OTG
support, and ESP USB interface cable (XG-PCS-IC-1)

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 14
5. Install Data Interface Cable
a. Automatic Installation (Requires Internet connection)
i. Plug the USB side of the Data Interface Cable into an available USB port.
ii. Windows will automatically detect and install appropriate device driver
files for the Data Interface Cable.
•
If a “Found New Hardware” pop-up box appears, follow the on-
screen instructions and allowWindows to search online for driver
files.
•
The installation could take several minutes to search for and
download appropriate driver files. Once the files are found, follow
the on-screen instructions to install.
•
Note: The driver installation process will first install USB Serial
Converter driver files, and then will install USB Serial Port drivers
separately.
b. Manual Installation
In the event that the automatic driver installation process was not successful, or if
no internet connection is available, the Data Interface Cable driver files may be
installed manually.
•
Select “Install Drivers” during the Software Installation process.
•
Or run “Interface Setup” from: Start/All Programs/ESP
SurgeX/Diagnostic Tool
c. Once the Data Interface Cable has been successfully installed, it will appear
in Device Manager as “USB Serial Port (COMx)” under “Ports (COM & LPT)”.
V. USING THE SOFTWARE
1. Physical Connections
a. Plug the USB side of the Data Interface Cable into an available USB port.
b. Plug the RJ-11 side of the Data Interface Cable into the RJ-11 “OUT”jack
labeled “Data Port”on the enVision enabled unit, which is the jack closest to the
LCD.
c. Note: The enVision PCS must be powered by AC Mains for communications with
the software to operate.
2. Start the Software
a. Double-click the desktop shortcut labeled “ESP SurgeX
Diagnostic Tool”, or use the “ESP SurgeX Diagnostic Tool”Start
Menu shortcut located at:
Start/All Programs/ESP SurgeX/Diagnostic Tool

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 15
3. Configure the Data Interface Cable and COM Port
a. Click the COM Port Setup button labeled COM.
b. Click Configure.
i. The auto configuration process will automatically set the correct device
parameters of the Data Interface Cable to operate properly with the
software and enVision.
•
Note: This process only needs to be done once for each new
Data Interface Cable installed on the PC.
•
Note: This process edits Windows registry values, and so may be
blocked by MS Windows User Account Control (UAC) in Windows
Vista/7/8/10. It may be necessary to exit the software and restart it
with administrative rights by right-clicking the software shortcut
and choosing “Run As Administrator”. It may also be necessary to
run the compatibility wizard by right-clicking the shortcut, selecting
“Troubleshoot Compatibility”, and following the prompts.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 16
ii. The COM port may also be manually configured using the Device Manager:
1. Open Device Manager
a. Click on Start button
b. Type the following command in the Search box: devmgmt.msc
c. Press Enter
2. In the Device Manager, expand “Ports (COM & LPT)”
3. Right-click on the entry labeled “USB Serial Port (COMx)” and click
“Properties”
4. In the USB Serial Port Properties pop-up box, click the “Port Settings”
tab, and then click the “Advanced” button.
5. In “USB Transfer Sizes”, change both the “Receive” and “Transmit”
values to 4096.
6. In “BM Options”, change the “Latency Timer” value to 2.
7. Leave all other settings at default.
+

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 17
c. Click Detect.
i. The auto detect process will automatically detect the COM Port number
assigned to the Data Interface Cable.
ii. If the auto detection process is successful, click Save. The software is
now properly configured and ready for use.
iii. If the auto detection process is not successful, verify that the Data
Interface Cable device drivers are properly installed, and that the physical
connections between the enVision and the PC have been made correctly.
d. The language may also be selected in this mode.
4. Software Modes
The enVision Software is organized into several operational modes. The modes are
activated by clicking the corresponding button at the bottom of the software interface.
Press the Help Button (“?”) in the upper right for additional information on the features
available in the current mode. Hovering the mouse cursor over items will also display
additional information.
Scope Mode, Chart Mode, Historical Data Mode, and Settings Mode
include a Save function. Press the Save button to save data to a CSV file.
Time Stamped data may also be saved as a report in PDF format.
Chart Mode and Historical data may be analyzed by an automatic Expert
Analysis tool. Press the Expert button to perform an expert analysis of
recorded time-stamped event data, historical data, or chart measurements
and generate a PDF report of potential conclusions and recommendations.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 18
a. Multimeter Mode
i. The Multimeter Mode provides information traditionally acquired from one
or more handheld digital multimeters, as well as an overview of the
recorded power quality events and energy consumption of connected
equipment. ±2% Measurement Accuracy.

User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com 19
ii. Real-time display of 8 electrical parameters
•
Line Voltage: AC RMS Volts Line-Neutral (Line1-Line2)
•
Load Current Draw: AC RMS Amps
•
Load Power Draw:Watts
•
Neutral-Ground Voltage: AC RMS Volts Neutral-Ground (Line2-
Ground)
•
Line Frequency: Hertz
•
Load Power Factor
•
Line Voltage Crest Factor
•
Energy Usage (kWh) of connected equipment since date and
time of last manual usage reset
iii. Number of recorded power quality events
•
Surge Events: SG
•
Overvoltage Events with turn off of connected equipment: OVoff
•
Overvoltage Events with no turn off of connected equipment:
OVrec
•
Undervoltage Events with no turn off of connected equipment:
UVrec
•
Undervoltage Events with turn off of connected equipment: UVoff
•
Power Outage Events: PO
b. Scope Mode
i. The Scope Mode enables a real-time voltage, current, and power
oscilloscope which incorporates many functions available in standalone
oscilloscopes. 4kHz Oscilloscope Bandwidth.
ii. Ch1-Ch3 buttons toggle waveform displays.
•
Ch1 button toggles line voltage trace.
•
Ch2 button toggles load current trace.
•
Ch3 button toggles load power trace.
This manual suits for next models
13