extronics iWAP200 Installation instructions

1
Installation & Operating Manual
iWAP200

Operating Manual
2
This page is intentionally left blank.
Document Number
316268
(See Last Page for Revision Details)
©2009 Extronics Limited. This document is Copyright Extronics limited.
Extronics reserve the right to change this manual and its contents without notice, the latest
version applies.

Operating Manual
3
Contents
1Introduction.......................................................................................................... 4
2Safety Information and Notes.............................................................................. 5
2.1 Storage of this Manual ................................................................................. 5
2.2 List of Notes ................................................................................................. 5
3Installation and Setting-to-Work .......................................................................... 7
3.1 Installation.................................................................................................... 7
3.1.1 Removing the cover.............................................................................. 7
3.1.2 Fitting the cables................................................................................... 7
3.1.3 Mains Variant Cable Installation............................................................ 8
3.1.4 Fibre Ethernet Input .............................................................................10
3.1.5 24VDC Variant Cable Installation.........................................................10
3.1.6 Fibre Ethernet Input .............................................................................12
3.1.7 Thermostat Control ..............................................................................12
3.1.8 Fitting the antennas..............................................................................12
3.1.9 Mounting The Antennas.......................................................................13
3.1.10 Setting to work .....................................................................................13
4Intended Purpose Usage....................................................................................14
4.1 Transportation and Storage.........................................................................14
4.2 Authorized Persons.....................................................................................14
4.3 Cleaning and Maintenance..........................................................................14
4.4 Safety Precautions......................................................................................14
4.5 Cleaning and Maintenance Intervals...........................................................15
4.6 Aggressive substances and environments..................................................15
4.7 Exposure to external stresses.....................................................................15
5Technical Data ...................................................................................................16
5.1 Specification................................................................................................16
5.2 Enclosure Dimensions.................................................................................17
6Type Codes........................................................................................................18
7Certification ........................................................................................................19
8Manual Revision.................................................................................................28

Operating Manual
4
1 Introduction
The iWAP200 Zone 2 Access Point Enclosure is designed to deploy wireless
networks in hazardous areas. The concept allows installation of equipment from
leading WLAN vendors such as Meru, Symbol and Firetide.
Each type of Access Point or RF transmitting device is rigorously checked and
tested by Extronics and our Notified Body to ensure conformity to the ATEX
standards and approvals. This means that Extronics can provide an OEM a
solution to enable your WLAN network devices to be installed in hazardous
areas.
The Extronics iWAP200 is designed for use with one to four standard antennas or
Extronics iANT200 series of intrinsically safe antennas for optimum coverage on
Chemical Plants, Oil Refineries or Oil & Gas Platforms.
Optional features include surge arrestors for lightening suppression in outdoor
installations and either single and multimode fibre inputs for the Ethernet,
enclosure heating or cooling for low/high temperatures and anti-condensation
plus the option of plug and socket cable entry instead of cable glands.

Operating Manual
5
2 Safety Information and Notes
2.1 Storage of this Manual
Keep this user manual safe and in the vicinity of the device. All persons who have to work on
or with the device should be advised on where the manual is stored.
2.2 List of Notes
The notes supplied in this chapter provide information on the following.
•Danger / Warning.
oPossible hazard to life or health.
•Caution
oPossible damage to property.
•Important
oPossible damage to enclosure, device or associated equipment.
•Information
oNotes on the optimum use of the device
Warning Installation to be by skilled electricians and instructed personnel in
accordance with national legislation, including the relevant standards
and, where applicable, in accordance with IEC 79.17 on electrical
apparatus for explosive atmospheres.
Warning! The iWAP200 must not be operated in Gas Zone 0, 1, or Dust Zone 20
hazardous areas. Refer to the specification for ATEX certificate
information.
Important The technical data indicated on the iWAP200 rating plate, this manual
and the ATEX certificate must be observed.
Important The technical data indicated on the iWAP enclosure must be observed.
Important Changes in the design and modifications to the equipment are not
permitted. This includes adding or removing heaters/fans which were
installed by Extronics Ltd. Changing the pre installed Access points
and/or MESH routers is NOT permitted.
Important The iWAP200 shall be operated as intended and only in an undamaged
condition.
Important Only antennas which have been approved for use by Extronics for the
area which they are to be installed may be used with iWAP200.
Caution This assembly may weigh up to 10Kg depending on requirements,
therefore ensure the assembly is mounted using suitable fixtures.

