Gardner Denver RHP Series User manual

HIGH PRESSURE
REFRIGERATED
TYPE
COMPRESSED
AIR DRYERS
INSTRUCTION MANUAL
RHP Series
Models: RHP130, RHP200, RHP300,
RHP500, RHP750, RHP1000
3250997 Rev. D 07/16
For Sales and Service: (800) 883-2477
Or visit Sales and Service at www.gardnerdenverproducts.com

CONTENTS
GENERAL SAFETY INFORMATION....................................................................................... 1
RECEIVING, MOVING, AND UNPACKING............................................................................. 1
1.0 INSTALLATION ................................................................................................................. 2
1.1 Location ........................................................................................................................................... 2
1.2 Mounting ........................................................................................................................................... 3
1.3 Piping Connections .......................................................................................................................... 3
1.4 Electrical Connections....................................................................................................................... 3
1.5 Moisture Separator ........................................................................................................................... 3
2.0 OPERATION...................................................................................................................... 4
2.1 Minimum/Maximum Operating Conditions ........................................................................................ 4
2.2 Start-up.............................................................................................................................................. 4
2.3 Timer Drain........................................................................................................................................ 4
2.4 Timer Drain Programming Mode ....................................................................................................... 5
2.5 Operating Check Points ................................................................................................................... 5
3.0 MAINTENANCE ................................................................................................................ 6
3.1 Daily .................................................................................................................................................. 6
3.2 Weekly............................................................................................................................................... 6
3.3 Monthly.............................................................................................................................................. 6
3.4 Annually............................................................................................................................................. 6
4.0 TROUBLESHOOTING GUIDE.......................................................................................... 7
5.0 REFERENCE..................................................................................................................... 8
5.1 Sizing................................................................................................................................................. 8
5.2 Engineering Data............................................................................................................................... 9
6.0 DIMENSIONS / WEIGHTS ................................................................................................ 10
7.0 DRAWINGS ....................................................................................................................... 11
7.1 Process Gas / Refrigeration Flow Diagram: Models RHP130 and RHP200 .................................... 11
7.2 Process Gas / Refrigeration Flow Diagram: Models RHP300 through RHP1000............................ 12
7.3 Wiring Diagram: Models RHP130 and RHP200 (115 or 208-230V/60 Hz, 100 or 240V/50 Hz) ...... 13
7.4 Wiring Diagram: Models RHP300 through RHP750 (230-400-460V/3/50-60 Hz)............................ 14, 15
7.5 Wiring Diagram: Model RHP1000 (230-400-460V/3/50-60 Hz) ....................................................... 16, 17
7.6 Wiring Diagram: Models RHP300 through RHP1000 (575-460/3/60 Transformer Pack)................. 18
8.0 REPLACEMENT PARTS LIST.......................................................................................... 19
8.1 Replacement Parts............................................................................................................................ 19
8.2 Maintenance Kits............................................................................................................................... 19
WARRANTY

1
GENERAL SAFETY INFORMATION
1. PRESSURIZED DEVICES:
This equipment is a pressure containing
device.
• Donotexceedmaximumoperating
pressure as shown on equipment
serial number tag.
• Makesureequipmentisdepressurizedbeforeworking
on or disassembling it for service.
2. ELECTRICAL:
This equipment requires electricity to
operate.
• Installequipmentincompliancewithall
applicable electrical codes.
• Standardequipmentissuppliedwithelectrical
enclosures not intended for installation in hazardous
environments.
• Disconnectpowersupplytoequipmentwhenperforming
any electrical service work.
3. BREATHING AIR:
• Airtreatedbythisequipmentmaynot
be suitable for breathing without further
purication.
Refertoapplicablestandardsandspecicationsforthe
requirements for breathing quality air.
RECEIVING, MOVING, AND UNPACKING
A. RECEIVING
This shipment has been thoroughly checked, packed and
inspectedbeforeleavingourplant.Itwasreceivedin
good condition by the carrier and was so acknowledged.
CheckforVisibleLossorDamage.Ifthisshipmentshows
evidence of loss or damage at time of delivery to you, in-
sist that a notation of this loss or damage be made on the
delivery receipt by the carrier’s agent.
B. UNPACKING
Check for Concealed Loss or Damage. When a shipment
has been delivered to you in apparent good order, but
concealed damage is found upon unpacking, notify the
carrier immediately and insist on his agent inspecting the
shipment. Concealed damage claims are not our respon-
sibility as our terms are F.O.B. point of shipment.
C. MOVING
Inmovingortransportingdryer,donottipdryerontoits
side.
D. STORAGE/SHUT DOWN
Dryer should not be stored outside (either
packed or unpacked) or exposed to the weather. Damage to
electrical and control components may result.
IMPORTANT: WATER-COOLED UNITS-Iftheunitisshut
down in below freezing temperatures, the water-cooled con-
denser may freeze and cause permanent damage. Condenser
must be drained when the unit is shut down.
IMPORTANT: Do not store dryer in temperatures above 130°F
(54.4°C).

