FGD FlameSpec IR3-H2 User manual

FlameSpec IR3-H2 User Manual Doc. No. F150V0020.09
4222 E. La Palma Ave, Anaheim, CA 92807 USA T: (+1) 714-671-8500
www.fg-detection.com · [email protected]
FlameSpec IR3-H2

Information
FlameSpec-IR3-H2 Triple IR H2 Flame Detector User Guide, January 2023
Copyright © Fire & Gas Detection Technologies Inc. All rights reserved.
The owner or authorized user of a valid copy of this manual may reproduce this publication for the
purpose of learning to use the specified equipment. No part of this publication may be reproduced or
transmitted for commercial purposes, such as selling copies of this publication or for providing paid for
support services.
The Fire & Gas Detection Technologies logo is a trademark of Fire & Gas Detection Technologies Inc.,
registered in the U.S. and other countries.
Every effort has been made to ensure that the information in this manual is accurate. However, Fire &
Gas Detection Technologies Inc. is not responsible for any inaccuracy or omission in this document. The
information in this document is subject to change without notice.
Legal Notice
Hardware, software or documentation is forbidden to reproduced, transmitted, transcribed, stored in a
retrieval system or translated into any language or computer language, in any form or by any means.
While great efforts have been made to assure the accuracy and clarity of this document, FIRE & GAS
DETECTION TECHNOLOGIES INC. assumes no liability resulting from any omissions in this document, or
from misuse of the information obtained herein. The information in this document has been carefully
checked and is believed to be entirely reliable with all of the necessary information included.
FIRE & GAS DETECTION TECHNOLOGIES INC. reserves the right to make changes to any products
described herein to improve reliability, function, or design, and reserves the right to revise this
document and make changes from time to time in content hereof with no obligation to notify any
persons of revisions or changes. FIRE & GAS DETECTION TECHNOLOGIES INC does not assume any
liability arising out of the application or any use of any product or circuit described herein; neither does
it convey license under its patent rights or the rights of others.

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com iii
Table of Contents
1. Introduction .................................................................................................................... 1
Features ..............................................................................................................................1
Model Number Description ..................................................................................................2
Internal tests .......................................................................................................................2
Product Overview ................................................................................................................3
Accessories ..........................................................................................................................4
2. Installation ..................................................................................................................... 8
General Considerations ........................................................................................................8
Preparations for Installation ............................................................................................... 11
Required Tools ................................................................................................................... 11
Certification Instructions .................................................................................................... 11
Mounting the Tilt Mount .................................................................................................... 12
Mounting the detector ....................................................................................................... 14
Electrical Wiring ................................................................................................................. 15
Current Output (0-20mA) Wiring ........................................................................................ 17
4 Wire Relay Connection .................................................................................................... 19
RS-485 Communication Network ........................................................................................ 20
Cabling Recommendations ................................................................................................. 20
Earth/Ground Regime ........................................................................................................ 21
3. Configuration options ................................................................................................... 22
Sensitivity .......................................................................................................................... 23
Ultra-Fast Detection ........................................................................................................... 23
Alarm Delay ....................................................................................................................... 23
Alarm Latch ....................................................................................................................... 23
Enable Pre-Alarm 0-20mA .................................................................................................. 24
Enable dirty window warning 0-20mA ................................................................................ 24
Auxiliary Relay ................................................................................................................... 24

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com iv
Window Heater ................................................................................................................. 24
Modbus Address ................................................................................................................ 24
Manual BIT – Alarm Output Test (Full Loop test) ................................................................. 24
4. Operation ..................................................................................................................... 25
Output Signals ................................................................................................................... 25
Testing............................................................................................................................... 26
Flame Simulator ................................................................................................................. 26
5 Maintenance ................................................................................................................ 27
Cleaning Procedure ............................................................................................................ 27
6 Troubleshooting ............................................................................................................ 28
7 Servicing ....................................................................................................................... 29
8 FGD Communicator Software ........................................................................................ 29
9 Specifications ................................................................................................................ 30
Fire Detection .................................................................................................................... 30
Electrical Specifications ...................................................................................................... 30
Outputs ............................................................................................................................. 31
Mechanical Specifications .................................................................................................. 31
Environmental Specifications ............................................................................................. 31
Product Labeling ................................................................................................................ 32
Approvals .......................................................................................................................... 34
Electromagnetic Compatibility ........................................................................................... 34
10 Performance .............................................................................................................. 35
FLS-IR3-H2-ASX1 (Standard Model) ..................................................................................... 35
False Alarm Immunity ........................................................................................................ 36
11 Ordering Information ................................................................................................. 37
12 Warranty ................................................................................................................... 38
Appendix A .......................................................................................................................... 39