Operating Manual
6
Caution When powering the iWAP200 via POE do not apply an external power
supply to the protection board.
Caution Never power the iWAP200 (if fans and/or heaters are installed) via POE.
Important For the installation, maintenance and cleaning of the units, it is
absolutely necessary to observe the applicable regulations and
provisions concerned with explosion protection (EN60079-0:2006, EN
60079-14:2003) as well as the Accident Prevention Regulations.
Important The iWAP200 must not be stored or operated outside of its rated
temperature range as stated on the ATEX certificate.

Operating Manual
7
3 Installation and Setting-to-Work
3.1 Installation
The iWAP200 is simple to install and can be secured directly to suitable surface
using the mounting holes on the Enclosure.
3.1.1 Removing the cover
Unscrew the four screws and remove the enclosure lid.
.
Diagram 3.1.1
3.1.2 Fitting the cables
Depending on the configuration of the iWAP200, the connections for power and
communication will need to be terminated into the enclosure via the correct cable
entries shown in Diagram 3.1.1.
The cables used to connect the power and/or Ethernet connection to the PCB screw
terminals must conform to the following specification;
All wires should be stripped and, if stranded cable is used, should be crimped using
2.5mm bootlace ferrules. The stripped/crimped wires should then be placed into the
corresponding screw terminal and securely screwed in place.
If using solid core cable;
Minimum cross section of cable = 0.2mm
2
Maximum cross section of cable = 2.5mm
2
Lid
screws
Lid
screws
Ethernet
Cable Entry
5.8 GHz
Antenna
Connections
Top Row
2.4GHz
Antenna
Connections
Bottom Row
AC/DC Power
Cable Entry

Operating Manual
8
If using crimped stranded core cable;
Minimum cross section of cable = 0.25mm
2
Maximum cross section of cable = 1.5mm
2
IMPORTANT! All cables should be connected to the iWAP200 via the correct
cable gland, fitted by a competent person.
IMPORTANT! Changes in the design and modifications to the equipment are not
permitted. This includes adding heaters/fans which are not
installed at the factory.
Important The installer MUST ensure that that all cables have adequate
mechanical protection to avoid damage to the wires.
3.1.3 Mains Variant Cable Installation
Diagram 3.1.3.1 shows the connectors on the mains variant of the iWAP200. Table
3.1.3.2 describes the pin out connection required for operation. There are two blocks
of screw terminals and one RJ45 connector. The Ethernet input screw terminals are
wired in parallel with the RJ45 connector. Do not make an Ethernet connection to the
RJ45 connector and the screw terminals at the same time, the installer should use
only one of these connectors.
Follow the instructions in section 3.1.2 to correctly prepare the cables and feed them
through the correct cable gland. Follow table 3.1.3 to connect the correct cable to the
correct screw terminal. If using the RJ45 connector instead of the screw terminals
simply connect the Cat-5 cable to the connector and ensure the cable is securely in
place.
Caution Only ever make one Ethernet cable to either the RJ45 connector or
Ethernet screw terminals – NEVER both.

Operating Manual
9
Diagram 3.1.3.1 – Mains Variant iWAP200 PCB
Connector Description Notes
110/230VAC
input These screw terminals allow the connection of a
110/230VAC power supply. Pinouts are; 1 = Live, 2 =
Neutral, 3 = Earth.
Chassis Earth There are two terminals which allow a connection to
earth. When the iWAP200 is delivered one of these
terminals will be connected to the enclosure. The
second earth terminal spare.
Ethernet Input
(Terminals) Connect a Cat-5 cable to these screw terminals for the
connection of the Ethernet input. The pinouts on this
terminal correspond with the standard cat-5
TIA/EIA-568-B T568B wiring methods. If powering via
POE this is where the power supply will come from.
Only one Ethernet input
should be made, only use
either the terminals or
RJ45 connector NOT
both.
Ethernet Input
(RJ45) This allows the connection of a standard Cat-5 cable
with plugs. Only one Ethernet input
should be made, only use
either the terminals or
RJ45 connector NOT
both.
Table 3.1.3.2 – iWAP200 Mains Variant Pinouts
Important Only connectors 110/230VAC Input, Chassis Earth and Ethernet Input
(Terminals or RJ45) are user serviceable. The end user should not
connect, disconnect or alter the wiring on any other connector!
Ethernet Input
(RJ45) Ethernet Input
(Screw Terminals) Chassis
Earth 110/230VAC
Input
L N E

