Installation Instructions
Model # VNLW-P-1001-MV-N-W
Model # VNLW-P-1001-MV-N-V
Model # VNLW-P-1001-MV-N-LA
NeoSwitch Passive Infrared (PIR) Single Relay
Vacancy Sensing Wall Switch with Night Light
(Neutral Required)
• Readallinstructionsonbothsidesofthis
sheetfirst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
General Information
Technology:PassiveInfrared(PIR)
Electrical Ratings:
120VAC:
• Incandescent/Tungsten–Max.load:6.7amps,
800W,50/60Hz
• Fluorescent/Ballast–Max.load:10amps,1200W,
50/60Hz
MotorLoad:¼HP@125VAC
277VAC:
• Fluorescent/Ballast–Max.load:9.8amps,
2700W,50/60Hz
Ballast Compatibility:Compatiblewithmagneticand
electronicballasts
No Minimum Load Requirement
Time Delays:Self-Adjusting,15seconds/test,1,5,15,
20,30minutes,1hour,2hours
Coverage:Majormotion–1000sq.ft.
Minormotion–300sq.ft.
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:20%to90%Non-condensing
Housing:Durable,injectionmoldedhousing.
PolycarbonateresincomplieswithUL94VO.
Size:
• MountingPlate/StrapDimensions:
4.195"Hx1.732"W(106.553mmx44mm)
• ProductHousingDimensions:2.618"Hx1.752"
Wx1.9"D(66.5mmx44.5mmx48.26mm)
LED Indicators:RedLEDindicatesPIRdetection;
AmberLEDnightlight.
Specifications
Description
ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightisalightingcontrolandWall
Switchall-in-onethatisusedforenergysavingsandconvenience.
PIR Technology
ThePassiveInfrared(PIR)SingleRelayVacancySensingWallSwitchwithNightLightusesPassiveInfrared(PIR)
sensortechnologiestomonitoraroomforoccupancy.
TheVNLW-P-1001-MV-Nallowsthecontrolofoneloadwithonevacancysensorswitch.
ThelightsareturnedONbypressingtheuniversallyrecognizedlighticonPushbutton.ThelightsstayONaslong
asthesensordetectsmotionintheroom.Whentheroomisvacated,thelightsturnOFFautomaticallyafterapreset
TimeDelayinterval.
A30secondgraceperiodisaddedafterthelightsshutOFFtogivetheoccupanttimetomoveagainincasethe
lightsshutOFF.Thispreventstheoccupantfromhavingtowalk-uptopressthePushbuttontoreactivatethesensor.
ThenightlightactivateswhensensorturnslightsOFF.Thisfeaturecanbedisabled,seeDIPSwitchSettings.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
TimeDelayinReal-time.ByadjustingsensitivityandTimeDelayautomatically,thesensorismaximizingthepotential
energysavingsthatareavailableintheparticularapplication.
Location
WheninstallingtheVNLW-P-1001-MV-Ninanewjunctionbox,choosetheswitchlocationcarefullytoprovide
optimumcoverageoftheoccupiedarea.WhenreplacinganexistingWallSwitch,bearinmindthattheremustbeaclear
Line-of-sightbetweenthesensorandtheareatobecovered.AvoidpointingtheVNLW-P-1001-MV-Ndirectlyintothe
hallwaywhereitmaydetectpassers-by.
Installation
TheVNLW-P-1001-MV-Ncanbeinstalledinanystandardsingle
gangbox.Itmaybeinstalledinthesamemannerasanordinary
WallSwitch.
• WiretheVNLW-P-1001-MV-Nasdescribedinthewiringsection.
• MounttheVNLW-P-1001-MV-Ninthejunctionbox.
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF
at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main
switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be
in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2. Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.
3. MountunittoWallBox.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5. Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
6. InstallWallSwitchplate.
LOAD
120/277 VACBLACK BLUE
NEUTRAL
GROUND
GREEN
WHITE
Wiring Diagram 1: 120/277 VAC single level single circuit wiring diagram
,
36
20,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
8,
Minor Motion, IR
Major Motion, IR
Coverage
TheVNLW-P-1001-MV-Nisdesignedforofficesupto300squarefeet.
P/N 9850-000353-01
LOAD 1
BLACK BLUE
NEUTRAL
GROUND
GREEN
WHITE
120/277 VAC
BLACK
BLUE
GROUND
GREEN
WHITE
TRAVELER
WIRES
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED
ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
Wiring Diagram 2: 120/277 VAC single level single circuit three-way wiring diagram
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per
relay. Both circuits must be fed from the same phase.
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, Georgia 30269
P:770-486-4800
www.cooperlighting.com
Printed in Malaysia
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10
minutes.Aslongastheself-adjustingfeatureisenabled,theswitchwillrespondtoeachpairofFalse-offswithnonormal
OFFinbetweenbyalternatelymakingslightadjustmentstoeitherTimeDelay(by2minuteincrements)orsensitivity,so
thereshouldbenoneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIP
Switchlegend.
ResetsensorTimeDelaytofactorysettingsbymovingDIPSwitches1,2,and3down.(IfDIPSwitches1,2,and3are
alreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Night Light
UnitisshippedwithNightLightfeaturedenabled.WhensensorturnsthelightsOFF,NightLightisactivated.Todisablethis
featuremoveDIPSwitch7up.
Override
TheOverridesettingallowsthesensortooperateasaserviceswitchintheunlikelyeventoffailure.
1. MoveDIPSwitch8up.
2. ThePushbuttoncanbeusedtomanuallyturnlightsONorOFF.
PIR Sensitivity
1. PressthePushbuttontoactivatesensor.
2. Standindifferentareasoftheroomandwaveyour
hands.
3. IftheRedLEDdoesnotturnON,checkforany
obstructions.
4. Standstillthreetofourfeetawayfromsensorforfive
seconds.LEDshouldnotturnON.
5. IfRedLEDturnsONwithoutmotionorisconstantly
ONadjustPIRsensitivityto50%bymovingDIP
Switch5up.
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch
5up.
2. Usenon-reflectivetapestripstocovertheportionsof
thesensorlensthatviewoutsidethespace.
Warranties and Limitation of Liability
DIP Switch Settings Troubleshooting
Checkout and Adjustment
1 Minute
Auto*
*Self-Adjusts to
10 min. user mode
Time Delay
DIP Switch
Not Used
PIR Sensitivity OverrideNight Light
Not Used
Default =
15 Minutes
20 Minutes
30 Minutes
5 Minutes
12
DIP Switch Legend
643



