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com v
List of Figures
Figure 1 - Front view of the FLS-IR3-H2 ........................................................................................................ 3
Figure 2 - Rear view of the FLS-IR3-H2 .......................................................................................................... 3
Figure 3 - Tilt mount ..................................................................................................................................... 4
Figure 4 - Weather COVER ............................................................................................................................ 4
Figure 5 - Pole Mount ................................................................................................................................... 5
Figure 6 - Air Shield ....................................................................................................................................... 5
Figure 7 - Flame Simulator Kit ....................................................................................................................... 6
Figure 8 - FLS-FSIM-IR3-H2 Flame Simulator Front View .............................................................................. 6
Figure 9 - Duct Mount DMX-S01 ................................................................................................................... 7
Figure 10 - Duct Mount DMW-S01 ............................................................................................................... 7
Figure 11 - Horizontal Field of View .............................................................................................................. 9
Figure 12 - Vertical Field of View .................................................................................................................. 9
Figure 13: Tilt Mount Base - Front View ..................................................................................................... 13
Figure 14: Tilt mount base – Side View ....................................................................................................... 13
Figure 15 - Detector on Tilt Mount – Side View.......................................................................................... 14
Figure 16 – Terminal View .......................................................................................................................... 15
Figure 17 – Source 4-Wire Scheme ............................................................................................................. 17
Figure 18 – Sink 4-Wire Scheme ................................................................................................................. 17
Figure 19 – Source 3-Wire Scheme ............................................................................................................. 18
Figure 20 – Sink 3-Wire Scheme ................................................................................................................. 18
Figure 21 - 4 Wire Relay Connection .......................................................................................................... 19
Figure 22: RS-485 Networking .................................................................................................................... 20

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com vi
List of Tables
Table 1: Terminal connections .................................................................................................................... 16
Table 2: Detector Configuration Options .................................................................................................... 22
Table 3: Sensitivity levels ............................................................................................................................ 23
Table 4: Output Signals ............................................................................................................................... 25

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 1
1. Introduction
The FlameSpec-IR3-H2 flame detector will detect hydrogen and other “energy transition” fires quickly
allowing actions to be initiated to minimize the extend of the fire. The detector addresses slow growing
fires as well as fast eruptions of fire using improved IR3 technology. The detector operates in all weather
and light conditions.
These features, along with a built-in event logger, provide additional means to study the cause and
development of fire events.
The detector is certified for use in hazardous area locations; it may also be used in other areas not
classified as hazardous. The two cable/conduit entries either side of the lower part of the detector
housing are for connecting power and outputs to associated signaling equipment.
During normal operation, the flame detector performs self-tests of its optics, electronics, and software.
These include a periodic BIT (Built-In-Test) in which the sensors and window cleanliness are tested.
Features
High sensitivity - up to 100ft (30m)
Ultra-fast detection mode - detection within 40 milliseconds for fireballs or explosions.
Detection of “energy transition” flames, like hydrogen, methane, syngas, and methanol
Extreme sensitivity: Up to 100 ft. (30m) for a 32” plume, 1.5secs response
Option: Improved speed of response for standard fires - (0.5s) for enclosed space protection, like spray
paint booths or printing presses
Built-in-Test (BIT) - Automatic and manual self-test of window cleanliness and detector operation.
Window heater to avoid condensation and icing.
Tilt mounting bracket for accurate detector positioning.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 2
Model Number Description
Model No are defined as follows:
FLS-IR3-H2 - A S X X
0 Standard, no Hart and not SIL certified.
1 Standard
5 Design for, but not limited to, automotive spray paint applications
where compliance with 0.5 s response (per NFPA 33) is needed.
Generally used for enclosed spare protection.
1 M25
2 ¾” NPT
1.2.1 Enhanced performance options
Option 5: Design for, but not limited to, enclosed space protection like automotive spray paint applications
where compliance with 0.5 s response (per NFPA 33) is needed
Internal tests
During normal operation, the flame detector performs self-tests of its optics, electronics and software. These
include a periodic BIT (Built-In-Test) in which the sensors and window cleanliness are tested. Any detected
fault is indicated as shown in Table 4 (in section 4). During “Dirty Window” fault the detection sensitivity is
significantly reduced, while “Fault” refers to critical faults which totally prevent flame detection.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 3
Product Overview
FIGURE 1 - FRONT VIEW OF THE FLS-IR3-H2
FIGURE 2 - REAR VIEW OF THE FLS-IR3-H2