Operating Manual
10
Caution When powering the iWAP200 via POE do not apply an external power
supply to the protection board.
Caution Never power the iWAP200 (if fans and/or heaters are installed) via POE.
3.1.4 Fibre Ethernet Input
Important When connecting the access point via a fibre connection do not use
any of the two Ethernet inputs of connectors.
To obtain greater wired link distances the iWAP200 can be shipped with an optional
fibre module. The fibre module will be connected directly to the access point, the user
should attach the fibre cable directly to the fibre module using a multimode fibre
cable on an ST connector.
3.1.5 24VDC Variant Cable Installation
Diagram 3.1.5.1 shows the connectors on the mains variant of the iWAP200. Table
3.1.5.2 describes the pin out connection required for operation. There are two blocks
of screw terminals and one RJ45 connector. The Ethernet input screw terminals are
wired in parallel with the RJ45 connector. Do not make an Ethernet connection to the
RJ45 connector and the screw terminals at the same time, the installer should use
only one of these connectors.
Follow the instructions in section 3.1.2 to correctly prepare the cables and feed them
through the correct cable gland. Follow table 3.1.5.2 to connect the correct cable to
the correct screw terminal. If using the RJ45 connector instead of the screw terminals
simply connect the Cat-5 cable to the connector and ensure the cable is securely in
place.
Caution Only ever connect one Ethernet cable to either the RJ45 connector or
Ethernet screw terminals.

Operating Manual
11
Diagram 3.1.5.1 – 24V Variant iWAP200 PCB
Connector Description Notes
24VDC input These screw terminals allow the connection of a
24VDC power supply. Pinouts are; 1 = +24V, 2 =
0V/GND, 3 = Earth/cable outer sheath.
Chassis Earth There are two terminals which allow a connection to
earth. When the iWAP200 is delivered from
Extronics’ factory one of these terminals will be
connected to the enclosure. The second earth
terminal spare.
Ethernet Input
(Terminals) Connect a Cat-5 cable to these screw terminals for
the connection of the Ethernet input. The pinouts on
this terminal correspond with the standard Cat-5
TIA/EIA-568-B T568B wiring methods.
Only one Ethernet input
should be made, only use
either the terminals or RJ45
connector NOT both.
Ethernet Input
(RJ45) This allows the connection of a standard Cat-5
cable with plugs. Only one Ethernet input
should be made, only use
either the terminals or RJ45
connector NOT both.
Table 3.1.5.2 – iWAP200 24VDC Variant Pinouts
Important Only connectors 110/230VAC Input, Chassis Earth and Ethernet Input
(Terminals or RJ45) are user serviceable. The end user should not
connect, disconnect or alter the wiring on any other connector!
Caution When powering the iWAP200 via POE do not apply an external power
supply to the protection board.
Ethernet Input
(RJ45) Ethernet Input
(Screw Terminals) Chassis
Earth 24 VDC Input
+ 0 E

