G26 Ambient Oil Mist Detector
Ver.2.0 –Revision March 2022 3
6.3 SETTING OF ALARM LEVELS 37
6.4 SETTING OF SIGNAL OUTPUTS 37
7MAINTENANCE 38
8TROUBLESHOOTING 39
9SPARE PARTS 40
10MAINTENANCE INSTRUCTION 42
TABLE OF FIGURES
FIGURE 1-1: OPACITY VERSUS PATH LENGTH FOR DIFFERENT CONCENTRATION 7
FIGURE 3-1: ILLUSTRATION OF A G26AMBIENT OIL MIST DETECTOR WITH TRANSCEIVER/REFLECTOR UNIT 13
FIGURE 3-2: MOUNTING POSITION OF THE TRANSCEIVER AND THE REFLECTOR 13
FIGURE 3-3: INSTALLATION OF TRANSCEIVER 14
FIGURE 3-4: INSTALLATION OF REFLECTOR 14
FIGURE 4-1: TRANSCEIVER INTERFACE 16
FIGURE 4-2: ILLUSTRATION OF THE STRONGEST SIGNAL,NO OBSTRUCTIONS TO THE LIGHT BEAM 17
FIGURE 4-3: ILLUSTRATION OF THE WEAKEST SIGNAL,OBSTRUCTIONS TO THE LIGHT BEAM 17
FIGURE 4-4: ILLUSTRATION OF POOR ALIGNMENT 18
FIGURE 4-5: ILLUSTRATION OF GOOD ALIGNMENT 18
FIGURE 4-6: TRANSCEIVER ADDRESS SETTINGS 19
FIGURE 4-7: SYMPTOM OF ADDRESS CONFLICT 20
FIGURE 4-8:ACCIDENTADDRESS CHANGE (2 SENSORS HAVE THE SAME ADDRESS) 20
FIGURE 4-9: THE ILLUSTRATION OF INTERFACE SHOW -ENTER TO SERVICE MODE 21
FIGURE 4-10: SERVICE MODE (FLASHING WARNING LED) 22
FIGURE 4-11: SERVICE MODE (1 SIGNAL STRENGTH LED REPRESENTS 10MINUTES) 22
FIGURE 4-12:THE SERVICE MODE TIMER INDICATION MAX 60 MINUTES 22
FIGURE 4-13: HOME MENU WITH 1CONFIGURED SENSOR 24
FIGURE 4-14: HOME MENU WITH 2CONFIGURED SENSORS 24
FIGURE 4-15: SENSOR MENU 26
FIGURE 4-16:ALARM LIST MENU 26
FIGURE 4-17: SELECT AN ALARM IN THE ALARM LIST MENU 27
FIGURE 4-18:ALARM INFO SCREEN -E.G.NOT ALIGNED ALARM 27
FIGURE 4-19: TREND MENU 30
FIGURE 4-20: PASSWORD POPUP WINDOW 30
FIGURE 4-21: SENSOR SETUP 31
FIGURE 4-22: SYSTEM SETUP 32
FIGURE 5-1:AUTO SPAN CALIBRATION READY TO STARTAFTER THE ZERO CALIBRATION IS COMPLETE 34
FIGURE 5-2: LASER BEAM HAS BEEN BLOCKED –AUTO SPAN CALIBRATION REGISTERING 35
FIGURE 5-3:AUTO SPAN CALIBRATION ACCEPTED –NOW UNBLOCK THE BEAM OF LIGHT 35
FIGURE 5-4: THE TRANSCEIVER IN NORMAL OPERATION MODE 36