Forza FDC-BT10KMR-20B User manual

Installation of external battery banks
FDC-BT10KMR-20B
User Manual
2-
year
warranty

1. Important safety instructions
You must first read and closely follow all installation and operation instructions contained in this manual. Keep these instructions in a
safe place for future reference.
• The battery bank which is supplied with a factory input plug can be safely connected to the wall receptacle by the user.
• This battery bank is connected to a UPS. Voltage is still present at the output terminals when the UPS is turned on, even if the unit
has been disconnected from the AC mains.
• Make sure that the AC outlet is correctly grounded.
• Servicing of batteries should be performed or supervised by trained personnel with knowledge of batteries and the required
precautions. Failure to do so will void the warranty.
• Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system.
• To eliminate any overheating of the battery bank, keep all ventilation openings free from obstruction and do not place any foreign
objects on top of the battery bank. Keep the battery bank 20m away from the wall.
• Make sure the battery bank is installed in a controlled environment as specified.
• Do not install the battery bank under direct sunlight. Your warranty will be void if the batteries fail due to overheating.
• This battery bank is designed for indoor use only.
• This battery bank is not designed for use in dusty, corrosive and salty environment.
• The warranty will be void if water or other liquid is spilt or poured directly onto the battery bank. Similarly we do not warrant any
damage to the battery bank if foreign objects are deliberately or accidentally inserted into the battery bank enclosure.
• The battery will discharge naturally if the system remains unused for a period of time.
• It should be recharged every 2-3 months if unused. If this is not done, then the warranty will be null and void. During normal
operation, the batteries will remain in the automatic charging mode.
• When replacing the batteries, make sure to use units of the same type, capacity and quantity as specified.
• CAUTION – Do not dispose of battery or batteries in an open fire. The battery may explode.
• CAUTION – Never try to open or mutilate a battery. Released electrolyte is toxic, and harmful to the skin and eyes.
• CAUTION – Risk of electric shock – Battery circuit is not isolated from AC, hazardous voltage may exist between battery terminals
and ground. Test before touching with bare hands.
• CAUTION – A battery can present the risk of electric shock and high short-circuit current. The following precautions should be
observed when working with batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery terminals.
• Do not plug or unplug the battery connector if UPS works in DC (discharging) mode.
2. Preliminary steps
2.1. Unpacking and inspection
Note: Carefully inspect the unit before installation. Make sure that nothing inside the package is damaged or loose. Please keep the
original package in a safe place for future use.
Upon opening the box, make sure the following items are included:
• Battery bank module (1)
• Installation manual (1)
• UPS to battery connection cable (1)
• Rack mounting bracket (2)
• Screws (8)
• Tower support base (2)
Note: The battery bank module is very heavy, be cautious when unpacking and lifting the unit to avoid injury.
2.2. Product overview
Rear panel view
1. DC connector: connects to either UPS or the 2nd battery pack
2. DC breaker:
- DC overcurrent protection breaker
-Easy swap battery: when switching batteries, put the breaker in its “O” position. In case there is a 2nd (or next) battery bank
connected to the first battery bank, the DC voltage from the UPS Bat.+/- will flow through without any interruption to the 2nd
battery bank.
3. Ground
20-pc battery pack
3

2.3. Connection to a UPS
Choose a location
Select a suitable location to install the unit, in order to minimize the possibility of damaging the battery bank and to extend the life of
the batteries. To do so, please follow the instructions included below:
1. Keep at least 20cm (8 inches) clearance from the rear panel of the unit from the wall or other obstructions.
2. Do not block the air-flow to the ventilation openings of the unit.
3. Please ensure the installation site environmental conditions are in accordance with the module operating specifications so as to
prevent overheating and excessive moisture.
4. Do not place the unit in a dusty or corrosive environment or near any flammable objects.
5. This unit is not intended for outdoor use.
Mounting options
This unit can be either placed on a desktop, mounted in a rack or installed in an upright position.
3. Required battery type
This battery bank is designed to work with the following types of batteries:
240V/ 9Ah version: Twenty 12V 9Ah batteries
4. Storage and maintenance
There are no user-serviceable parts inside the enclosure. If the battery service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.
Storage
Charge the UPS for at least 4 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During storage,
recharge the battery in accordance with the following table:
Batteries must not be discarded as regular household waste! As part of the company’s
eco-friendly approach, we encourage you to follow all applicable local waste regulations
to dispose of your used devices and batteries properly.
-25°C - 40°C
-40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours
Storage temperature Recharge frequency Charge time
Rack installation
Tower installation
Connecting the UPS to an external battery bank
Follow the installation chart below to connect the UPS to an external battery bank using the supplied cable.
First battery pack
Second battery pack
UPS

5. Technical specifications
NOTES
Forza Power Technologies®is a registered trademark. Other company and product names mentioned herein are trademarks of their respective
owners. Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a recommendation.
Forza Power Technologies®assumes no responsibility with regards to the performance or use of these products. Made in China.
MPN FDC-BT10KMR-20B
Input / output
Input voltage
Output voltage
Capacity
Battery breaker
Battery
Type
Expected battery life
Expandable battery runtime
Battery voltage
Battery volt-amp-hour capacity
Battery quantity
UPS connection
Physical features
Form factor
Color
Construction material
Minimum required rack depth
Dimensions (HxWxD)
Rack units
Net weight
Environmental characteristics
Operating temperature
Operating relative humidity
Operating elevation
Storage temperature
Warranty
Standard warranty
240VDC
240VDC
9Ah
50A max
Maintenance-free sealed lead-acid battery
3 to 5 years
Includes a second input/output connector to daisy-chain multiple battery packs
12VDC
9Ah
20
Detachable cable with UPS specific DC connector (150cm length, 8 gauge)
Rack/Tower*
Black
Metal
628mm
5.3x17.6x24.7in
3U
64kg
32°F-104°F
0-90% non-condensing
<4000m
32°F-95°F
Two years
* Includes rack bracket (rail kit not included) and tower conversion base

www.forzaups.com
Table of contents
Other Forza Camera Accessories manuals
Popular Camera Accessories manuals by other brands

Trojan
Trojan GC2 48V quick start guide

Calumet
Calumet 7100 Series CK7114 operating instructions

Ropox
Ropox 4Single Series User manual and installation instructions

Cambo
Cambo Wide DS Digital Series Main operating instructions

Samsung
Samsung SHG-120 Specification sheet

Ryobi
Ryobi BPL-1820 Owner's operating manual