Fiber Mountain Sensus User manual

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
1
Sensus FPA Installation Manual
150-00006.01.04
Fiber Mountain
Sensus Patch Panel
Installation Manual

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
2
Sensus FPA Installation Manual
150-00006.01.04
Document History
The Sensus FPA Installation manual provides detailed safety instructions, specifications and
installation instructions.
The document history table that follows is used to track changes to this document, providing
an historical summary as the product evolves and matures.
150-00006 Document History:
Release Version
Date
Description of Change
Issue 1
13 December, 2017
Issue 1 release is intended for general distribution
Issue 2
15 January, 2018
Functionality updates
Issue 3
6 April, 2017
Functionality and installation updates
Issue 4
LED functionality added. FCC and IC registration documented.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
3
Sensus FPA Installation Manual
150-00006.01.04
Product & Company Information
This publication and the product it describes contain proprietary and confidential information.
No part of this document may be copied, photocopied, reproduced, translated or reduced to any
electronic or machine-readable format without prior written permission of Fiber Mountain, Inc. The
information in this document is subject to change without notice. Fiber Mountain assumes no
responsibility for any damages arising from the use of this document, including but not limited to, lost
revenue, lost data, claims by third parties, or other damages.
If you have comments or suggestions concerning this manual, please contact:
Fiber Mountain, Inc.
700 West Johnson Ave., Suite 100
Cheshire, Connecticut 06410
203-806-4040
www.fibermountain.com
Trademarks
The Fiber Mountain logo, Fiber Mountain symbol, Fiber Mountain, Glass Core, Connectivity
Virtualization, PLP, Intelligent Connection Identification, ICID, Sensus, and AllPath are all trademarks of
Fiber Mountain, Inc.
List of Related Publications
Documents related to Sensus FPA Installation Manual include:
Document Title
Document Part Number
Brief Description
Glass Core Operations Manual
150-00009
Glass Core Operations Manual
Sensus LCD Screen Guide
150-00007
Sensus LCD Screen Guide
Sensus Family Datasheet
DS-00122
Sensus Family Datasheet

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
4
Sensus FPA Installation Manual
150-00006.01.04
Table of Contents
1. Safety Instructions ...................................................................................................... 7
2. Consignes de sécurité............................................................................................... 15
3. Sensus Specifications............................................................................................... 23
3.1 Sensus Chassis Specifications .............................................................................. 23
3.2 Sensus Management Module Specifications .......................................................... 23
3.3 Sensus Patching Modules Specifications ............................................................... 23
4. Installation of Sensus FPA......................................................................................... 24
4.1 Installing the Modules into the Sensus Chassis ...................................................... 24
4.2 Fiber Cable Support............................................................................................... 25
4.3 Attaching Sensus Cable Fingers and Rack-Mounting the Sensus Chassis ............... 26
4.3.1 Installing the LC-to-LC extension ...................................................................... 27
4.4 Powering the Sensus Device.................................................................................. 29
5. Front Panel LC Tx and Rx Port Legend....................................................................... 30
5.1 96xLC to 8xMPO-12, Front-to-Back Mapping......................................................... 30
6. Getting Started .......................................................................................................... 31
6.1 Craft Interface - PC Console Port Settings.............................................................. 31
6.2 Changing the Sensus’ Local/SHH IP Address......................................................... 32
6.2.1 Changing IP Address from the LCD screen ....................................................... 32
6.2.2 Changing IP Address from the Craft Port........................................................... 33
6.3 View the Sensus’ current IP address...................................................................... 33
6.4 Tail the Sensus log via the SSH craft port............................................................... 34
6.5 Changing the hostname of the Sensus device ........................................................ 35
6.6 Changing the SFP status from the Sensus screen................................................... 36
6.7 Discovering Sensus products with APD ................................................................. 36
6.8 Password Recovery Procedure.............................................................................. 37

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
5
Sensus FPA Installation Manual
150-00006.01.04
Table of Figures
Figure 4-1: Sensus Cable Support Fingers ........................................................................... 25
Figure 4-2: Sensus with cable support fingers attached to rack mount ears.......................... 26
Figure 4-3: Sensus Extended Rack Mount Ears.................................................................... 27
Figure 4-4: Installing LC-to-LC Extension Cover ................................................................... 28
Figure 5-1: 96xLC to 8xMPO-12 Port Mapping..................................................................... 30
Figure 6-1: RJ-45 Connector............................................................................................... 31
Figure 6-2: Input New IP Information ................................................................................... 32
Figure 6-3: Sensus Set New Address................................................................................... 33
Figure 6-4: Sensus Current IP Address ................................................................................ 34
Figure 6-5: Toggling SFP Functionality................................................................................. 36

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
6
Sensus FPA Installation Manual
150-00006.01.04
Please Read This Entire Manual
Important
Please read this entire guide before you install or operate this product. Give particular attention
to all safety statements.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
7
Sensus FPA Installation Manual
150-00006.01.04
1. Safety Instructions
Standards
Icon
Meaning
Explanation
Note
Indicates important features or instructions.
