Grant ESKIT User manual


2
Installation Instructions
Product specication and Installation 3
Installation and Wiring 4
DIL switch settings 5
Advanced Programming Options 5
Copy Functions 6-7
Service Interval Timer 7
Wiring Conversion 8-15
User Instructions
What is a Programmer? 16
Your programmer 17
Preset programmes 17
Resetting the unit 18
24hr or AM/PM display 18
Setting the Date, Time and Day 18-19
Accepting the preset programmes 19
Changing the preset programmes 20
Programming heating - 5/2 day 21-22
Programming heating - 7 day 23-24
Programming heating - 24 hour 25
Programming hot water 26
Running the programme 27
Temporary overrides 28
Holiday Programme 29
Changing clocks forward/back 30
Service Interval Timer 31
Fully Resetting the Unit 32
.
DAY/HOL
Central Heating
1HR override
Central Heating
MAN override
RESET
Central Heating
Mode SELECT
Hot Water
1HR override
Hot Water
MAN override
Hot Water
Mode SELECT
Index
Index

3
Installation & Specication
Please Note: This product should only be installed by a
qualied electrician or competent heating installer, and
should be in accordance with the current edition of the
IEEE wiring regulations.
Specication 230V model 24V model
Power supply 230 Vac,
±15%,
50/60 Hz
24 Vac,
±15%,
50/60 Hz
Switching action
2 x SPDT internally linked,
Type 1B
Unit switch rating 230 Vac,
3(1)A
24Vac,
3(1)A
Battery back-up 24 hours minimum
Programme resolution ± 1 minute
Dimensions, mm (W, H, D) 135 x 88 x 32
Design standard EN 60730-2-7
Control Pollution Situation Degree 2
Rated Impulse Voltage 2.5 kV
Ball Pressure Test 75°C
Product specication
Installation Instructions
Installation
Remove wallplate from unit by unscrewing the two screws
on the bottom edge of the unit.
From the top left hand corner of the wallplate, there must
be clearances of at least 140 mm to the right, 15mm to the
left, 30mm above and 100mm below in order to mount the
plug-on module.

4
NL1234
230V
Fused
3A
OFF
DHW
OFF
HTG
ON
DHW
ON
HTG
ELECTRONICS
N/O
N/C
N/O
N/C
The wallplate must be securely mounted either directly to
the wall using suitable wood screws or to a ush mounted
1-gang electrical accessory box using M3.5 screws.
Cable access can either be from behind for concealed
cabling, or from below for surface cabling. If surface cable
is used, cut out cable access slot on plug-on module prior
to mounting.
For wiring connections refer to diagram below.
ESKIT models are double insulated and do not require an
earth connection, however a parking terminal is provided
on the wallplate. This is clearly marked with an Earth
symbol.
Prior to mounting the plug-on module, DIL switches on the
rear of the plug-on module must be set. See diagram on
page 5 for available options.
Mount plug-on module to wallplate by locating tabs on top
of wallplate in apertures on rear of module, hinge down
and press rmly to wallplate before tightening securing
screws on bottom of wallplate.
Installation and Wiring
Wiring (For Wiring Conversion tables see - pages 8-15)
Always switch o mains rst and never t programmer
to a live wallplate.
Please Note:
On 24 volt models
power supply must
be wired to A & B
on wallplate.

5
Not Used
Gravity
5/2 Day
7 Day
Sw.1
Sw.2
Sw.3
Sw.4
Not Used
Pumped
7 Day or 24 Hour
24 Hour
DIL switch settings and Advanced Programming Options
Tick the INSTALLER SETTING box
on the inside ap label to notify
user in which mode their unit is
set (24hr, 5/2 day or 7 day).
DIL Switch Settings
Before mounting the unit, ensure the
4 DIL switches on the rear have been
moved to the required settings.
!INSTALLER SETTING
24 Hour
5+2 Day
7 Day
Advanced Programming Options
To enter advanced programming press PROG, +and DAY/HOL
together and hold for 5 seconds.
Option 1 - (3 or 2 On/O’s per day)
Use +or - to change between 3 or 2 on/o’s each day.
Option 2 - (Disable or enable auto time change)
Press NEXT, then use + or -to change between auto time
change enabled to auto time change disabled.
Option 8 - (Advanced Copy Functions)
Press NEXT, then +or -to change between the following copy
options:
(0) Standard copy in 7 day and 5+2 day.
(1) Enhanced copy in 7 day and 5+2 day
(2) Enhanced copy in 7 day and AB copy in 5+2 day.
For an explanation of the copy features and how to use them
please see page 6.
Press PROG to return to RUN.
32
3 on/o’s each day (Factory setting) 2 on/o’s each day
Auto time change enabled (Factory setting) Auto time change disabled