Operating Manual
12
Caution Never power the iWAP200 (if fans and/or heaters are installed) via POE.
3.1.6 Fibre Ethernet Input
Important When connecting the access point via a fibre connection do not use
any of the two Ethernet inputs of connectors.
To obtain greater wired link distances the iWAP200 can be shipped with an optional
fibre module. The fibre module will be connected directly to the access point, the user
should attach the fibre cable directly to the fibre module using a multimode fibre
cable on an ST connector.
3.1.7 Thermostat Control
The thermostats are currently not user configurable. The default configuration is for
the heaters to be turned on when the internal ambient temperature is between -20
o
C
and +10
o
C and for the fans/wireless hardware to be on above 1.5
o
C
3.1.8 Fitting the antennas
•Connect the antennas to the correct the N type connector on the outside of the
enclosure (see Diagram 3.1.1). Make sure to only connect antennas which are
intended to be used at the frequency required (i.e. either 2.4GHz or 5.8GHz
antennas).
•Depending on the options ordered some of the N-types may have been
replaced with blanking plugs or surge arrestors.
•If the version ordered contains both a mesh router and access point; the mesh
router and access point should be setup in software to run at 5.8GHz and
2.4GHz respectively. The iWAP200 will be wired in this way when delivered.
•The iWAP200 may be used with any antenna (all antennas will however, need
to be assessed to the BS EN 60079-11:2007 standard and approved by
Extronics for use with the iWAP200). It is recommended to use the Extronics
iANT200 series of antennas as these have already been pre-approved for use
with the iWAP200.
IMPORTANT! Do not exceed the Effective Isotropic Radiated Power (EIRP) for
the country/region of operation. Also do not exceed the maximum
EIRP for the gas group the iWAP200 is located in according to the
standard BS 6656:2002 table 2.
Important Only antennas which have been approved for use by Extronics for
the area which they are to be installed may be used with iWAP200.
Important Any plastic coated antenna shall have a warning label fitted to it
stating “WARNING – Potential electrostatic charging hazard. Wipe
only with a damp cloth”

Operating Manual
13
3.1.9 Mounting The Antennas
Extronics can supply two sizes of antenna brackets which can be mounted either on
the top or bottom of the enclosure. The bracket sizes offered are 365mm and 680mm
in length. The brackets allow the mounting of two antennas (either the iANT100 or
iANT200) at the far extremities of the bracket.
3.1.9.1 iANTMB02
316L SS Antenna bracket 365mm length for 2 iANT100 / iANT200
antennas for mounting on an iWAP enclosure
Bespoke mounting brackets can also be designed for most applications. Please
contact Extronics for more information.
3.1.10 Setting to work
•Once all cables are connected correctly, refit the enclosure lid using the four
screws previously removed. Use a torque screwdriver set to 2.5 Nm. Do not
over tighten screws.
•Refer to the original manufacturers instructions for a detailed information on
setting the network to work correctly.
Note! Ensure the lid is secure, correct cable glands are fitted and the
unit device correctly wired and earthed for the particular
application before applying power
Note! Ensure that the lid gasket is clean and undamaged before fitting
the lid.

Operating Manual
14
4 Intended Purpose Usage
Important Before setting the units to work read the technical documentation
carefully.
Important The latest version of the technical documentation or the corresponding
technical supplements is valid in each case.
The iWAP200 is built using modern components and is extremely reliable in
operation; however it must only be used for its intended purpose. Please note that
the intended purpose also includes compliance with the instructions issued by the
manufacturer for installation, setting up and service.
Any other use is regarded as conflicting with the intended purpose. The manufacturer
is not liable for any subsequent damage resulting from such inadmissible use. The
user bears the sole risk in such cases.
4.1 Transportation and Storage
All iWAP200 devices must be so transported and stored that they are not subjected
to any excessive mechanical stresses.
4.2 Authorized Persons
Only persons trained for the purpose are authorized to handle the iWAP200; they
must be familiar with the unit and must be aware of the regulation and provisions
required for correct installation as well as the relevant accident prevention
regulations.
4.3 Cleaning and Maintenance
The iWAP200 and all its components require no maintenance and are self-
monitoring. All work on the iWAP200 by personnel who are not expressly qualified for
such activities will cause the guarantee to become void.
4.4 Safety Precautions
Important For the installation, maintenance and cleaning of the units, it is
absolutely necessary to observe the applicable regulations and
provisions concerned with explosion protection (EN 60079-0:2006, EN
60079-14:2003) as well as the Accident Prevention Regulations.

Operating Manual
15
4.5 Cleaning and Maintenance Intervals
The cleaning intervals depend on the environment where the system is installed.
4.6 Aggressive substances and environments
The iWAP200 is not designed to come into contact with aggressive substances or
environments, please be aware that additional protection may be required.
4.7 Exposure to external stresses
The iWAP200 is not designed to be subjected to excessive stresses e.g. vibration,
heat, impact. Additional protection is required to protect against these external
stresses.
The iWAP200 will require additional protection if it is installed in a location where it
may be subjected to damage.