2
IMPORTANT:READPRIORTOSTARTINGTHISEQUIPMENT
1.0 INSTALLATION
1.1 Location
A. For typical placement in a compressed air system, see
drawing.
B. Air compressor intake – Locate air compressor so that
contaminants potentially harmful to the dryer (e.g. ammo-
nia) are not drawn into the air system.
C. Free Air Flow Clearances
Front: 36 inches (914 mm)
Back: 6 inches (152 mm)
Sides: 36 inches (914 mm)
Service - To facilitate maintenance leave 36 inches
(914 mm) of clearance in front of dryer.
D. Standard units are designed to operate in ambients:
Air-cooled: 40 to 110°F (4 to 43°C).
Water-cooled: 40 to 130°F (4 to 54°C).
E. Installationsinaltitudesabove4500feet(1370meters)
– Dryer is adjusted to operate in altitudes up to 4500 feet
(1370meters).Ifdryerisinstalledinanaltitudeabove
this, and has not been preset at the factory for this altitude,
contact manufacturer’s Service Department.
There shall be no external forces or vibrations
transmitted to the dryer inlet/outlet connections from the piping.
External piping must be properly supported. The installation of
aexibleconnectionorvibrationdampener,withintheair/gas
stream, prior to the dryer is recommended to further reduce the
possibility of damage from vibration or pulsations. Failure to do
so may void the warranty.
NOTE: Outdoor installation – Standard units are designed for
indoor installation. Contact manufacturer if installing outdoors.
Aftercooler
Separator
Dryer
Oil Removal
Filter
Compressor
Air Outlet
Air Inlet
Control Panel
Moisture Separator
Electric Timed Drain
w/3-Way Valve
(Standard)
Condenser
230-VAC Electrical Entry
120-VAC Electrical Cord
Drain Outlet
Drain Outlet
Models: RHP300 Through RHP750 Only
Drain Outlet for RHP1000
on rear panel.
Air Outlet
Air Inlet
Control Panel
Moisture Separator
Electric Timed Drain Assembly
w/3-Way Valve
Water Inlet Connection
Models: RHP300 Through RHP1000
(W/C Models Only)
Water Outlet Connection
Models: RHP300 Through RHP1000
(W/C Models Only)
Condenser
Primary Electrical Entry
Secondary Electrical Entry
Models
RHP130 and RHP200
Models
RHP300, RHP500, RHP750, and RHP1000

3
1.2 Mounting
Mount the dryer on a level solid surface. Holes are provided in
thedryerbasetopermanentlymountthedryertotheoor.
1.3 Piping Connections
A. AirInlet-Connectcompressedairlinefromairsource
to air inlet. (Reference markings on dryer or see call out
drawing on page 10 for air inlet/outlet connection loca-
tions.)
NOTE:Useback-upwrenchwhenmakingpipingconnec-
tions.
There shall be no external forces or vibrations
transmitted to the dryer inlet/outlet connections from the piping.
External piping must be properly supported. The installation of
aexibleconnectionorvibrationdampener,withintheair/gas
stream, prior to the dryer is recommended to further reduce the
possibility of damage from vibration or pulsations. Failure to do
so may void the warranty.
RefertoSerialNumberTagformaximum
working pressure. Do not exceed dryer’s Maximum Working
Pressure.
NOTE:Installdryerinairsystemathighestpressurepossible
(e.g. before pressure reducing valves).
NOTE: Installdryeratcoolestcompressedairtemperature
possible. Maximum inlet compressed air temperature: 120°F
(49°C).Ifinletairexceedsthistemperature,precooltheair
with an aftercooler.
B. Air Outlet – Connect air outlet to downstream air lines.
NOTE:Useback-upwrenchwhenmakingpipingconnec-
tions.
There shall be no external forces or vibrations
transmitted to the dryer inlet/outlet connections from the piping.
External piping must be properly supported. The installation of
aexibleconnectionorvibrationdampener,withintheair/gas
stream, prior to the dryer is recommended to further reduce the
possibility of damage from vibration or pulsations. Failure to do
so may void the warranty.
C. Bypasspiping–Ifservicingthedryerwithoutinterrupting
the air supply is desired, piping should include inlet and
outlet valves and an air bypass valve.
D. Water cooled models – cooling water inlet and outlet
1. Connect cooling water supply to cooling water inlet.
2. Connect cooling water return line to cooling water
outlet connection.
NOTE: Strainer and water regulating valve are supplied on
water cooled models.
1.4 Electrical Connections
IMPORTANT:Usecoppersupplywiresonly.
A. Dryer is designed to operate on the volt-
age, phase, and frequency listed on the
serial number tag.
B. Ifdryerissuppliedwithacordandplug,
install in a receptacle of proper voltage.
C. Electrical entry on larger dryers is through a hole in the
cabinet.Itislocatedontherightsidepanelwhenfacing
the front of the unit. Connect power source to terminal
strip in electrical enclosure as shown on the wiring dia-
gram included with the dryer.
NOTE: Refrigeration condensing unit is designed to run con-
tinuously and should NOT be wired to cycle on/off with the air
compressor.
1.5 Moisture Separator
A. Separator has an external drain which auto-
matically discharges collected condensate.
NOTE:Itmaybedesirabletopipethecon-
densate from the Automatic Drain outlet to a
suitable drain.
B. For manual draining, convenient dryer depressurization,
and drain valve maintenance, a three-way valve assembly
is installed between the drain port on the moisture separa-
tor and the drain valve. On all models, the three-way
valve is mounted to the bottom of the separator vessel
using a pipe union. Review the following for proper drain
function:
• AutomaticDraining-Valvehandleshouldbepositioned
parallel to the valve body (as shown), with the arrow
onthehandlepointingtowardthedrainvalve.Inthis
position,condensatewillowfromthebowltothedrain
valve.
• DrainIsolation(Shutdown)-Valvehandleshallbe
turnedperpendiculartothevalvebody(rotate90°).In
thisposition,condensateowisshutoff.
Pipe Union 3-Way Valve
Manual Discharge Line
Solenoid Valve
Automatic Discharge Line
• ManualDraining-Drainvalvehandleshallberotated
slightly past the drain isolation position to allow
throttling through the valve for manual discharge and
depressurization.
• NOTE: The pipe union allows removal of the
entire drain assembly. However, the unit must be
depressurized prior to disassembly or serious injury
may occur.
NOTE: Discharge is at system pressure. Drain line should be
anchored.
NOTE: Condensate may contain oil. Comply with applicable
laws concerning proper disposal.