6
Copy Functions Explained
There are 3 possible copy functions available. These are;
Standard Copy, Enhanced Copy, and AB copy. Copy functions
are enabled/disabled in the Advanced Programming Options
(page 5).
Standard Copy: Pressing copy will copy the previous days
events into the displayed day. The unit will then display the 1st
event for the new day. This copy function is present only if the
unit is set to run in 5+2 or 7 day mode.
Enhanced Copy: The enhanced copy function is available in 7
day mode only. This allows any day to be copied to any other
day, or days. To use the enhanced copy function go into the
event programming using the PROG button, then:
Use the DAY button to nd the day to be copied from.
Press the COPY button to select the day to be copied from.
When selected, the day should begin to ash.
Use the DAY button to nd the day to be copied to.
Press COPY button to copy the selected day.
Repeat steps 3 and 4 to select and copy other days.
To stop copying, use the DAY button to go back to the
ashing day and press the COPY button. The previously
ashing day will stop ashing to indicate it has been de-
selected.
NOTE: When a day has been copied to, it will remain visible and
not ashing when the DAY button is used to select other days.
AB Copy: The AB copy function is available in 5+2 mode only
and only if activated in the Advanced Programming setting.
A and B days, when selected, can be any group of days e.g. 5+2,
4+3 etc. The days do not have to run in sequence. For example,
to operate in a 5+2 day mode the days can be set as follows:
1.
2.
3.
4.
5.
6.
Copy Functions

7
Service Interval Timer
The ESKIT is tted with an installer setback service interval
timer. If this feature is required please contact our technical
department. Setting instructions for this gas safety feature are
only available to bona de heating installers.
To use the AB copy function – press the PROG button:
This will show the“A” days, with all the days selected.
Use the DAY button to highlight a day.
Subsequent presses of the DAY button will increment
through the days.
Press the +button to select a specic day as an “A” day, or
press the –button to specify a day as a “B” day.
Once the day has been selected as an “A” or “B” day the
programme will automatically jump to the next day.
When the last day of the week is active, pressing +, -, or DAY
will move back to the “A” days displayed with no selected
(ashing) days (see image below).
Repeat 2 to 6 until all selections have been made.
When selections are completed, press the PROG button to
move to event programming.
Event Programming in AB mode
Programme“A”day events using the +(time advance), - (time
decrease), and NEXT (next period) buttons.
Press the DAY button to change to programme the“B” days
Programme“B”day events using the +(time advance), -(time
decrease), and NEXT (next period) buttons.
1.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
A Days B Days
Mon Tues Thurs Fri Sat Wed Sun
DIL switch settings and Advanced Programming Options

8
Wiring Conversions, (applies only to 230 volt models)
Wiring conversions can be used when replacing the following
programmers with the ESKIT. Some time controls are
connected dierently depending on the type of system
they are controlling. Consult the column headed “NOTE This
conversion ...” to determine whether Table A (pages 8-11) or
Table A
GRANT
ESKIT
(PUMPED)
MAINS DHW
OFF
HTG
OFF
DHW
ON
NL1 2 3
DANFOSS RANDALL 922/972 N L 1 4 3
DANFOSS RANDALL 4033 7 6 5 3 4
DANFOSS RANDALL SET 5 N L 3 6 1
HORSTMANN 423, AMETHYST 7 & 10 2,3 1 4 6 5
HORSTMANN 424 GEM 2,3 1,10 6 9 4
HORSTMANN LEUCITE 423 & 424 2 1 4 8 3
HORSTMANN 425 DIADEM N L 3 6 1
HORSTMANN 525 & 527 N L 3 6 1
HONEYWELL ST669 N L 7 4 6
HONEYWELL ST6300 & ST6400 N L 1 2 3
PEGLER SUNVIC SP50/SP100 N L 1 4 2
POTTERTON EP2000, EP3000 N L 1 2 3
RANDALL TSR3+3 3,6 7 2 5 1
RANDALL 3033 1,7 6 5 3 4
RANDALL 702 N L 4 2 3
SANGAMO FORM 1 410 & 414 4,5 6 2 7 1
SANGAMO S409/1 N,1,3 L - - 2
Wiring Conversions