Operating Manual
16
5 Technical Data
5.1 Specification
Power Supply Universal 90-264VAC, 24VDC or IEEE802.3af POE
Maximum Power
Consumption (De endant on hardware)
16W without heating or cooling
21W with cooling
121W with heating
Enclosure Material 316L Stainless Steel
Ingress Protection IP66
Weight A roximately 10Kg, hardware de endent
Dimensions 390 x 286 x 300 mm (h x w x d)
Environmental Operating temperature:
Without heating or cooling –20
o
C to 55
0
C
With cooling –20
o
C
to 70
0
C
With heating and cooling –40
o
C
to 70
0
C
Storage temperature: –20
o
C
to 70
0
C
Relative humi ity: 0 to 95%, non condensing
Input Connections 10/100BaseT Ethernet on RJ45 socket and screw terminals
115V/230VAC in ut o tion on screw terminals
24VDC in ut o tion on screw terminals
Multimode fibre in ut o tion on ST connectors
Note that connectors may be s ecified as an o tion in the ordering data
Output Connections Dual energy-limited external RF out uts via N-ty e RF connectors with
o tional lightning arrestors
Ra io De endant u on chosen hardware
Antennas To be used with one or two intrinsically safe antennas (not included) e.g.
Extronics iANT200 series or any standard antenna conforming to the
conditions of safe use in the Ex certificate

17
5.2 Enclosure Dimensions

18
6 Type Codes
iWAP200 Zone 2 Access Point Enclosure iWAP200-[#1]-[#2]-[#3]-[#4]-[#5]-[#6]-[#7]-[#8]-[#9]-[#10]
Specify option [#1] - Wireless Network Har ware
Hardware su lied by customer* 0
Hardware su lied by Extronics 1
Specify option [#2] - Type Of Wireless Network Har ware
Symbol AP300 Access Port Single Radio 8
Symbol AP5131 Access Point Single Radio 9
Symbol AP300 Access Port Dual Radio 10
Symbol AP5131 Access Point Dual Radio 11
Meru AP200 13
Meru AP150 14
Firetide 6000 Series Mesh Router 20
Firetide 6000 Series Dual Radio Mesh Router 21
Firetide Hot oint 4500 Access Point 22
*Extronics can su ly the above wireless network hardware, alternatively you may wish to “free issue” one of the above
solutions so that we can factory fit it. Please note that new hardware not already on the list above will need to be
assessed and certified to determine its suitability.
Specify option [#3] - Wireless MESH Backhaul—Number of Ra ios
No Mesh Backhaul N
Single radio backhaul 1
Dual radio backhaul 2
Specify option [#4] - Power Supply
Universal 90-264VAC
(If heater o tion [#8] selected, the unit cannot use universal voltage, use either 115VAC or 230VAC)
AC
24V DC DC
IEEE802.3af com liant Power-Over-Ethernet POE
Specify option [#5] - Ethernet Connection
10/100BaseT Ethernet on CAT5 co er C
Multimode 10/100BaseFX fibre with ST connector F
Specify option [#6] - 2 x Antenna Lightning Protection For Option [#2]
No Surge Arrestors N
Surge Arrestors Fitted S
Specify option [#7] - 2 x Antenna Lightning Protection For Option [#2]/Option [#3]
No Surge Arrestors N
Surge Arrestors Fitted S
Specify option [#8] - Enclosure Heating (not compatible with universal 90-264VAC or POE supplies)
No enclosure heating
- T4/T5 tem erature classification
N
230VAC enclosure heating - T3 tem erature classification H1
115VAC enclosure heating - T3 tem erature classification H2
24VDC enclosure heating - T3 tem erature classification H3
Specify option [#9] - Enclosure Cable Entry
Cable glands fitted G
Quick Release Sockets fitted (Not for fibre o tic in ut) S
Specify option [#10] - Enclosure cooling (not compatible with POE supply)
No enclosure cooling N
Enclosure cooling fitted C

Operating Manual
19
7 Certification

Operating Manual
20
Other manuals for iWAP200
1
Table of contents
Other extronics Enclosure manuals