4
Ifwaterispresentdownstreamofthedryer,
always verify that any condensate drains installed upstream of
the dryer are draining properly before attempting to readjust
the LED setting.
1. For minimum inlet air pressures that fall between column
values, the setting for the lower pressure is recommended.
(i.e. select the 300 psi column values for 324 psi inlet pres-
sure listed in Table 1.)
2. Where the dryer is consistently operating at less than max-
imum capacity, it may be possible to increase the LED set
point to minimize air loss. Discretionary adjustments to the
dryer should only be made on a hot, humid day when the
maximumexpectedairloadisowingthroughthedryer.
Failure to do so may prevent the condensate from draining
completely when operating under peak load conditions.
Table 1 Timed Drain Illuminated LED Settings
Inlet Pressure (psi)
300 400* 500 600 725
Dryer Model
RHP130 3 4 4 4 5
RHP200 3 3 4 4 4
RHP300 3 4 4 4 5
RHP500 3 3 3 4 4
RHP750 2 2 3 3 3
RHP1000 1 2 2 3 3
* Recommended and pre-programmed factory settings for each model dryer.
Assumes inlet conditions with 120°F ambient and 10°F air-cooled aftercooler
approach temperature.
Table 2 Timed Drain Illuminated LED Settings
LED
Illuminated
Minutes
between
Drain Cycles
1st 1
2nd 3
3rd 5
4th 10
5th 20
6th 30
7th 40
8th 50
9th 60
2.0 OPERATION
2.1 Minimum/Maximum Operating Conditions
A. Maximum inlet air pressure: 725 psig (50 barg)
B. Minimum inlet air pressure: 15 psig (1.0 barg)
C. Maximum inlet air temperature: 120°F (49°C)
D. Maximum ambient temperature:
Air-cooled models: 110°F (43°C)
Water-cooled models: 130°F (54°C)
E. Minimum ambient temperature: 40°F (4°C)
Condensate
Draining
Drain
Push-to-Test
On/Off
Switch
Switch Legend
Power On
Light
Compressor
On Light
Dew Point
Temperature
Indicator
2.2 Start-up
IMPORTANT: Energize dryer disconnect switch (provided by
others,seeNEC)24hoursbeforerefrigerationcompressor
isstarted!Neverusethedisconnectswitchtoshut-downthe
dryer for a extended period of time (except for repair). Failure
to follow these instructions may result in a non-warrantable
compressor failure.
NOTE:Itisrecommendedthatdryerbestarted15minutes
beforecompressedairowbegins.
NOTE:Ifthereisnopowertothecontrolboardforaperiod
of two weeks or more, it may return to the default mode.
1. ConrmOn/OffSwitchisinthe“Off”position.
2. Check for proper electrical voltage.
3. Energizedryerdisconnectswitch(seeIMPORTANTnote
above)
4. For water-cooled models: after 24 hours, begin cooling
waterow.
5. ToggleON/OFFswitchtotheONpositiontoenergize
dryer. Green power-on light will illuminate.
6. Slowly pressurize unit air side by opening inlet isolation
valve. Check for leaks.
7. After 15 minutes, open outlet isolation valve slowly.
8. Close air by-pass valve.
2.3 Timer Drain
NOTE: The Timer Drain LED level has been pre-programmed
atthefactoryforyourspecicdryermodel.Programmingis
based upon a minimum of 400 psig saturated inlet air pressure
andmaximumenergyefciency.Thedrainopentimeisxed
at one second and a small amount of air will be exhausted with
each cycle. Generally, no adjustment to the timer is required.

5
2.4 Timer Drain Programming Mode
1. Pressthe“DrainIntervalProgram”button.The“Conden-
sateDraining”LEDwillstarttoash,andtheilluminated
LEDonthe“DewPointTemperatureIndicator”willidentify
thefactorysettingfor“MinutesBetweenDrainCycles.”
(See Table 1)
2. Pressandreleasethe“DrainIntervalSelector”buttonto
sequencethe“MinutesBetweenDrainCycleLED’s”from
lefttorightuntilreachingyourselection.The“Red”LEDis
notused(ReferenceTable2for“DrainCycleIntervals”)
3. Toinitiatethenewsetting,pressthe“DrainIntervalPro-
gram”button(thiswillstorethenewsettingandexitthe
program).
4. Exiting the Program will cause the Timer Drain to dis-
charge and begin a new cycle.
NOTE: Failure to perform step 3 within 25 seconds of com-
pleting step 2 will cause the unit to revert back to the previous
setting.
NOTE:Intheeventofabrieforextendedperiodofpower
loss, the unit will retain the existing program setting and will
begin a new cycle once power is reapplied. Had drain been
ready to drain before the loss of power, the drain bowl’s capac-
itywouldpreventdownstreamooding.Condensatewilldrain
completely within a couple of cycles. (Manually pressing the
“Push-to-Test”buttonwoulddrainbowlimmediately)
2.5 Operating Check Points
Check the following on a periodic basis:
A. Green power on light is illuminated.
B. Dew point indicator is in green area.
C. Condensate is discharging from drain.
Condensate Draining
(Flashes in
programming mode)
DrainInterval
Program
Dew Point
Temperature
Indicator
DrainInterval
Selector
(LED illuminated
indicates drain
cycle setting)