Caution
Indicates that you may risk losing data or damaging your hardware.
Warning
Alerts you to the risk of personal injury.
Laser Warning
Laser output may be hazardous if viewed with magnifying optics.
Protect yourself from electric shock and your system from damage!
•This product complies with international safety and design standards. Observe all safety
procedures that appear throughout this guide and the safety symbols that are affixed to this
product.
•If circumstances impair the safe operation of this product, stop operation and secure this
product against further operation.
Avoid personal injury and product damage! Do not proceed beyond any symbol until you fully
understand the indicated conditions!
Power
WARNING:
Redundant Power –The unit is provided with redundant power system. Disconnect all supplies before
servicing!
•Important! This is a Class I product. You must earth this product. This equipment may
have up to two power supply cords. To reduce the risk of electric shock, two power supply
cords may have to be disconnected before servicing.
•This product plugs into a socket-outlet. The socket-outlet must be near this product, and
must be easily accessible.
•Connect this product only to the power source that is indicated on the rear panel of this
product.
•If this product does not have a mains power switch, the power cord serves this purpose.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
8
Sensus FPA Installation Manual
150-00006.01.04
Laser
WARNING:
Laser Warnings: Laser output may be hazardous if viewed with magnifying optics.
Invisible laser radiation may be emitted from disconnected fibers or connectors. Do not stare
into beams or view directly with optical instruments.
Class I (21 CFR 1040.10 and 1040.11) and Class 1M (IEC 60825-1 2001-01) laser products.
Statement 291
Cables
•Always disconnect all power cables before servicing this product.
•Always pull on the plug or the connector to disconnect a cable. Never pull on the cable
itself.
•Do not walk on or place stress on cables or plugs.
Factory service
•Refer service only to service personnel who are authorized by the manufacturer.
Read and Retain Instructions
•Carefully read all safety and operating instructions before operating this equipment, and
retain them for future reference.
Follow Instructions and Heed Warnings
•Follow all operating and use instructions. Pay attention to all warnings and cautions in the
operating instructions, as well as those that are affixed to this equipment.
Terminology
The terms defined below are used in this document. The definitions given are based on those
found in safety standards.
Service Personnel - The term “service personnel”applies to trained and qualified individuals
who are allowed to install, replace, or service electrical equipment. The service personnel are expected
to use their experience and technical skills to avoid possible injury to themselves and others due to
hazards that exist in service and restricted access areas.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
9
Sensus FPA Installation Manual
150-00006.01.04
User and Operator - The terms “user”and “operator”apply to persons other than service
personnel.
Ground(ing) and Earth(ing) - The terms “ground(ing)”and “earth(ing)”are synonymous. This
document uses “ground(ing)”for clarity, but it can be interpreted as having the same meaning as
“earth(ing).”
Electric Shock Hazard
This equipment meets applicable safety standards.
