Filsa L-E4 User manual

Página
Index
Capacitive level indicator
for liquids or solids
L-E4 and L-E4S
Operating
Instructions
Talleres Filsa, S.A.U. www.filsa.es• • • • •E-08100 Mollet del Vallès (Barcelona) Tel. +34 93 570 46 01 Fax +34 93 570 24 71 [email protected] 01
07/14 MI-LE4-EN-01© by FILSA
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
Operating instructions
1. Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
1.1 Intended use
1.2 Function
1.3 Technical data
1.4 Materials
1.5 Dimensions
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
2.1 Preparing for use
2.2 Mechanical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
2.3 Electrical connection
3. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
3.1 Commissioning
3.2 Normal operation
3.3 Inexpert handling
4. Maintenance, servicing and spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
4.1 Maintenance
4.2 Servicing
4.3 Spare parts
5. Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
6. Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05

Read these Safety Instructions before using the switch for the first time and follow the Operating instructions.
Safety instructions
1. The installation, initial operation and maintenance should only be carried out by a qualified expert with electrical know-how.
2. Comply with the local and statutory rules and/or the VDE0100.
3. Before electrical connection, check the specifications on the data plate and the technical data of this manual.
4. A fuse must be connected in series to the supply voltage, according to the Standard and Normative documents.
5. Protect the signal contacts of the limit switch against voltage peaks when inductive or capacitive loads are connected.
6. The device may be put into operation only if the electrical connection is correct. To secure the type of protection, the sealing cap and the gasket
must be placed correctly and the screw nut of the cable gland has to be fixed and fastened to the cable entry.
7. The rod must not to be struck by the filling stream.
8. For a proper function in side mountings, the device should be installed with a 20 º to 30 º slope from the horizontal onto the silo wall to to facilitate
the flow of the material and to prevent the material from remaining over the probe.
9. For a proper function, the device should be installed with a distance of minimum 300 mm from the silo walls.
10. Switch off the power supply, before disconnecting the device.
Therefore the bulk material stream should be directed or redirected accordingly, or install a
stable deflector or protective cover. Also, this protection roof or cover has to be installed in the detection of minium levels in silos or vessels where
heavy loads due to the nature of the materials or the emptying system may damage the rod.
L-E4 and L-E4S
02 Talleres Filsa, S.A.U. www.filsa.es• • • • •E-08100 Mollet del Vallès (Barcelona) Tel. +34 93 570 46 01 Fax +34 93 570 24 71 [email protected]
07/14 MI-LE4-EN-02© by FILSA

Operating instructions
1. Specification
1.1 Intended use
The capacitive levels indicators L-E4 are to be used to control the
maximum or minimum level of liquid like water, oil, chemical
products, etc., in tanks or recipients and the capacitive levels
indicators L-E4S are to be used to control the maximum or
minimum level of bulk solids in silos or vessels.
These indicators have a Stainless Steel rod recovered of PTFE
and the devices can have a shaft up to 2.000 mm length
depending of the product to control.
1.2 Function
The rod must to be exposed to the material. When the level of
product reaches the rod, the control unit reverses the signal due to
a change of the capacity of the environment.
When the product disappear from the detection range, the
signal turns to the initial position.
These devices have inside the housing a regulation system that
allow the adjustment of the sensitivity due to a nut in the electronic
module.
1.3 Technical data
Manufacturer Talleres Filsa, S.A.U.
Address Bernat Metge, 33
08100 Mollet del Vallès
(Barcelona)
Name Capacitive level indicator
Type L-E4 ref: 2170-4
L-E4S ref: 2170-4S
Supply voltage Standard 230 V AC (50 ... 60 Hz)
(Under request 115 V AC, 24 V AC, 12 ... 35 V DC)
1 VA
Cable entry 2 of M20x1.5
Weight 1.40 kg depending on the model
1.4 Materials
Housing Polycarbonate
Rod Stainless Steel 1.4305
Rod cover PTFE
Power consumption
Product temperature -10 °C ... +90 °C
Ambient temperature -10 °C ... +60 °C
Relay output 1 NA + 1 NC
1 A / 250 V AC
Function status Under voltage: green LED
Relay enabled: red LED
Protection IP65 according DIN EN60529
1.5 Dimensions
Approximate measures are given in mm.
2. Installation
-
-
-
-
2.1 Preparing for use
The rod must not to be struck by the filling stream.
For a proper function in side mountings, the device should be
installed with a 20 º to 30 º slope from the horizontal onto the silo
wall to to facilitate the flow of the material and to prevent the
material from remaining over the probe.
For a proper function, the device should be installed with a
distance of minimum 300 mm from the silo walls.
Read the Safety Instructions and the Operation Instructions
before using the controller.
stable deflector or protective cover. Also, this
protection roof or cover has to be installed in the detection of
minium levels in silos or vessels where heavy loads due to the
nature of the materials or the emptying system may damage the
rod.
Therefore the
bulk material stream should be directed or redirected accordingly,
or install a
L-E4 and L-E4S
Talleres Filsa, S.A.U. www.filsa.es• • • • •E-08100 Mollet del Vallès (Barcelona) Tel. +34 93 570 46 01 Fax +34 93 570 24 71 [email protected] 03
07/14 MI-LE4-EN-03© by FILSA
80x80
85
38
35
Ø12
Under request, maximum length 2.000 mm
46
G 1 "
LE4-001
Weather protection
Protection roof
Min. 300mm
LE4-002