6
3.0 MAINTENANCE
3.1 Daily
A. Check separator daily to be sure automatic drain is dis-
charging.
3.2 Weekly
A. Blow down separator weekly by pushing test button on
control panel.
3.3 Monthly
A. Condenser Coil
1. Air-cooled - clean off accumulated dust and dirt
monthly or as necessary in dirty environments.
2. Water-cooled - clean strainer monthly, more often if
required. Shut off water, remove small plug to relieve
pressure, then remove large plug to remove strainer.
Clean strainer and replace.
3.4 Annually
NOTE: Prepackaged maintenance kits are available that
includeallnecessarylterandtimeddrainvalvecomponents.
MaintainmaximumperformanceandefciencywithGenuine
Parts. See page 19 for ordering information.
A. Rebuild drain mechanism annually.
B. Moisture Separator/Oil Removal Filter
1) Replacelterelementannually,orwhenpressuredrop
across dryer is excessive.
Whenremovingliquidsatratedowconditions,an
increase in pressure drop will occur as the separator/
lterelementsbecomeloadedwithsolidparticles.
2) Procedure for Separator / Filter Element Replacement
THISFILTERISAPRESSURE
CONTAININGDEVICE.DEPRESSURIZEBEFORE
SERVICING.
a) Isolatedryer(closeinletandoutletvalvesifin-
stalled) or shut off air supply.
b) Removefrontpanelanddepressurizelterby
slowly opening manual drain by-pass valve.
c) Disconnect drain line from bottom of separator.
d) Disassemblelterhousing.
1) Forallmodels-removethelterbowl,
unscrewingitfromthelterheadbyhandor
strap wrench.
e) Cleanlterbowl.
D
D
Separator Bowl Insulation
Drain Assembly
Pipe Union
Separator Element
Replacement Sleeve
Separator Element Nut
Separator Element Bottom Cap
Air Inlet Air Outlet
Separator Bowl O-Ring
Separator Element O-Rings
Separator Head
Separator Bowl
f) Remove and replace complete element.
1) Unscrewtheoldlterelementanddiscard.
Also,discardthesmallO-ringthatsealsthelter
tothelterassemblyhead.
g) InstallnewlterelementandbowlwithnewO-rings
properly seated to head or bowl (dependent upon
dryer size).
h) Connect drain line and replace panel.
i) Repressurize dryer and resume operation.

7
4.0 TROUBLESHOOTING GUIDE
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
A) Water downstream of dryer 1. Residual free moisture remaining in
downstream pipelines
2. Air bypass system is open
3. InletandOutletconnectionsarereversed
4. Air lines downstream of dryer are exposed
to temperatures below the dew point.
5. Excessive free moisture (bulk liquid) at
dryer inlet.
6. Condensate not being drained
Drain mechanism is clogged or
inoperative.
Drain line is restricted or frozen.
Electric drains-timer not set to allow for
sufcientcondensateremoval.
7. Dryer overloaded resulting in elevated dew
point.
8. Refrigeration system not functioning
Blow out system with dry air
Check valve positions
Check for correct connection
Insulateorheattraceairlinesexposedtolow
ambients or dry air to lower dew point
Installseparatoraheadofdryer
Replace drain mechanism if inoperative.
Open drain line.
Electric drains-reset time so that all liquid is
discharged
Checkinletairtemperatureandpressure,ow
rate (compressor capacity) and ambient air or
water temperature.
See D below
B) High pressure drop across dryer 1. Excessiveairow
2. Freezing of moisture in evaporator
because of refrigeration system fault
3. Separatorlterelementclogged
Checkowrate
See D below
Replacelterelement
C) Dew point indicator in red area 1. Dryer overloaded resulting in high air
outlet temperature
2. Refrigeration system not functioning
properly resulting in high air outlet
temperature
See A 7
See D below
D) Refrigeration system not functioning
properly
1. Power on light off
2. Compressor on light off
3. Refrigeration compressor cycles on
and off
a. Power failure
b. Line disconnect switch open
c. Blown fuses, open breaker
d. Faulty wiring, loose terminals
a. ON/OFFswitchis“OFF”
b. Line disconnect switch open
c. Blown fuses, open breaker
d. Faulty wiring, loose terminals
a. High or low ambient conditions
b. Air-cooled-Dirty,cloggedcondenserns,
obstructedowacrosscondenser,faulty
fan motor or fan control switch.
Check for power to unit
Close disconnect switch
Check for continuity
Have electrician check electrical connections.
Turnswitch“ON”
Close disconnect switch
Check for continuity
Have electrician check electrical connections
Check min./max. temperature ranges
Cleancondenserandcheckforfreeairow,if
problempersistscontactqualiedrefrigeration
repairman or manufacturer’s service
department.