9
Table B (pages 12-15) should be used. If in any doubt, contact
our Technical Services Department before proceeding with the
replacement. *Any wires connected to switch COMMONS which
are linked LIVE on existing wallplates must be transferred to the
LIVE terminal on the new wallplate.
HTG
ON
Wires other
than links in
these terms
go to LIVE
NOTE
This conversion applies
only if....
An additional terminal
block may be required
where these discon-
nected leads (or pairs)
should be terminated
4LL
ABCD
625 Programmed
selectors UNLINKED
21-
425
7-- 8
7 5 8 Terminals 5,8 & 10 are LINKED
6 5 7 Terminals 5 & 7 are LINKED
425 Programme
selectors UNLINKED
425 Programme
selectors UNLINKED
385
4--
53- SS
4-5 Programme
selectors UNLINKED ABCD
4--
2--
165
83-
5--
Wiring Conversions

10
Table A cont..
GRANT
ESKIT
(PUMPED)
MAINS DHW
OFF
HTG
OFF
DHW
ON
NL12 3
SANGAMO S409/3 3,6 7 4 2 5
SATCHWELL LIBRA & DHP 2201 1 2 8 5 6
SATCHWELL ET 1401 & 1451 1 2 8 5 7
SMITHS IND. CENTROLLER 90 1 2 - - 5
SMITHS IND. CENTROLLER 1000 N L 1 2 3
SWITCHMASTER 800 & 805 N L 4 2 3
SWITCHMASTER 900 & 9000 N L 4 2 3
SWITCHMASTER SONATA N L 3 6 1
VENNER CHC/W2 (WITH STAT) N,2,4 L - - 1
VENNER CHC/W2 (AIR STAT LINKED) N,2,4 L - - 1
VENNER VENOTROL 80M & 80PM
(WITH AIR STAT) N,3 L 1 4 2
VENNER VENOTROL 80M & 80PM
(AIR STAT LINKED) N,3 L 1 4 2
Wiring Conversions

11
W
HTG
ON
Wires other
than links in
these terms
go to LIVE
NOTE
This conversion applies
only if....
An additional terminal
block may be required
where these discon-
nected leads (or pairs)
should be terminated
4LL
ABCD
1--
374
463
4-- 36
4-- Programme
selectors UNLINKED
1--
1-- Programme
selectors UNLINKED ABC
4--
A/S - - Used in a system having
independent control of
water and heating
A/S
3
3--
A/S - - A/S
5
5--
Wiring Conversions

12
Table B
GRANT
ESKIT
(PUMPED)
MAINS DHW
OFF
HTG
OFF
D
NL12
DANFOSS RANDALL 922/972 N L 1 4
DANFOSS RANDALL 102/102E/102E7 5 3,6 - -
HORSTMANN 423 DIAMOND
POTTERTON 423 N L,1,3 - -
HORSTMANN 424 DIAMOND N L,1,3 - -
HORSTMANN CORAL 423 & 424 2,3 1 - - BO
HORSTMANN 425 DIADEM N L 3 6
HORSTMANN 525 & 527 N L 3 6
HONEYWELL ST669 N L - -
POTTERTON EP2000, EP3000 N L 1 2
RANDALL TSR2P 3 1,2 - -
RANDALL MKII R6 3 1,2 - -
DANFOSS RANDALL 3060 & 3020P 1,7 6 - -
RANDALL 701 N L 4 2
DANFOSS RANDALL SET 2 N L 3 6
SANGAMO M5 410 FORM 4 4,5 3 2 7
SANGAMO S409 FORMS 1 & 4 N,1,3 L - -
SANGAMO (EARLY MODEL) S410
FORM 4 N,2 L - -
SATCHWELL LIBRA 1 2 8 5
Wiring Conversions