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 4
Accessories
1.5.1 Mounting Bracket
The detector should be mounted using the
stainless-steel tilt mount part number FLS-
TMO-S01. This allows the detector to be
securely attached to a wall, pole or other
solid surface using appropriate fixings. See
section2.5 and 2.6 for further details.
F
IGURE
3
-
T
ILT MOUNT
1.5.2 Weather Cover
The weather
cover
P/N
FLS-WCO-S01
protect the detector from extreme
weather conditions such heat, rain and
snow
FIGURE 4 - WEATHER COVER

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 5
1.5.3 Pole mount
The pole mount enables the detectors
to be
installed with its tilt mount brackets. The pole
mount kit we supply are suitable for 2-inch or 3-
inch poles. Part number FLS-PMA-S23.
F
IGURE
5
-
P
OLE
M
OUNT
1.5.4 Air shield
The air shield P/N FLS-ASD-S01 allows installation of
flame detectors in harsh weather conditions where
they may be exposed to dust, sand, and other
particulate matter. The connection point can be
mounted in the 3, 9 or 12 o’clock locations.
Air pressure source: Clean, dry, and oil-free air
Pressure: 2-3 bar /30-45 psi
Fitting: 7/16”—20UNF-2A
Operation temperature: -55°C to +85°C / -67°F to
+185°F
F
IGURE
6
-
A
IR
S
HIELD

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 6
1.5.5 Flame Simulator
The FLS-IR3-H2 may be tested using the FLS-FSIM-
IR3-H2-KIT. The FlameSpec flame simulator family
provides a fast and convenient means of
periodically testing the detector and control system
end-to-end. Maintenance costs can be reduced as
the detectors can be tested in situ without needing
a hot work permit.
FlameSpec Flame Simulators emit IR radiation in a
special electromagnetic radiation pattern which
simulates a hydrogen fire to the detectors. The
simulators are lightweight, easy to use, with testing
distances of up to 23 ft. (7m) and capable of more
than 1000 activations between battery charging.
FlameSpec Flame Simulators are ATEX approved for
use in hazardous Zone 1, Zone 2, Zone 11, Zone 22
areas.
Each simulator kit contains a carrying case,
simulator, carrying strap, battery charger, user
manual, Allen key and a tool for removing the
simulator rear cover.
FIGURE 7 - FLAME SIMULATOR KIT
FIGURE 8 - FLS-FSIM-IR3-H2 FLAME SIMULATOR FRONT
V
IEW

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 7
1.5.6 Duct Mounts
Duct Mount DMX-S01
The FLS-DMX-S01 allows a standard (non-HD)
detector to be mounted remotely from a potential
fire source by allowing the device to look through
cut hole in the side of a duct. This duct mount must
be use with air shield FLS-ADS-S01
Duct Mount DMW-S01
The FLS-DMW-S01 allows a standard detector to be
mounted remotely from a potential fire source by
allowing the device to look through a special
sapphire window. It must be acknowledged that
the detector cannot tell if this window becomes
dirty and so a maintenance routine must be
established to check the optical contamination of
this window. Please note, the frequency of cleaning
needed will vary from installation to installation. It
is highly recommended therefore that a means of
access be designed into the installation, as close as
practicable to the assembly, for inspection and
cleaning purposes.
F
IGURE
9
-
D
UCT
M
OUNT
DMX
-
S01
F
IGURE
10
-
D
UCT
M
OUNT
DMW
-
S01