8
5.0 REFERENCE
5.1 Sizing
Determining dryer capacity at actual operating conditions
Todeterminethemaximuminletowcapacityofadryeratvari-
ous operating conditions, multiply the rated capacity from Table
1 by the multipliers shown in Table 2.
Example: How many scfm can an air-cooled model RHP300
handle when compressed air to be dried is at 350 psig and
90°F; ambient air temperature is 80°F?
Answer: 300 x 1.19 x 1.12 = 400 scfm.
Table 1. Rated Capacity
Rated capacity (scfm) @ 725 psig inlet pressure, 100°F inlet
temperature, and 100°F ambient temperature and 60 Hertz
operation.
MODEL
RATED FLOW
(scfm) m3/hr
RHP130
RHP200
RHP300
RHP500
RHP750
RHP1000
130
200
300
500
750
1000
221
340
510
850
1275
1700
Table 2. Capacity Adjustment Factors for Air Inlet
Temperature and Pressure
INLET PRESSURES INLET TEMPERATURES
(psig) (barg) 80°F
27°C
90°F
32°C
100°F
38°C
110°F
43°C
120°F
49°C
300 to 725 21 to 50 1.49 1.19 1.00 0.83 0.72
Table 3. Capacity Adjustment Factors for Ambient Air
Temperature
AMBIENT
TEMPERATURE
°F (°C)
CAPACITY
ADJUSTMENT
FACTOR
80°F (27°C) 1.12
90°F (32°C) 1.06
100°F (38°C) 1.00
110°F (43°C) 0.94
Water-cooled
(85°F, 29.4°C
cooling water)
1.15
Table 4. Capacity Adjustment Factors for Electrical
Frequency
50 Hertz 60 Hertz
0.83 1.00

9
5.2 Engineering Data
Models RHP130 RHP200 RHP300 RHP500 RHP750 RHP1000
Air System Data
Maximum / Minimum Inlet Air Pressure (compressed air at inlet to dryer) 725 psig (50 barg) / 15 psig (1.0 barg)
Maximum / Minimum Inlet Air Temperature (compressed air at inlet to dryer) 120°F (49°C) / 40°F (4°C)
Maximum / Minimum Ambient Temperature Air-cooled: 110°F (43°C) / 40°F (4°C), Water-cooled: 130°F (54°C) / 40°F (4°C)
Outlet Air Temperature (nominal at rated conditions) 85°F (29.4°C)
Refrigeration System Data
Refrigeration Capacity @ 35°F Evaporator & 100°F Ambient (BTU/hr) 60 Hz 4820 6030 8900 15200 22000 30500
50 Hz 4020 5690 7420 12700 18300 25400
Refrigerant Type R-134A
Refrigerant Charge See Data Tag on Dryer
Suction Pressure Setting - Hot Gas Bypass Valve (psig) 30.5 psig (2.1 barg)
Compressor Control Ranges (out-in)
(both air-cooled and water-cooled models) High N/A 281 - 190 psig (19.4 - 13.1 barg)
Low N/A 22 - 34 psig (1.5 - 2.3 barg)
Air-Cooled Condensers
Air Flow Across Condenser (cfm) (air-cooled models) 60 Hz 300 450 710 1070 1680 2170
50 Hz 250 370 590 890 1400 1810
Condenser Fan Switch Setting (in-out) Fan 1 110 - 70 psig (7.6 - 4.8 barg) 113 - 78 psig (7.8 - 5.4 barg)
Fan 2 N/A 183 - 124 psig (12.6 - 8.6 barg)
Water-Cooled Condensers
Water Regulating Valve Setting 135 psig (9.3 barg)
Required Available Water Pressure Differential 40 psig (2.8 barg) - minimum
Flow Required with 85°F Cooling Water (gallons per minute) 60 Hz N/A 1.3 2.1 3.0 3.6
50 Hz N/A 1.2 2.0 2.8 3.3
Electrical Data
Nominal Voltage 115/1/60 208-230/3/60
Min. - Max. Voltage 104 - 127 187 - 253
Input Power @ Rated Flow (watts) 932 1280 1255 1962 2910 4120
Rated Load Amps** 10.2 13.0 7.5 10.4 13.9 22.1
Locked Rotor Amps** 51.0 70.0 51.0 66.0 88.0 115.0
Minimum Circuit Ampacity 13.6 18.0 10.5 15.9 19.7 30.4
Branch Circuit Fuse Size (amps) 20 25 15 20 30 45
Resistance (ohms) 4.3 S / 0.7 R 3.2 S / 0.4 R 1.8 1.3 1.0 0.7
Nominal Voltage 208-230/1/60 460/3/60
Min. - Max. Voltage 187 - 253 414 - 506
Input Power @ Rated Flow (watts) 932 1280 1255 1962 2910 4120
Rated Load Amps** 5.4 6.5 3.6 4.7 7.1 9.6
Locked Rotor Amps** 30.0 35.0 25.0 33.0 44.0 63.0
Minimum Circuit Ampacity 7.3 9.1 5.2 7.5 10.4 15.2
Branch Circuit Fuse Size (amps) 15 15 15 15 15 20
Resistance (ohms) Main/Start 9.0 S / 2.3 R 7.9 S / 1.6 R 7.4 5.0 4.0 2.7
Nominal Voltage 240/1/50 575/3/60
Min. - Max. Voltage 216 - 264 518 - 633
Input Power @ Rated Flow (watts) 680 1019 1255 1962 2910 4120
Rated Load Amps** 4.5 5.0 3.6 4.7 7.1 9.6
Locked Rotor Amps** 21.0 30.0 25.0 33.0 44.0 63.0
Minimum Circuit Ampacity 6.2 7.3 4.2 6.0 8.3 12.2
Branch Circuit Fuse Size (amps) 15 15 15 15 15 20
Resistance (ohms) 19.5 S / 3.3 R 10.5 S / 1.8 R 7.4 5.0 4.0 2.7
Nominal Voltage N/A 380-420/3/50
Min. - Max. Voltage N/A 342 - 462
Input Power @ Rated Flow (watts) N/A 1002 1613 2040 2860
Rated Load Amps** N/A 3.6 4.7 7.1 9.6
Locked Rotor Amps** N/A 25.0 33.0 44.0 63.0
Minimum Circuit Ampacity N/A 5.2 7.5 10.4 15.2
Branch Circuit Fuse Size (amps) N/A 15 15 15 20
Resistance (ohms) N/A 7.4 5.0 4.0 2.7
* For 60 Hz, 35°F Evaporator, 100°F Ambient; for 50Hz, 35°F Evaporator, 77°F Ambient
** Compressor Only