13
D
HW
ON
HTG
ON
Wires other
than links in
these terms to
LIVE
NOTE
This conversion
applies only if....
An additional terminal
block may be required
where these disconnected
leads (or pairs) should be
terminated
34LL
ABCD
3625 Programmed
selectors UNLINKED
12--
24-- 56
24-- 5
O
ILER
(8)
AIR
STAT
(8)
- - 4,7 5 6
1425 Programme
selectors UNLINKED
1425 Programme
selectors UNLINKED
8 7,3 6 5 ...set for gravity HW
34-5 Programme
selectors UNLINKED ABCD
5,6 7 - - 1 & 2 are LINKED
5 & 6 are LINKED 4
45-- 67
42-- 35
3165
1,5 4 2 - With Links L-2 & 1-5
1,6 8 - - 1 & 6 are LINKED
2 5 - - 6,4
1,3 4 - - 1 & 3 are LINKED
6374
Wiring Conversions

14
Table B cont...
GRANT
ESKIT
(PUMPED)
MAINS DHW
OFF
HTG
OFF
DH
O
NL12
SMITHS IND. CENTROLLER 1000 N L - -
SMITHS IND. CENTROLLER 60 1 2 - -
SMITHS IND. CENTROLLER 10 N L - -
SMITHS IND. CENTROLLER 70 1 2 - -
SMITHS IND. CENTROLLER 1000 N L 1 2
SWITCHMASTER 320 & 350 N 4,L - -
SWITCHMASTER 400 N L - 4
SWITCHMASTER 600 N L - -
SWITCHMASTER 900 & 9000 N L 4 2
VENNER VENTROL N,A,M L,L,1 - -
VENNER VENOTROL 80 (AIR STAT) N,1,
3,4 L--
VENNER VENOTROL 80 (AIR STAT
LINKED)
N,1
3,4 L--
VENNER CHC/W2 (WITH STAT) N,2,4 L - -
VENNER CHC/W2 (AIR STAT LINKED) N,2,4 L - -
VENNER VENOTROL 80P (WITH AIR
STAT) N,1,3 L - 4
VENNER VENETROL 80P (AIR STAT
LINKED) N,1,3 L - 4
Wiring Conversions

15
H
W
O
N
HTG
ON
Wires other
than links in
these terms
to LIVE
NOTE
This conversion
applies only if....
An additional terminal
block may be required
where these discon-
nected leads (or pairs)
should be terminated
34LL
ABCD
32-- 14
54-- 3
3 2 - - 1,4
54-- 36
34-- Programme
selectors UNLINKED
3 1 - - L & 4 are LINKED 2
31-- 2
31-- 24
31-- Programme
selectors UNLINKED ABC
V S,F - - T,P O
2 A/S - - A/S
5
25--
1 A/S - - Used in a system having
control of WATER ONLY
or WATER & HEATING
TOGETHER
A/S
3
13--
2 A/S - - A/S
5
2 5 - - 6,4
Wiring Conversions

16
What is a programmer?
... an explanation for householders.
Programmers allow you to set ‘On’ and ‘O’ time periods.
Some models switch the central heating and domestic hot
water on and o at the same time, while others allow the
domestic hot water and heating to come on and go o at
dierent times.
Set the ‘On’ and ‘O’ time periods to suit your own lifestyle.
On some programmers you must also set whether you want
the heating and hot water to run continuously, run under the
chosen ‘On’ and ‘O’ heating periods, or be permanently o.
The time on the programmer must be correct. Some types
have to be adjusted in spring and autumn at the changes
between Greenwich Mean Time and British Summer Time.
You may be able to temporarily adjust the heating
programme, for example,‘Override’,‘Advance’or‘Boost’. These
are explained in the manufacturer’s instructions.
The heating will not work if the room thermostat has switched
the heating o. And, if you have a hot-water cylinder, the
water heating will not work if the cylinder thermostat detects
that the hot water has reached the correct temperature.
The text below has been edited and approved by the Plain
English Campaign, who has issued a Crystal Mark to be
displayed with it.
What is a programmer?