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 8
2. Installation
This chapter does not attempt to cover all of the standard practices and codes of installation.
Rather, it emphasizes specific points of consideration and provides some general rules for
qualified personnel. You must always observe special safety precautions.
General Considerations
This section includes important information.
To help obtain optimal performance, the detector should be aimed toward the center of
the hazard or area to be monitored and protected ("detection zone") and have, to the
extent that is required, an unobstructed view of the protected area. Whenever possible,
the detector face should be tilted (aimed) down at an angle to prevent the accumulation
of dust and dirt.
Do not start an installation until the performance target, system configuration,
installation location and coverage considerations have been defined by the responsible
person.
To ensure optimal performance the following guidelines should be addressed:
Sensitivity
To determine the sensitivity level, the following points should be considered:
The size of the fire to be detected at the determined distance.
The type of flammable fuel.
Potential sources of false alarms that may be present (e.g., naked flames, hot process).
Spacing and Location
Consider the following factors when determining the number of detectors and their locations in
the protected area:
The size and shape of the protected area
The nature of the hazards, including materials stored or used and the protected objects
The sensitivity of the detectors
If there are any obstructed lines of sight
The field of view of the detectors (See Figure 11 and Figure 12)

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 9
FIGURE 11 - HORIZONTAL FIELD OF VIEW
FIGURE 12 - VERTICAL FIELD OF VIEW

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 10
Environment
Environmental conditions including but not limited to dust, snow or rain can reduce the
detectors sensitivity and require additional consideration.
Hot Work
Arc welding should not be performed within 15 ft. (5m) of the detector. It is
recommended that the system be inhibited during welding operations in situations
where the possibility of a false alarm cannot be tolerated.
Gas welding requires a system inhibit, since the gas torch is an actual fire.
Arc welding rods can contain organic binder materials in the flux that burn during the
welding operation and are detectable by the device.
Welding rods with clay binders do not burn and should not be detected. However, a
system inhibit is always recommended, since the material being welded may be
contaminated with organic substances (paint, oil, etc.) that will burn and may be of the
size that should be detected.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 11
Preparations for Installation
The installation must comply with national and local regulations and standards applicable to
flame detectors (e.g., NFPA 72) and all local and common engineering practices. It is
recommended to consult with the authority having jurisdiction.
Prior to installation:
Make sure that you have all the components and tools required to complete the
detector installation readily available before beginning installation. In cases where you
cannot complete the installation in a single session, secure and seal the detectors and
conduits before leaving the site.
Use color-coded conductors or suitable wire markings or labels for the wiring. You may
use 14 to 17 AWG (2.5 to 1mm2) multi-strand wires for the site wiring. The selection of
wire gauge should be based on the number of detectors used on the same line and the
distance from the control unit, in compliance with specifications.
Individually screen twisted pair cable is recommended for RS485 terminals.
Use suitably rating wire for the application certification and temperatures.
Required Tools
The detector can be installed using the following tools:
Tool Function
Hex. KEY 6 mm Vertical alignment
Hex. KEY 10 mm Horizontal alignment
Wrench 13 mm Mounting the detector
Flat Screwdriver 6 mm Ground screw connection
Flat screwdriver 3.5mm Terminal connection
Certification Instructions
Warnings
Do not open the detector, even when isolated, when flammable atmosphere present.
The equipment may be used in hazardous areas with flammable gasses and vapors with
apparatus groups IIC, IIB and IIA and with temperature classes T1, T2, T3, T4 and T5. See
details of the explosion proof approvals in section 9.7.
The equipment is certified for use in ambient temperatures in the range of -67°F to
+167°F (-55°C to +75°C) or -67°F to +185°F (-55°C to +85°C) and should not be used in
temperatures outside this range.
Installation shall be carried out in accordance with the applicable code of practice by
suitably trained personnel.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 12
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice.
If the equipment is likely to come into contact with corrosive and other harsh
substances, consult with the relevant technical persons to take suitable precautions to
prevent the detector from being adversely affected, thus ensuring that the type of
protection is not compromised.
Harsh substances: For example, acidic liquids, gases, or solvents that may attack the
windows, metals, seals or polymeric materials.
Suitable precautions: For example, regular checks as part of routine inspections or
establishing from the material’s data sheet that it is resistant to specific chemicals.
Specific conditions for use
The equipment is not intended to be repaired by the user. Repair of this equipment shall
be carried out by the manufacturer in accordance with the applicable code of practice.
The flame paths are not intended for repair. Contact the manufacturer if the flame
paths are damaged.
Consult the manufacturer for genuine replacement cover and housing to connection box
fasteners. M6x1x18 Hexagonal Socket head fasteners with a minimum of ISO 4762
Grade A4 Class 80 are acceptable alternatives.
One suitably certified stopping plug is supplied with the detector.
The external earthing connection consists of cable lug with M5x10 stainless steel screw,
the terminals is suitable for connection of a wire of maximum 2.5mm2 / 14AWG.
The internal terminals are suitable for connection of a wire equal to or greater than the
power input wiring and at a minimum of 1mm2 / 17AWG conductor.
Mounting the Tilt Mount
The tilt mount enables the detector to be rotated up to 45 degrees (horizontal/vertical) in all
directions. The following installation instructions show how to use it to support the detector
from below (the preferred method). However, with a designated adapter the tilt mount can hold