10
6.0 DIMENSIONS / WEIGHTS
FRONT VIEW
BOTTOM VIEW
RIGHT SIDE VIEW
BACK VIEW
DETAIL A
DETAIL B
A
B
"B"
"A"
"D"
"E"
"F"
"G"
"H"
"I" "J"
"C"
Ø"K" MOUNTING HOLE
4-PLACES TYP.
"L" - I/O CONNECTIONS
2.500
CONDENSER AIR FLOW
ELECTRICAL ENTRY
MODELS RHP130 through RHP200 (230 VOLT)
0.25-NPT DRAIN CONNECTION
MODELS RHP130 through RHP200
ELECTRICAL ENTRY
MODELS RHP300 through RHP1000
0.25-NPT DRAIN CONNECTION
MODELS RHP300 through RHP750
1/4-18 NPT DRAIN CONNECTION
Model RHP1000 ONLY "N"
"M"
"O" 1/2-14 FPT I/O WATER CONNECTIONS
MODELS RHP300 through RHP1000 ONLY
6-FT (1.8 Meters) POWER CORD
MODELS RHP130 through RHP200 (115 VOLT):
INLET OUTLET
Dimensions, inches (mm)
Model RHP130 RHP200 RHP300 RHP500 RHP750 RHP1000
A 37.56 (954) 37.56 (954) 38.60 (980) 38.60 (980) 58.06 (1475) 58.06 (1475)
B 25.62 (651) 25.62 (651) 32.15 (817) 32.15 (817) 32.15 (817) 32.15 (817)
C 2.50 (63.5) 2.50 (63.5) 2.50 (63.5) 2.50 (63.5) 2.50 (63.5) 2.50 (63.5)
D 23.62 (600) 23.62 (600) 30.15 (766) 30.15 (766) 30.15 (766) 30.15 (766)
E 17.62 (448) 17.62 (448) 30.15 (766) 30.15 (766) 39.62 (1006) 39.62 (1006)
F 19.62 (498) 19.62 (498) 32.15 (817) 32.15 (817) 41.62 (1057) 41.62 (1057)
G 9.58 (243) 9.58 (243) 7.64 (194) 7.64 (194) 20.44 (519) 20.44 (519)
H 14.96 (380) 14.96 (380) 15.80 (401) 15.80 (401) 27.79 (706) 27.79 (706)
I 28.54 (725) 28.54 (725) 30.19 (767) 30.19 (767) 49.06 (1246) 49.06 (1246)
J 25.02 (636) 25.02 (636) 26.04 (661) 26.04 (661) 44.78 (1137) 44.78 (1137)
K 0.31 (7.9) 0.31 (7.9) 0.31 (7.9) 0.31 (7.9) 0.63 (16) 0.63 (16)
L 1.5 MPT 1.5 MPT 1.5 MPT 1.5 MPT 1.5 MPT 1.5 MPT
M N/A N/A 4.56 (116) 4.56 (116) 4.81 (122) 4.81 (122)
N N/A N/A 9.84 (250) 9.84 (250) 20.82 (529) 20.82 (529)
O N/A N/A 3.13 (80) 3.13 (80) 3.13 (80) 3.13 (80)
Weight, lbs (kg) 251 (114) 279 (127) 425 (193) 463 (210) 691 (313) 734 (333)
NOTE: DimensionsandWeightsareforreferenceonly.Requestcertieddrawingsforconstructionpurposes.

11
PROCESS GAS
SYSTEM
HIGH
PRESSURE
SIDE
CRANKCASE
HEATER
(MODEL 200 ONLY )
COMPRESSOR
CAPILLARY TUBE
~
~
SUCTION PRESSURE
GAUGE (OPTIONAL)
LOW
PRESSURE
SIDE
REFRIGERATION
SYSTEM
AIR COOLED CONDENSER
FAN SWITCH
ACCESS
FITTING
PRESSURE
RELIEF
VALVE
PRE-COOLER
REHEATER
CONDENSATE
DRAIN
AUTOMATIC
ELECTRIC DRAIN
SERVICE VALVE/
MANUAL DRAIN
AIR-AIR
HEAT EXCHANGER
HIGH TEMPERATURE
SWITCH (OPTIONAL)
EVAPORATOR
CARTRIDGE
TYPE
MOISTURE
SEPARATOR
AIR
INLET
IN
TEMP
(OPTIONAL)
AIR
OUTLET
OUT
PRESSURE
(OPTIONAL)
DISCHARGE
PRESSURE
GAUGE
(OPTIONAL)
HEAT EXCHANGER SET
HOT GAS
BY-PASS
VALVE
FILTER / DRYER
7.0 DRAWINGS
7.1 Process Gas / Refrigeration Flow Diagram: Models RHP130 and RHP200