5


Full
50%
8



7
Enable
Disable
Disable
Enable
1 Hour
2 Hours
12345678
AdjustmentsshouldbemadewiththeHVACsystemonsothattheinstallerwillbeabletodetecttheeffectof
airflowontheoperationoftheVNLW-P-1001-MV-N.Useonlyinsulatedtoolstomakeadjustments.
Immediatelyafterapplyingpowertothelightingcircuit,waitapproximatelytwominutesfortheswitchtopowerup
andstabilize.
Self-Adjust
Sensorisshippedinself-adjustmode.ThisappliestoTimeDelayandPIRsensitivity.Inpreparationforthe
InstallerTest,theTimeDelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilizedthe
unitwillTime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconfirmedbywatching
theRed(PIR)indicatorLEDonthefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLED.
2. Standindifferentpartsoftheroomandwaveyourhands.LEDshouldonlyturnONforonesecondwitheach
motion.(IfLEDdoesnotturnON,gotoInstallerAdjustments–SensitivityAdjustmentSection)
3. Standstillthreetofourfeetawayfromthesensorforfiveseconds.LEDshouldnotturnON.(IfLEDturnsON,
gotoInstallerAdjustments–SensitivityAdjustmentSection)
4. Walkoutsidetheroomandwait30secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
5. Re-entertheroomandmanuallyactivatethesensor.(IflightsdonotturnONgotoTroubleshootingSection)
6. AtthispointyoucanexittheroomandletthesensorTime-out.WhenthesensorTimes-outandisinactivefor
fiveminutes,theunitwillgotoa10minuteTimeDelayusermodesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch8outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.
ON/OFF Button
PIR Lens
DIP Switches
Red (PIR) LED
Lens glows amber
when night light is
activated
1, 2, and 3 12345678
7 and 8
12345678
Installer Adjustments
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
SensorisinManualONmode PressPushbutton.IfAutoMode
isdesiredchangeActivationModetoAuto.
SensorwasturnedOFFmanually.IftheSensor
wasturnedOFFmanuallybeforetheTimeDelay
expired,lightswillremainOFFfortheremainder
oftheTimeDelay.
CheckEcoMeterLED,ifLEDisONthisis
anindicationthatthelightswereturnedOFFmanually.
PressthePushbuttontoturnthelightsbackON.
Powerinterruption Checkincomingvoltageand/orwiring.
Lights
Will Not
Turn ON
manually
Powerinterruption Checkincomingvoltageand/orwiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode.
CheckDIPSwitch8tomakesureitisdown.
SelfAdjust
IfsensorisinSelf-AdjustMode.Itmaybe
possiblefortheunittohaveincreasedtheTimeDelayto
a30minutedelay.Ifthelightsdonot
turnOFFafter30minutesfollownextstep.
2hourDelay
MaximumTimeDelayis2hours.CheckDIPSwitches
toverifyDIPSwitchsettings.IflightsdonotturnOFF
atthesetTimeDelay,checknextstep.
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5up.
Lights
Will Not
Turn OFF
manually
CallTechnicalServices
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, Georgia 30269
P:770-486-4800
www.cooperlighting.com
Pleaserefertowww.cooperlighting.comundertheLegalsectionforourtermsandconditions.