WARNING:
To reduce risk of electric shock, perform only the instructions that are included in the operating
instructions. Refer all servicing to qualified service personnel only.
•Electric shock can cause personal injury or even death. Avoid direct contact with
dangerous voltages at all times. The protective ground connection is essential to safe
operation and must be verified before connecting the power supply.
•Know the following safety warnings and guidelines:
oDangerous Voltages
▪Only qualified service personnel are allowed to perform equipment installation or
replacement.
▪Only qualified service personnel are allowed to remove chassis covers and access
any of the components inside the chassis.
oGrounding
▪Do not violate the protective grounding by using an extension cable, power cable,
or autotransformer without a protective ground conductor.
▪Take care to maintain the protective grounding of this equipment during service or
repair and to re-establish the protective grounding before putting this equipment
back into operation.
Federal Communications Commission (FCC) Compliance Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
10
Sensus FPA Installation Manual
150-00006.01.04
in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Fiber Mountain has not approved any changes or modifications to this device by the user. Any
changes or modifications could void the user’s authority to operate the equipment. See 47 CFR Sec.
15.21.
FCC ID: 2APNW - SENFG1MA
Installation Site
•When selecting the installation site, comply with the following:
•Protective Ground - The protective ground lead of the building's electrical installation
should comply with national and local requirements.
•Environmental Condition –The installation site should be dry, clean, and ventilated. Do
not use this equipment where it could be at risk of contact with water. Ensure that this
equipment is operated in an environment that meets the requirements as stated in this
equipment's technical specifications, which may be found on this equipment's data sheet.
Installation Requirements
WARNING:
Allow only qualified service personnel to install this equipment. The installation must conform to all
local codes and regulations.
Equipment Placement
WARNING:
Avoid personal injury and damage to this equipment. An unstable mounting surface may cause this
equipment to fall.
To protect against equipment damage or injury to personnel, comply with the following:
•Install this equipment in a restricted access location.
•Do not install near any heat sources such as radiators, heat registers, stoves, or other
equipment (including amplifiers) that produce heat.
•Place this equipment close enough to a mains AC outlet to accommodate the length of this
equipment's power cord.
•Route all power cords so that people cannot walk on, place objects on, or lean objects
against them. This may pinch or damage the power cords. Pay particular attention to
power cords at plugs, outlets, and the points where the power cords exit this equipment.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
11
Sensus FPA Installation Manual
150-00006.01.04
•Use only with a cart, stand, tripod, bracket, or table specified by the manufacturer, or sold
with this equipment.
•Make sure the mounting surface or rack is stable and can support the size and weight of
this equipment.
•The mounting surface or rack should be appropriately anchored according to
manufacturer's specifications. Ensure this equipment is securely fastened to the mounting
surface or rack where necessary to protect against damage due to any disturbance and
subsequent fall.
Ventilation
This equipment has openings for ventilation to protect it from overheating. To ensure
equipment reliability and safe operation, do not block or cover any of the ventilation openings. Install
the equipment in accordance with the manufacturer's instructions.
Rack Mounting Safety Precautions
Mechanical Loading
•Make sure that the rack is placed on a stable surface. If the rack has stabilizing devices,
install these stabilizing devices before mounting any equipment in the rack.
WARNING:
Avoid personal injury and damage to this equipment. Mounting this equipment in the rack should be
such that a hazardous condition is not caused due to uneven mechanical loading.
Reduced Airflow
•When mounting this equipment in the rack, do not obstruct the cooling airflow through the
rack. Be sure to mount the blanking plates to cover unused rack space. Additional
components such as combiners and net strips should be mounted at the back of the rack,
so that the free airflow is not restricted.
CAUTION:
Installation of this equipment in a rack should be such that the amount of airflow required for safe
operation of this equipment is not compromised.
Elevated Operating Ambient Temperature
•Only install this equipment in a humidity- and temperature-controlled environment that
meets the requirements given in this equipment's technical specifications.
