Greengate ONW-D-1001-347-W User manual

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Model # ONW-D-1001-347-W
Model # ONW-D-1001-347-V
Model # ONW-D-1001-347-LA
Model # ONW-D-1001-347-G
Model # ONW-D-1001-347-B
NeoSwitch Dual Technology Single Relay
Occupancy Sensing Wall Switch
(Ground Required)
• Readallinstructionsonbothsidesofthis
sheetrst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
General Information
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Electrical Ratings:
347VAC:
• Incandescent/Tungsten–
Max.load:4.3amps,150 0W,50/60Hz
• Fluorescent/Ballast–
Max.load:4.3amps,150 0W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test(10min
Auto),Selectable5,15,30minutes
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Light Level Sensing:0to200foot-candles
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.35"Hx1.732"W(110.49mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752 "
Wx1.9 "D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
GreenLEDindicatesUltrasonicdetection.
Specifications
Description
Coverage
TheONW-D-1001-347OccupancySensingWallSwitchisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrolandconventionalwallswitchall-in-one,usedforenergysavingsandconvenience.
ThesensorcombinesPIRandUStechnologiestomonitoraroomforoccupancy.
PIR Technology
Thesensor’ssegmentedlensdividesthefield-of-viewintosensorzones,anddetectsthechangesintemperature
thatarecreatedwhenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
US Technology
Thesensorproducesalowintensity,inaudiblesound.Itdetectsoccupancyfromchangesintheacousticwaves
causedbymotion,suchasreachingforatelephone,turningapageinabook,walkingintoaroom,turningina
swivelchair,etc.Thesensordoesnotrespondtoaudiblesound.
DualTechnologysensorsensurethegreatestsensitivityandcoveragefortoughapplicationsthussavingadditional
energy.PIRisusedtoturnthelightsONandtheneitherorbothtechnologiesareusedtokeepthelightsON.
TheONW-D-1001-347allowsthecontrolofoneloadwithoneoccupancysensorswitch.
ThesensorcanbeconfiguredtoenhanceenergysavingsbysettingtheunitforManualONoperation.
InAutomaticONMode,thelightsturnONautomaticallywhenapersonenterstheroom.InManualONMode,the
lightsareturnedONbypressingtheuniversallyrecognizedlighticonpushbutton.Ineithermode,thelightsstayON
aslongasthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyaftera
presettimedelayinterval.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtime
delayinreal-time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergy
savingsthatareavailableintheparticularapplication.
TheDaylightingfeaturepreventslightsfromturningON,whentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.
ThesensorwillswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinueto
detectmotion20secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
TheON/OFFButtonDisableOption–WhenselectedthisoptiondisablestheON/OFFbutton(s)andsensor
becomesautomaticonlycontrol.
TheONW-D-1001-347isdesignedforofficesupto300squarefeet.
Location
WheninstallingtheONW-D-1001-347inanewjunctionbox,choosetheswitchlocationcarefullytoprovideoptimum
coverageoftheoccupiedarea.Whenreplacinganexistingwallswitch,bearinmindthattheremustbeaclear
line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheONW-D-1001-347directlyintothe
hallwaywhereitmaydetectpassers-by.
Installation
TheONW-D-1001-347canbeinstalledinanystandardsinglegangbox.Itmay
beinstalledinthesamemannerasanordinarywallswitch.
• WiretheONW-D-1001-347asdescribedinthewiringsection
• MounttheONW-D-1001-347inthejunctionbox
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used
as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All
installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3.Mountunittowallbox.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6.Installwallswitchplate.
LOAD
347 VACBLACK BLUE
NEUTRAL
GROUND
GREEN
Wiring Diagram 1:
347 VAC single level
single circuit wiring diagram
LOAD 1
347 VACBLACK BLUE
NEUTRAL
GROUND
GREEN
LOAD 2
A/B SWITCHING USING TOGGLE
SWITCH TO TURN OFF SECOND LOAD
Wiring Diagram 2:
347 VAC single level switch
dual level wiring using a toggle
switch wiring diagram
,
36
8,
Minor Motion, IR
Major Motion, IR
20,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
8,
,
15
20
,
P/N 9850-000314-01