12
PROCESS GAS
SYSTEM
VALVE
HIGH
PRESSURE
SIDE
CRANKCASE
HEATER
COMPRESSOR
ACCUMULATOR
~
~
PRESSURE
SWITCH
SWITCH
LOW PRESSURE
GAUGE
SUCTION PRESSURE
LOW
PRESSURE
SIDE
ACCESS
FITTING
REFRIGERATION
SYSTEM
AIR COOLED CONDENSER
WATER
STRAINER
REGULATING VALVE
COOLING WATER
COOLING
WATER (IN)
COOLING
CONDENSER
WATER COOLED
WATER (OUT)
COOLING
(OPTIONAL)
(AIR COOLED UNITS ONLY)
MODELS 750 TO 1000
FAN SWITCH
(AIR COOLED
UNITS ONLY)
FAN SWITCH
FILTER / DRYER
ACCESS
FITTING FITTING
ACCESS
PRESSURE
VALVE
RELIEF
HEAT EXCHANGER
REHEATER
PRE-COOLER
AIR-AIR
SWITCH
(STANDARD)
CONDENSER DETAIL
OPTIONAL WATER COOLED
TYPE
CARTRIDGE
SEPARATOR
MOISTURE
(OPTIONAL)
GAUGE
(OPTIONAL)
HEAT EXCHANGER
INLET
REHEATER
PRE-COOLER
AIR
AIR-AIR
EVAPORATOR
IN
TEMP
(OPTIONAL)
OUTLET
AIR
PRESSURE
OUT
(OPTIONAL)
PRESSURE
DISCHARGE
HIGH
CAPILLARY TUBE
HEAT EXCHANGER SET #2
HEAT EXCHANGER SET #1
BY-PASS
HOT GAS
(USED ONLY ON MODEL 1000)
(USED ON MODELS 300-1000)
CONDENSATE
DRAIN
AUTOMATIC
ELECTRIC
SERVICE VALVE/
MANUAL DRAIN
DRAIN
EVAPORATOR
HIGH TEMPERATURE
(OPTIONAL)
7.2 Process Gas / Refrigeration Flow Diagram: Models RHP300 through RHP1000

13
7.3 Wiring Diagram: Models RHP130 and RHP200 (115 or 208-230V/60 Hz, 100 or 240V/50 Hz)
RC - RUN CAPACITOR
SC - START CAPACITOR
SR - START RELAY
120 VAC
POWER CORD SUPPLIED
21
20
19
18
17
16
15
14
13
12
11
10
09
08
07
05
06
04
03
02 L1
00
01
COMPRESSOR HARNESS
JUMPER J5-1 TO J5-3 AND J5-5 TO J5-7 FOR 120 VAC
1
NOTES:
T1
N
3RH1921-1CA01 NC AUX
3RH1921-1CA10 NO AUX
SIEMENS 1026-1AC20
L1
L1
T2
L1
N
L1 CONT 1
T1
T2
TO GROUND STUD PE
T1
T2
TO GROUND STUD PE
FAN 1 HARNESS
C
1
FAN 1
MTR2
FPS 1
COMPRESSOR
MTR1
DRAIN NEUTRAL
COMPRESSOR ON
L1
L1
N
L1
11
N
L1
1L1
N
1
N
GROUND STUD
6
7
J5
3
5
4
1
2
N
N
COMPRESSOR
CONTACTOR N
TO GROUND STUD PE
N
1L1
HEATER HARNESS
DRAIN LINE 3
THERMISTER
L1
THERMISTER
NEUTRAL
TC1
TO GROUND STUD PE
3
L1
BLUE
BROWN
GRN/YELLOW
DRAIN HARNESS
CONTROL BOARD
N PE
L1
LINE
HEATER 1
H1
TEST ALM
2
1
3DRAIN
120VAC
230 VAC
CUSTOMER SUPPLIED
*NOTE: HEATER IS USED
ON .75 MODELS ONLY.
1
L3 T3
T1L1
L2 T2
A1
O I
-2NC-1NC CONT 1
CONT 1
A2
H2
SR
C
R
S
RC
SC 1 2 5

14
7.4 Wiring Diagram: Models RHP300 through RHP750 (230-400-460V/3/50-60 Hz)
(Page 1 of 2)
H4
H3
H2
H1
FU2
FU3
B100-3683-5
MICRON
L1L3
H5
208V
230V H5
400V H5
460V H5
FACTORY SET TO 460V
FU1
24/120 VAC SECONDARY
100VA
208/230/400/460 VAC PRIMARY
H5
COM
H3
230V
H4
208V
H2
400V
X3
X2
X1
H1
120V 24V
460V
COMPRESSOR
Model 750
(air-cooled models only)
TO LINE 22
21
20
18
19
17
16
15
14
13
L1 L3
L2
PE
HEATER HARNESS
1L2
L3
TB2
TB2
PE
T3
T2
H1
HEATER 1
FAN 2 HARNESS
FPS 2
FAN 2
REF SHEET 02 LINE 18
REF SHEET 01 LINE 19
03
10
11
12
09
08
07
06
05
04
L3
L3
L3
L2
L2
02
01
00
PETB1 L1 L2 L3
L1
L1
L1 L2 L3
CONT 1
PE
TB2
T1
T2
T3
T3
T2
T3
TB2
PE
T2
T3
T2
FAN 1 HARNESS
FPS 1
FAN 1
T1
T1
T1
COMPRESSOR HARNESS
TO SHEET 02
43
42
X
40
41
39
38
37
36
35
TO SHEET 02
N
25
(4 Terminal Blocks)
TB2
32
33
34
X
31
30
X
29
28
27
26
FROM LINE 21
L3
24
23 L1
22
L3
L1
(4 Terminal Blocks)
NTB2
N
L3
L1
ELECTRICAL SUPPLY
480VAC/3PH/60HZ/GND
CONT 1
-1NC -2NC H2
MTR3
L3
L2
T3
T2
L1 T1
MTR2
MTR1