CAUTION:

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
12
Sensus FPA Installation Manual
150-00006.01.04
If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack
environment may be greater than room ambient temperature. Therefore, install this equipment in an
environment compatible with the manufacturer's maximum rated ambient temperature.
Handling Precautions
•When moving a cart that contains this equipment, check for any of the following possible
hazards:
WARNING:
Avoid personal injury and damage to this equipment! Move any equipment and cart combination with
care. Quick stops, excessive force, and uneven surfaces may cause this equipment and cart to overturn.
•Use caution when moving this equipment/cart combination to avoid injury from tip-over.
•If the cart does not move easily, this condition may indicate obstructions or cables that
may need to be disconnected before moving this equipment to another location.
•Avoid quick stops and starts when moving the cart.
•Check for uneven floor surfaces such as cracks or cables and cords.
Grounding
This section provides instructions for verifying that the equipment is properly grounded.
Safety Plugs
Equipment protection Class I - FMI supplies a mains cord with a 3-terminal (grounding-type)
safety plug. Do not defeat the safety purpose of the grounding type or polarized safety plug.
To properly ground this equipment, follow these safety guidelines:
•Grounding-Type Plug - For a 3-terminal plug (one terminal on this plug is a protective
grounding pin), insert the plug into a grounded mains, 3-terminal outlet.
Note: This plug fits only one way. If this plug cannot be fully inserted into the outlet,
contact an electrician to replace the obsolete 3-terminal outlet.
AC Power
This equipment is Class I equipment, it must be grounded.
•If this equipment plugs into an outlet, the outlet must be near this equipment, and must be
easily accessible.
•Connect this equipment only to the power sources that are identified on the equipment-
rating label normally located close to the power inlet connector(s).

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
13
Sensus FPA Installation Manual
150-00006.01.04
•If this equipment has two power sources be sure to disconnect all power sources before
working on this equipment.
•If this equipment does not have a main power switch, the power cord connector serves as
the disconnect device.
•Always pull on the plug or the connector to disconnect a cable. Never pull on the cable
itself.
•Unplug this equipment when unused for long periods of time.
Circuit Overload
Know the effects of circuit overloading before connecting this equipment to the power supply.
CAUTION:
Consider the connection of this equipment to the supply circuit and the effect that overloading of circuits
might have on overcurrent protection and supply wiring. Refer to the information on the equipment-rating
label when addressing this concern.
General Servicing Precautions
WARNING:
Avoid electric shock! Opening or removing this equipment's cover may expose you to dangerous
voltages. Be aware of the following general precautions and guidelines:
•Servicing –Disconnect all supplies before servicing. Refer all servicing to qualified service
personnel. Servicing is required when this equipment has been damaged in any way, such
as power supply cord or plug is damaged, liquid has been spilled or objects have fallen
into this equipment, this equipment has been exposed to rain or moisture, does not operate
normally, or has been dropped.
•Wrist watch and Jewelry - For personal safety and to avoid damage of this equipment
during service and repair, do not wear electrically conducting objects such as a wristwatch
or jewelry.
•Lightning - Do not work on this equipment, or connect or disconnect cables, during
periods of lightning.
•Labels - Do not remove any warning labels. Replace damaged or illegible warning labels
with new ones.
•Covers - Do not open the cover of this equipment and attempt service unless instructed to
do so in the instructions. Refer all servicing to qualified service personnel only.
•Moisture - Do not allow moisture to enter this equipment.
•Cleaning - Use a damp cloth for cleaning.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
14
Sensus FPA Installation Manual
150-00006.01.04
•Safety Checks - After service, assemble this equipment and perform safety checks to
ensure it is safe to use before putting it back into operation.
Accessories
Use only attachments or accessories specified by Fiber Mountain Inc.
Se il vous plaît lire ce manuel en entier
Important
Se il vous plaît lire l'intégralité de ce guide avant d'installer ou d'utiliser ce produit. Accorder
une attention particulière à toutes les consignes de sécurité.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
15
Sensus FPA Installation Manual
150-00006.01.04
2. Consignes de sécurité
Normes
Icône
Sens
Explication
Remarque
Indique caractéristiques ou des instructions importantes.