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 13
the detector from above. Contact FGD for more details on mounts suitable for retro fit of
existing installations.
To install the tilt mount:
a) Mount the tilt mount base (Figure 13: Tilt Mount Base - Front View) to a solid structure using
four suitable fixings through the four 7mm (0.28") diameter holes. Four captive screws with
spring washers are provided in the tilt mount.
Figure 13: Tilt Mount Base - Front View
Figure 14: Tilt mount base – Side View

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 14
Mounting the detector
Referring to Figure 13 use the following steps to connect the detector to the tilt mount:
a) Place the detector, with its cable/conduit entries pointing down, on the holding plate of the
tilt mount (item 2).
b) Secure the detector to the plate using the two hex screws and spring lock washers (items 3
and 4).
c) Loosen the locking screws (Items 5 and 6) in such a way that enables you to rotate the
detector.
d) Point the detector towards the detection area and make certain that the view of the area is
unobstructed.
e) Secure the detector in that position by tightening the locking screws (Items 5 and 6) on the
tilt mount. (Make sure the detector is pointing in the correct direction).
The detector is now correctly mounted, aligned and ready for electrical connection. Please refer
to section 2.7 for wiring instructions, and section 3 for a description of the detector’s
configuration settings.
FIGURE 15 - DETECTOR ON TILT MOUNT – SIDE VIEW
3, 4
1
6
2
5
Other manuals for FlameSpec IR3-H2
1
Table of contents
Popular Gas Detector manuals by other brands

Comelit
Comelit 47RTS282E Series user manual

Axetris
Axetris LGD F200P2 Operation and integration instructions

Brunner
Brunner 3-SICUR Instructions for use

mPower Electronics
mPower Electronics POLI MP400 user guide

Honeywell
Honeywell Searchpoint Optima Plus operating instructions

Tecnogas
Tecnogas CD-34 quick start guide

Comelit
Comelit 47RTS282K user manual

New Cosmos Electric
New Cosmos Electric XP-3000II Series instruction manual

BW Technologies
BW Technologies GasAlert MicroClip XT instructions

Greystone Energy Systems
Greystone Energy Systems CEDT Series installation instructions

SENKO
SENKO SP secure operating manual

Geca
Geca Beta 752CO quick start guide