Sensitivity
adjustment
Supply
ON: Relay engaged WITH PRODUCT
OFF: Relay engaged WITHOUT PRODUCT
C NO NC
1 A / 250 V AC
The green LED is illuminated when the device is
connected to the supply. The red LED is
illuminated when the relay is engaged.
3.3 Inexpert handling
- Ignoring the Safety instructions and the Operating instructions.
- Not intended use.
- Making changes or handling the controller.
- Violation against applicable Law and Standards.
- Using of non original parts.
4. Maintenance, servicing and spare parts
4.1 Maintenance
- If used correctly, no specific maintenance is required.
4.2 Servicing
- Check and review the state of the housing, the rod and the correct
commutation of the electrical contact, as well.
4.3 Spare parts
- Use original spare parts.
- The only possible spare part for these controllers is the electronic
module.
5. Storage
- Store the controller in a dry and dust-free environment.
6. Disposal
-
- The controller can be recycled.
- The disposal applies to the valid environmental Guidelines
according to the location of the carrier and the local
manufacturing conditions.
Switch off the power supply, before disconnecting the device.
2.2 Mechanical connection
The device can be mounted horizontally or vertically depending on
the model.
The normal installation is by screwing the device onto the deposit
wall, with a mounting flange or
2.3 Electrical connection
Connection diagram
Cable gland
with an appropiate support to fix it.
- Fasten the cable gland after making the electrical connection.
- Fix and fasten the screw nut of the cable glandto ensure the
water-tightness.
3. Use
3.1 Commissioning
- Put the controller into operation only if the installation and the
electrical connection have been done correctly.
3.2 Normal operation
- Use the pneumatic controller in its intended application only.
- Comply with the specifications
- If the controller is damaged, disconnect it immediately.
- It is forbidden to make changes to the device. This violates the
Normative.
on the data plate and the
technical data of this manual.
L-E4 and L-E4S
04 Talleres Filsa, S.A.U. www.filsa.es• • • • •E-08100 Mollet del Vallès (Barcelona) Tel. +34 93 570 46 01 Fax +34 93 570 24 71 [email protected]
07/14 MI-LE4-EN-04© by FILSA
LE4-003
FILSA constantly strives to improve its products and reserves the right to modify designs, materials and data without prior notice.
Keep this manual for further questions!
This manual suits for next models
1
Other Filsa Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

PCB Piezotronics
PCB Piezotronics IMI SENSORS TO604B91 Installation and operating manual

CARLO GAVAZZI
CARLO GAVAZZI UA 18 CLS user manual

Levenhuk
Levenhuk Wezzer BASE L30 user manual

SIGLENT
SIGLENT SHA850A quick guide

YOKOGAWA
YOKOGAWA EXAxt ZR22G technical information

Thermo Electron
Thermo Electron Nicolet 4700 user guide