Prudence
Indique que vous risquez de perdre des données ou d'endommager votre matériel.
Avertissement
Vous avertit des risques de blessures.
Avertissement de
laser
Sortie laser peut être dangereuse si on la regarde avec des optiques grossissantes.
Protégez-vous contre les chocs électriques et votre système de dommages!
•Ce produit est conforme aux normes de sécurité et de design internationaux. Observez
toutes les procédures de sécurité qui apparaissent dans ce guide, et les symboles de
sécurité qui sont fixés à ce produit.
•Si les circonstances compromettre l'exploitation sûre de ce produit, arrêter le
fonctionnement et sécuriser ce produit contre d'autres opérations.
Éviter les blessures et endommagement du produit! Ne pas aller au-delà tout symbole jusqu'à
ce que vous comprenez parfaitement les conditions indiquées!
Puissance
AVERTISSEMENT:
Alimentation redondante - L'appareil est fourni avec le système d'alimentation redondante. Débranchez
toutes les fournitures avant l'entretien!
•Important! Ce est un produit de classe I. Vous devez terre ce produit. Cet équipement
peut avoir jusqu'à deux cordons d'alimentation. Pour réduire le risque de choc électrique,
deux cordons d'alimentation peuvent être déconnectés avant l'entretien.
•Ce produit se branche sur une prise de courant. La prise de courant doit être à proximité
de ce produit, et doit être facilement accessible.
•Connectez ce produit qu'à la source d'alimentation qui est indiqué sur le panneau arrière de
ce produit.
•Si ce produit ne possède pas d'interrupteur d'alimentation secteur, le cordon d'alimentation
sert à cette fin.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
16
Sensus FPA Installation Manual
150-00006.01.04
Laser
AVERTISSEMENT:
Avertissements laser: Sortie laser peut être dangereuse si on la regarde avec des optiques grossissantes.
Les fibres ou connecteurs débranchés risquent d'émettre des rayonnements laser invisibles à
l'œil. Ne regardez jamais directement les faisceaux laser à l'œil nu, ni d'ailleurs avec des instruments
optiques. Classe I (21 CFR 1040.10 and 1040.11) et Classe 1M (IEC 60825-1 2001-01) produits
laser. Déclaration 291.
Câbles
•Toujours débrancher tous les câbles d'alimentation avant de réparer ce produit.
•Tirez toujours sur la fiche ou le connecteur pour déconnecter un câble. Ne tirez jamais sur
le câble lui-même.
•Ne pas marcher ou placer le stress sur les câbles ou les bouchons.
service de l'usine
Reportez-vous service uniquement au personnel de service qui sont autorisées par le fabricant.
Lisez et Conservez les instructions
Lisez attentivement toutes les instructions de sécurité et de fonctionnement avant d'utiliser cet
équipement, et les conserver pour référence future.
Suivez les instructions et avertissements Respectez
Suivez toutes les instructions de fonctionnement et d'utilisation. Faites attention à tous les
avertissements dans les instructions d'utilisation, ainsi que ceux qui sont apposées à cet équipement.
Terminologie
Les termes définis ci-dessous sont utilisés dans ce document. Les définitions données sont
basés sur ceux trouvés dans les normes de sécurité.
Service du personnel - Le personnel de service à long terme se applique aux personnes
formées et qualifiées qui sont autorisés à installer, remplacer ou équipements électriques de
service. Le personnel de service sont tenus d'utiliser leur expérience et leurs compétences techniques
pour éviter les blessures à eux-mêmes et les autres en raison de risques qui existent dans le service et
zones d'accès restreint.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
17
Sensus FPA Installation Manual
150-00006.01.04
Utilisateur et l'opérateur - Les termes utilisateur et l'opérateur se appliquent aux personnes
autres que le personnel de service.
Rez (ING) et de la Terre (ing) - Les termes sol (ING) et la terre (ING) sont synonymes. Ce
document utilise sol (ing) pour plus de clarté, mais il peut être interprété comme ayant la même
signification que la terre (ING).