17
User Instructions
Your programmer
The ESKIT allows you to switch your heating and hot water
on and o at times that suit you.
Your programmer has had the date and time set up during
manufacture and will automatically change between Greenwich
Mean Time and British Summer Time.
You can programme up to 3 ON/OFF times per day for the
heating and the hot water and the two systems can be operated
independently.
Preset Programmes
Your ESKIT comes ready programmed with a set of operating
times which often suit most people.
If you want to change any of these settings, you can do so by
following the instructions on pages 20-26. First, follow the steps
on page 18-19 to set the correct time and date.
Overview & Preset Programmes
Event No. Hot Water &
Heating Mon-Fri Sat-Sun**
1 1st ON 6:30 7:30
2 1st OFF 8:30 10:00
3* 2nd ON* 12:00* 12:00*
4* 2nd OFF* 12:00* 12:00*
5 3rd ON 17:00 17:00
6 3rd OFF 22:30 22:30
* Not applicable if unit set to 2 ON/OFF’s per day by installer
**Not applicable if unit set to 24 hour mode by installer
See page 20 for explanations of dierent settings

18
Before you start
Open the ap on the front of the clock. Press the RESET button
using a non-metallic object (e.g. pencil/matchstick) until you
hear a click and the 2 red lights on the front of the unit ash
once.
This will stop and restart the
electronics, without losing the
factory set time and date settings.
To fully reset the unit see page 32.
Choice of 24hr or AM/PM display
Press and hold DAY/HOL & NEXT
ON/OFF for 1.5 seconds to toggle
between 24hr clock and AM/PM
display, as required.
Setting the Date and Time
These settings are made during
manufacture and only need to be
made in the unlikely event that the
unit has lost the settings.
Setting the Date
Press and hold PROG for 5 seconds
to display year.
Use the +or -buttons to set the
correct year.
DAY/HOL
DAY/HOL
DAY/HOL
DAY/HOL
RESET, 24hr or AM/PM display, Setting Date and Time

19
Press DAY/HOL to display day and
month. Use the +or - buttons to set
the correct month (Jan = 1, Feb = 2
etc.).
Press DAY/HOL to display day and
month. Use the +or - buttons to set
day of month.
Press PROG to display the time.
The words SET TIME will appear at
the top of the display & the time will
ash on and o.
Use the +or - buttons to set the
correct time (press and hold to
change in 10 min. increments).
Setting the Day
The day of the week is set automatically.
Accepting the preset programmes
If you are happy to use the preset
programmes on page 17, you don’t
need to do anything else.
Press the PROG button once to return to run mode.
Setting Day, Accepting Preset Programmes
7

20
Before you change the preset programmes
Your installer will have set your unit to operate in one of the
following modes:
5/2 day - one set of programmes for weekdays and another
for weekends (page 21-22)
7 day - dierent settings for each day of the week.
(page 23-24)
24 hour - one set of programmes for the whole week.
(page 25)
See INSTALLER SETTING tick box
on inside ap label to ascertain
which mode your unit is set .
Please Note
The unit must be programmed in sequence and ON/OFF
times cannot be set out of sequence.
If you want to leave a preset time as it is, simply press NEXT
to move on to the next setting
Your installer will have set your unit to programme either
2 or 3 ON/OFF’s per day. If your clock has been installed to
allow 3 ON/OFF’s and you do not wish to use one of the
ON/OFF settings, simply programme the ON time to be the
same as the OFF time and the setting will not operate.
INSTALLER SETTING
24 Hour
5+2 Day
7 Day
!
Changing Preset Programmes
Table of contents
Other Grant Thermostat manuals
Popular Thermostat manuals by other brands

Flash
Flash THERMOFLASH DIGI 2 Eco quick start guide

HaiLin Controls
HaiLin Controls A4100 Installer manual

resideo
resideo Honeywell Home T6R quick start guide

Aprilaire
Aprilaire 8244 Installation and operation manual

CIAT
CIAT HELIOTHERME 3V HEE instruction manual

Belimo
Belimo CFU-D Series installation manual