This manual suits for next models

2

Other Greengate Switch manuals

Greengate VNLW-P-1001-MV-N-W Service manual

Greengate

Greengate VNLW-P-1001-MV-N-W Service manual

Greengate ONW-D-1001-347-W User manual

Greengate

Greengate ONW-D-1001-347-W User manual

Greengate VNW-P-1001-DMV-W Quick start guide

Greengate

Greengate VNW-P-1001-DMV-W Quick start guide

Greengate OSW-P-0801-120 User manual

Greengate

Greengate OSW-P-0801-120 User manual

Greengate ONW-P-1001-SP-W User manual

Greengate

Greengate ONW-P-1001-SP-W User manual

Popular Switch manuals by other brands

3Com OfficeConnect 3CDSG8 user guide

3Com

3Com OfficeConnect 3CDSG8 user guide

Mellanox Technologies MIS5300 Hardware installation guide

Mellanox Technologies

Mellanox Technologies MIS5300 Hardware installation guide

Fracarro Smart Switchline SWI85 STPLUS Series operating instructions

Fracarro

Fracarro Smart Switchline SWI85 STPLUS Series operating instructions

Generac Power Systems 004635-3 owner's manual

Generac Power Systems

Generac Power Systems 004635-3 owner's manual

Helmholz 700-841-16S01 instruction manual

Helmholz

Helmholz 700-841-16S01 instruction manual

ATEN ALTUSEN SN0108 quick start guide

ATEN

ATEN ALTUSEN SN0108 quick start guide

WoMaster DP208 Quick installation guide

WoMaster

WoMaster DP208 Quick installation guide

FineTek SP2 Operation manual

FineTek

FineTek SP2 Operation manual

Maiwe MIEN2016 user manual

Maiwe

Maiwe MIEN2016 user manual

kasa HS210 KIT user guide

kasa

kasa HS210 KIT user guide

milleteknik 4p M user manual

milleteknik

milleteknik 4p M user manual

NetComm NP3005 user guide

NetComm

NetComm NP3005 user guide

Inline IN3546R Operation manual

Inline

Inline IN3546R Operation manual

gofanco EthSwitch24P user guide

gofanco

gofanco EthSwitch24P user guide

Ultra Products ULT31106 Specifications

Ultra Products

Ultra Products ULT31106 Specifications

D-Link DGS-1008T reference guide

D-Link

D-Link DGS-1008T reference guide

Directed Electronics VS100 owner's guide

Directed Electronics

Directed Electronics VS100 owner's guide

GRASS VALLEY KULA installation manual

GRASS VALLEY

GRASS VALLEY KULA installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.