Risque de choc électrique
Cet équipement répond aux normes de sécurité applicables.
AVERTISSEMENT:
Pour réduire les risques de choc électrique, ne effectuer que les instructions qui sont inclus dans la
notice d'utilisation. Confiez toute réparation à un personnel qualifié seulement.
•Un choc électrique peut entraîner des blessures ou même la mort. Eviter le contact direct
avec des tensions dangereuses en tout temps. La protection à la terre est essentielle pour
un fonctionnement sûr et doit être vérifiée avant de brancher l'alimentation.
•Connaître les avertissements et les consignes de sécurité suivantes:
oTensions dangereuses
▪Seul le personnel de service qualifiés sont autorisés à procéder à
l'installation de l'équipement ou de remplacement.
▪Seul le personnel de service qualifiés sont autorisés à retirer les capots du
châssis pour accéder aux composants internes du châssis.
oÉchouage
▪Ne pas violer la terre de protection en utilisant un câble d'extension, câble
d'alimentation, ou autotransformateur sans conducteur de protection.
▪Prenez soin de maintenir la terre de protection de cet équipement pendant
le service ou la réparation et à rétablir la terre de protection avant de mettre
cet équipement en service.
Site d'installation
•Lors de la sélection du site d'installation, respecter les conditions suivantes:
•Rez de protection - Le fil de terre de protection de l'installation électrique du bâtiment doit
être conforme aux exigences nationales et locales.
•État de l'environnement - Le site d'installation doit être sec, propre et aéré. Ne pas
utiliser cet équipement où il pourrait être à risque de contact avec l'eau. Assurez-vous que
cet équipement est utilisé dans un environnement qui répond aux exigences énoncées
dans les spécifications techniques de cet équipement, qui peuvent être trouvés sur la fiche
technique de cet équipement.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
18
Sensus FPA Installation Manual
150-00006.01.04
Exigences d'installation
AVERTISSEMENT:
Seul un personnel de service qualifié pour installer cet équipement. L'installation doit être conforme à
tous les codes et règlements locaux.
Équipement Placement
AVERTISSEMENT:
Éviter les blessures et les dommages à cet équipement. Une surface de montage instable peut
provoquer cet équipement à l'automne.
Pour se protéger contre des dommages matériels ou corporels, respecter ce qui suit:
•Installez cet appareil dans un endroit à accès restreint.
•Ne pas installer près de sources de chaleur telles que des radiateurs, registres de chaleur,
poêles ou autres appareils (y compris les amplificateurs) produisant de la chaleur.
•Placez cet équipement suffisamment près d'une prise secteur AC pour accueillir la
longueur du cordon d'alimentation de cet équipement.
•Route tous les cordons d'alimentation de sorte que les gens ne peuvent pas marcher sur,
placer des objets sur ou objets maigres contre eux. Cela peut pincer ou endommager les
cordons d'alimentation. Faites particulièrement attention aux cordons d'alimentation au
niveau des fiches, prises, et les points où les cordons d'alimentation sortent cet
équipement.
•Utilisez uniquement avec un chariot, socle, trépied, support ou table spécifié par le
fabricant, ou vendus avec cet équipement.
•Assurez-vous que la surface de montage ou un rack est stable et peut supporter la taille et
le poids de cet équipement.
•La surface de montage ou un rack doivent être ancrés de façon appropriée selon les
spécifications du fabricant. Assurez-vous cet équipement est solidement fixé à la surface
de montage en rack ou si nécessaire pour protéger contre les dommages dus à toute
perturbation et la chute subséquente.
Ventilation
Cet équipement a des ouvertures pour la ventilation pour protéger de la surchauffe. Pour
assurer la fiabilité de l'équipement et un fonctionnement sûr, ne pas obstruer ou recouvrir l'une des
ouvertures de ventilation. Installer le matériel conformément aux instructions du fabricant.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
19
Sensus FPA Installation Manual
150-00006.01.04
Montage en rack Mesures de sécurité
Chargement mécanique
•Assurez-vous que le rack est placé sur une surface stable. Si le support a des dispositifs
de stabilisation, installer ces dispositifs de stabilisation avant de monter l'équipement dans
le rack.