15
Wiring Diagram: Models RHP300 through RHP750 (230-400-460V/3/50-60 Hz)
(Page 2 of 2)
CONT 1
21
20
19
18
17
14
16
15
13
12
X
X
TB2
X
TB2
X
X5COMPRESSOR
XX
TB2
07
11
10
09
08
06
05
04
03 XX
02
01
00
FROM SHEET 01
XX
X
X
THERMISTER
CONTROL BOARD
DRAIN NEUTRAL
DRAIN LINE
THERMISTER
NEUTRAL
3
N
N
HPS
1
LINE
1
1
1
TB2
GRN/YELLOW
DRAIN HARNESS
DRAIN HARNESS
PE
TB2
3
TB2
PE
X
3
BROWN
BLUE
TEST ALM
2
1
324VAC
N
LPS
HPS/LPS SENSOR HARNESS
2 2
TB2
2
4
COMPRESSOR
CONTACTOR
4 N
TB2
NN
TB2
FROM SHEET 01
N
N
-4NO -3NO
O I A1
CONT 1
A2

16
7.5 Wiring Diagram: Model RHP1000 (230-400-460V/3/50-60 Hz)
(Page 1 of 2)
H4
H3
H2
H1
FU2
FU3
B100-3683-5
MICRON
L1L3
H5208V
230V H5
400V H5
460V H5
FACTORY SET TO 460V
FU1
24/120 VAC SECONDARY
100VA
208/230/400/460 VAC PRIMARY
H5
COM
H3
230V
H4
208V
H2
400V
X3
X2
X1
H1
120V 24V
460V
COMPRESSOR
TO LINE 22
21
20
18
19
17
16
15
14
13
L1 L3
L2
PE
HEATER HARNESS
1L2
L3
TB2
TB2
PE
T3
T2
H1
HEATER 1
FAN 2 HARNESS
FPS 2
FAN 2
REF SHEET 02 LINE 12
REF SHEET 01 LINE 20
03
10
11
12
09
08
07
06
05
04
L3
L3
L3
L2
L2
02
01
00
PE
L1
L1
L1
L3
L2
TB1 L1 L3L2
CONT 1
DISCONNECT
PE
TB2
T1
T2
T3
T3
T2
T3
TB2
PE
T2
T3
T2
FAN 1 HARNESS
FPS 1
FAN 1
T1
T1
T1
COMPRESSOR HARNESS
43
42
X
TO SHEET 02
40
41
39
38
37
36
35
N
TO SHEET 02
25
(4 Terminal Blocks)
TB2
32
33
34 X
31
30
X
29
28
27
26
FROM LINE 21
24
23
22
L3
L1
(4 Terminal Blocks)
TB2
NN
L3
L1
L1
L3
ELECTRICAL SUPPLY
480VAC/3PH/60HZ/GND
CONT 1
-1NC -2NC H2
MTR3
L3
L2
T3
T2
L1 T1
MTR2
MTR1

17
Wiring Diagram: Model RHP1000 (230-400-460V/3/50-60 Hz)
(Page 2 of 2)
CONT 1
21
20
19
18
17
14
16
15
13
12
X
X
TB2
X
TB2
X
X5COMPRESSOR
XX
TB2
07
11
10
09
08
06
05
04
03 XX
02
01
00
FROM SHEET 01
XX
X
X
THERMISTER
CONTROL BOARD
DRAIN NEUTRAL
DRAIN LINE
THERMISTER
NEUTRAL
3
N
N
HPS
1
LINE
1
TB2
GRN/YELLOW
DRAIN HARNESS
DRAIN HARNESS
PE
TB2
3
TB2
PE
X
3
BROWN
BLUE
TEST ALM
2
1
324VAC
N
LPS
HPS/LPS SENSOR HARNESS
2 2
TB2
2
4
COMPRESSOR
CONTACTOR
4 N
TB2
NN
TB2
FROM SHEET 01
N
N
1
-4NO -3NO
O I A1
CONT 1
A2

18
7.6 Wiring Diagram: Models RHP300 through RHP1000 (575-460/3/60 Transformer Pack)
Other manuals for RHP Series
1
This manual suits for next models
6
Table of contents
Other Gardner Denver Dryer manuals

Gardner Denver
Gardner Denver SPX FLOW DHP Series User manual

Gardner Denver
Gardner Denver 9VXRD Series User manual

Gardner Denver
Gardner Denver 9VXRD Series User manual

Gardner Denver
Gardner Denver RHS20 SCFM User manual

Gardner Denver
Gardner Denver 9VXRD025 User manual

Gardner Denver
Gardner Denver 9VXRD Series User manual

Gardner Denver
Gardner Denver RDS Series Installation guide

Gardner Denver
Gardner Denver VSS Series Troubleshooting guide