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Sensitivity Adjustments
Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthe
greenpotentiometersothatthearrowpointsU P.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthe
greenpotentiometerclockwiseinsmallincrements.RepeatStep1.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasethe
US sensitivitybyturninggreenpotentiometercounter-clockwiseinsmall
decrements.RepeatStep3.
Note:DoNotadjustsensitivityhigherthannecessary.
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillthreetofourfeetawayfromsensorforfiveseconds.LEDshouldnot
turnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPswitch5up.
2. Usenon-reflectivetapestripstocovertheportionsofthesensorlensthatviewoutsidethespace.
3. AdjustUltrasonicSensitivity.
ON/OFF Disabled Feature
1. ON/OFFButtonDisableOption–Whenselected
thisoptiondisablestheON/OFFbuttonandsensor
becomesautomaticonlycontrolregardlessofthe
settingforautomaticormanualactivation.Thisfeature
willnotallowsomeonetoturnlight(s)OFFviathe
pushbuttonwhilepeopleareincommonareassuchas
restroom,breakroomandcopyroomareas.
Daylight Adjustments
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthereis
enoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,the
sensorwillallowthelightstoturnONwhenoccupied.ThesensorwillnotallowtheDaylightingfeaturetoturntheloadOFFuntilthe
spaceisvacantorthelightlevelrisesabovethesetpointandthetimedelayexpires.WhileinManualActivationMode,ifsomeone
attemptstoturntheloadONandthereissufficientdaylightavailabletheDaylightingfeaturewillholdthelightsO F F.
1. Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Ifthisfeatureisnotneeded,leavethe
lightlevelatmaximum(fullyCW).
2. Withtheload(s)ON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPswitch8outofitscurrentposition,wait
3secondsandthenbackintoitsoriginalposition.
3. Setthelightleveltominimum(fullyCCW).
4. Letthesensortime-outsolightsareOFF.Enterthe
spaceandlightsshouldremainOFF.
5. Makesurenottoblockthesensorfromthedaylight
sourceandadjustthelightlevelpotentiometerCWin
smallincrements.(Pause5secondsbetween
eachadjustment)
6. LightswillnotturnONuponoccupancyactivation,
whentheambientlightlevelexceedsthedaylight
thresholdsetting.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10minutes.As
longastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,by
alternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedfor
manualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPswitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPswitches1and2down.(IfDIPswitches1and2arealreadydown,
toggleDIPswitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPswitch12up.
2. ThepushbuttoncanbeusedtomanuallyturnlightsONorO FF.
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
LOAD 1
BLACK BLUE
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
GROUND
GREEN
347
VAC
BLACK
BLUE
GROUND
GREEN
TRAVELLER
WIRES
Wiring Diagram 3: 347 VAC single level single circuit three-way wiring diagram
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit
per relay. Both circuits must be fed from the same phase.
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
SensorisinManualONmode Presspushbutton.IfAutoModeis
desiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.Ifthe
SensorwasturnedOFFmanuallybefore
thetimedelayexpired,lightswillremain
OFFfortheremainderofthetimedelay
PressthepushbuttontoturnthelightsbackON
DaylightingFeatureEnabled IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
ON/OFFButtonDisabled MoveDIPSwitch7down
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode
Self-Adjust
IfsensorisinSelf-AdjustMode,itmaybe
possiblefortheunittohaveincreasedthetime
delaytoa30minutedelay.Ifthelightsdonot
turnOFFafter30minutesfollownextstep.
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
PIRactivatedbyheatsource
otherthanoccupant MoveDIPSwitch5up
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
ON/OFFButtonDisabled MoveDIPSwitch7down
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
12345678
5 Minutes
15 Sec Test/Auto*
Time Delay
DIP Switch
Activation PIR Sensitivity Not UsedOverrideMaintain Lights On Not Used
Relay 1 Not Used
ON/OFF ButtonWalk-Through Mode
15 Minutes
12
DIP Switch Legend
121196
Disable
Enable
43
Auto
Manual
5
Full
50%
8
Enable
Disable
7
Disable
Enable
10
Either
Both
Default =
30 Minutes
*Self-Adjusts to
10 min. user
mode
9101112
AdjustmentsshouldbemadewiththeHVACsystemONsothattheinstallerwillbeabletodetecttheeffectofairflowonthe
operationoftheONW-D-1001-347.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopower-upandstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.Thisappliestotime
delay,USandPIRsensitivity.InpreparationfortheInstaller
Test,thetimedelayissetto15seconds,afterthesensoris
installed,poweredONandhasstabilized,theunitwilltime-
out15secondsafterthelastmotiondetected.Coverageand
sensitivitycanbeconfirmedbywatchingtheGreen(US)and
Red(PIR)indicatorLEDsonthefrontofthesensor,while
movingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.
2. Standindifferentpartsoftheroomandwaveyour
hands.LEDsshouldonlyturnONforonesecondwith
eachmotion.(IfLEDsdonotturnON,gotoInstaller
Adjustments–SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromsensorfor
fiveseconds.LEDsshouldnotturnON.(IfanyLED
turnsON,noteLEDandgotoInstallerAdjustments–
SensitivityAdjustmentssection)
4. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6. Atthispointyoucanexittheroomandletthesensortime-out.Whenthesensortimes-outandisOFFwithpowerONforfive
minutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch12outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
ON/OFF Button
PIR Lens
DIP Switches
Ultrasonic Detection
Daylight
Sensor Level
Adjustment Ultrasonic
Sensitivity
Adjustment
Red (PIR) & Green (US)
Detection LEDs
1 and 2 1234 5678
9101112
12345678
9101112
Installer Adjustments
This manual suits for next models
4
Table of contents
Other Greengate Switch manuals
Popular Switch manuals by other brands

Crystal Image Technologies
Crystal Image Technologies KVM-IP8 user manual

Rose electronics
Rose electronics MASTER SWITCH Installation and operation manual

Westermo
Westermo PSI-010-FT2G-P8G manual

Mellanox Technologies
Mellanox Technologies MSX6512-NR Hardware installation guide

Tabs
Tabs TBGW100-915 Reference manual

Gefen
Gefen EXT-DVIK-MV-441 user manual