AVERTISSEMENT:
Éviter les blessures et les dommages à cet équipement. Montage cet équipement dans le rack doit être
telle qu'une situation dangereuse ne est pas due à une charge mécanique irrégulière.
Airflow réduit
•Lors du montage de cet équipement dans le rack, ne pas obstruer le flux d'air de
refroidissement à travers la grille. Ne oubliez pas de monter les plaques d'obturation pour
couvrir l'espace rack utilisé. Des éléments additionnels tels que les multiplexeurs et les
bandes nettes doivent être montés à l'arrière du rack, de sorte que le flux d'air libre ne est
pas limité.
ATTENTION:
Installation de cet équipement dans un rack doit être telle que le volume d'air nécessaire au bon
fonctionnement de cet équipement ne est pas compromise.
Température ambiante de fonctionnement Température
•Seulement installer cet équipement dans un environnement humidité et à température
contrôlée qui répond aux exigences énoncées dans les spécifications techniques de cet
équipement.
ATTENTION:
Se il est installé dans un rack fermé ou à unités multiples, la température ambiante de fonctionnement de
l'environnement du rack peut être supérieure à la température ambiante de la pièce. Par conséquent,
installer cet équipement dans un environnement compatible avec la température ambiante nominale
maximale du fabricant.
Précautions d'emploi
•Lors du déplacement d'un panier qui contient cet équipement, vérifier l'un des dangers
possibles suivantes:
AVERTISSEMENT:
Éviter les blessures et les dommages à cet équipement! Déplacez tout équipement et chariot avec
soin. Des arrêts brusques, une force excessive et des surfaces inégales peuvent causer cet équipement
et le chariot.

©Copyright 2018, Fiber Mountain, Inc. All Rights Reserved
20
Sensus FPA Installation Manual
150-00006.01.04
•Soyez prudent lorsque vous vous déplacez ce / panier combinaison d'appareils pour éviter
les blessures en cas de chute.
•Si le panier ne se déplace pas facilement, cette condition peut indiquer des obstacles ou
des câbles qui peuvent avoir besoin d'être débranchés avant de déplacer cet équipement à
un autre endroit.
•Évitez les arrêts et les démarrages rapides lors du déplacement du panier.
•Vérifiez pour les surfaces de plancher inégal tels que des fissures ou des câbles et
cordons.
Échouage
Cette section fournit des instructions pour vérifier que l'équipement est correctement mis à la
terre.
fiches de sécurité
Équipement de protection Classe I - FMI fournit un cordon d'alimentation avec une fiche de
sécurité 3-terminal (de type mise à la terre). Ne pas contourner le dispositif de sécurité du type de
mise à la terre ou la fiche de sécurité polarisée.
Pour bien la masse de cet appareil, suivre les consignes de sécurité:
•Mise à la terre de type plug - Pour une prise à 3 bornes (une borne sur cette fiche est
une broche de terre de protection), insérer la fiche dans un secteur à la terre, sortie 3-
terminal.
Remarque: Cette fiche se adapte une seule façon. Si cette fiche ne peut être entièrement
insérée dans la prise, contactez un électricien pour remplacer la prise à 3 bornes obsolète.
AC Power
Cet équipement est un équipement de classe I, il doit être mis à la terre.
•Si cet équipement se branche dans une prise, la prise doit être près de cet équipement et
doit être facilement accessible.
•Connectez cet appareil uniquement à des sources d'énergie qui sont identifiés sur
l'étiquette équipement note normalement situé près du connecteur (s) d'entrée de
puissance.
•Si cet équipement dispose de deux sources d'alimentation veillez à débrancher toutes les
sources d'alimentation avant de travailler sur cet appareil.