30308778 Issue 1.06
Features
Two-wire and four-wire modes can be
programmed through hand held programmer.
Electronic address can be modified in field.
Built-in MCU processes messages intelligently.
Monitoring power supply.
Fault and action indicators available.
Four wire output cable checking.
Plug-in structure.
Standard: EN 54-18:2005.
Description
I-9301 Addressable Single Output Module works in
two-wire mode and four-wire mode.
In four-wire mode, on receiving start command from
the fire alarm control panel (FACP), it will close the
output relay to output 24VDC and illuminate the
Active indicator. If there is short, open circuit, or
power down, the module can check failure and report
it to the FACP.
In two-wire mode, on receiving start command from
the fire alarm control panel (FACP), it will close the
output relay to output normally-open normally close
contact signal and illuminate the Active indicator.
Connection and Cabling
Fig. 1 shows terminals on the module.
1
2
7
8
16
15
10
9
65
S+
5
R
10
S- COM NC
D1 D2 Z2Z1
Bottom Cover(Remove Top Cover And Terminal Plate)
NO
I-9301
Fig. 1
Z1,Z2:ConnectingwithloopofFACP, polarity-insensitive.
D1, D2: 24VDC power cable, polarity-insensitive
(only for four-wire mode).
S+, S-: Output for four-wire mode, polarity-sensitive.
Connecting with D1 (9), D2 (7) of C-9403. S+
connects with D1(9), and S- with D2(7).
NC, COM, NO: Normally open and normally close
terminals for two-wire mode.
Recommended Wiring
1.5mm2 or above fire cable for 24VDC, 1.0mm2 or
above fire cable for others, subject to local codes.
Installation
The module is simply plugged onto the base after
corresponding terminals are connected.
If the cable conduit is on the surface of the wall, the
B-9310 Back Box is available. Note the upward
arrow for mounting direction (Fig.1).
Conduit
B-9310
Back Box
Conduit Module
Module
Back Box
Fig. 2
Application
The module connects with fire control devices such
as lifts and fire doors which are activated by FACP.
The address and working mode of the module can
be programmable by a GST programmer in field.
Please refer to P-9910B Hand Held Programmer
Installation and Operation Manual for details. Factory
default mode is two-wire (number “2”). Four-wire
mode (number “1”) can be programmed in field.
The module connects with C-9403 conventional
sounder strobe. Its system connection is shown in
Fig. 3. Working mode should be set to four-wire (1),
volt output for S+, S- should connect with 4.7kΩ
resistor in parallel (refer to Fig. 3).
I-9301
Addressable Single Output Module
548m/02
0832-CPD-0838
All manuals and user guides at all-guides.com
all-guides.com
30308778 Issue 1.06
Z2
Z1
GND
+24V
S-
Z1D1 D2
S+
Z2
I-9301
4.7kΩ
1
Z
D
1
S
2
Z
K
2
D
2
1
K
G
Fig. 3
The module connects with filed devices as
shown in Fig. 4. The working mode is two-wire.
Control Input
Z2
Z1
Controlled Devices
COM
Z1
NO
Z2
I-9301
NC
Fig. 4
Setting Working Modes
On power on state, press Function and number “3”on
the programmer, “_”will show on the last digit.
Inputting one working mode and pressing Program, it
will display “P”on the screen. The working mode has
been set. Factory default mode is two-wire (number
“2”). Four-wire mode (number “1”) can be
programmed in field. Program the module before
installation and select the working mode according to
actual situation.
Warning:
Please do not connect the contact to AC control
loop directly to avoid the module or controlled
devices being damaged by strong AC
interference.
WEEE Information
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European Union.
For proper recycling, return this product to your local
supplier upon the purchase of equivalent new
equipment, or dispose of it at designated collection
points.
Specification
Operating Voltage
Signal Loop 24V(16V~28V)
Power 24VDC(20VDC~28VDC)
Standby Current
Loop≤1mA ; Power≤5mA
Action Current
Loop≤3mA ; Power≤20mA
Output Capacity
Four-wire mode: 24VDC/1A
Two-wire mode: 24VDC/2A
Output Control Type
Four-wire mode: Volt contact
output
Two-wire mode: Relay normally
open normally closed volt-free
contact output
Programming
Method
Electronically addressed
Code Range
One address within 1~242.
Indicators
Active Indicator: Red, flashes
when polling. Illuminates in
action.
Fault Indicator: Yellow,
illuminates in fault.
Ingress Protection
Rating
IP30
Operating
Temperature
-10℃~+55℃
Relative Humidity
≤93%, non condensing
Material of
Enclosure
ABS
Dimension
(L×W×H)
120mm×80mm×43mm
(with base)
Weight
About 194g (with base)
Accessories and Tools
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during the warranty period.
This warranty shall not apply to any product that is
found to have been improperly installed or used in any
way not in accordance with the instructions supplied
with the product. Anybody, including the agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
Model
Name
Remark
P-9910B
Hand Held
Programmer
Order separately
B-9310
Back Box
Order separately
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn
All manuals and user guides at all-guides.com

Other GST I/O System manuals

GST DI-M9301 User manual

GST

GST DI-M9301 User manual

GST I-9301 User manual

GST

GST I-9301 User manual

GST I-9301 User manual

GST

GST I-9301 User manual

GST I-9301 User manual

GST

GST I-9301 User manual

GST I-9301 User manual

GST

GST I-9301 User manual

GST DI-9305E User manual

GST

GST DI-9305E User manual

GST DI-M9305 User manual

GST

GST DI-M9305 User manual

Popular I/O System manuals by other brands

Savant VOM-LN04-01 Quick reference guide

Savant

Savant VOM-LN04-01 Quick reference guide

Keithley 7037 instruction manual

Keithley

Keithley 7037 instruction manual

ICP DAS USA I-7018 quick start guide

ICP DAS USA

ICP DAS USA I-7018 quick start guide

Measurement Computing PC-CARD-D24/CTR3 user guide

Measurement Computing

Measurement Computing PC-CARD-D24/CTR3 user guide

ICP DAS USA CAN-2084C Application User's Manual

ICP DAS USA

ICP DAS USA CAN-2084C Application User's Manual

SeaLevel COMM+4 3064 user manual

SeaLevel

SeaLevel COMM+4 3064 user manual

WAGO IO-SYSTEM 750-415 manual

WAGO

WAGO IO-SYSTEM 750-415 manual

Valcom InformaCast VIP-848AR-IC manual

Valcom

Valcom InformaCast VIP-848AR-IC manual

National Instruments R Series user manual

National Instruments

National Instruments R Series user manual

Teracom TCG140 user manual

Teracom

Teracom TCG140 user manual

SMC Networks EX245-EA2 Series Operation manual

SMC Networks

SMC Networks EX245-EA2 Series Operation manual

ICP DAS USA SG-3071 user manual

ICP DAS USA

ICP DAS USA SG-3071 user manual

WAGO 750-842 Quick start quide

WAGO

WAGO 750-842 Quick start quide

National Instruments FD-11637 quick start

National Instruments

National Instruments FD-11637 quick start

Siemens 6DL2804 Series Hardware installation manual

Siemens

Siemens 6DL2804 Series Hardware installation manual

Lenze c250-S operating instructions

Lenze

Lenze c250-S operating instructions

ASTi AI-Delta Technical user guide

ASTi

ASTi AI-Delta Technical user guide

Caen N625 Technical information manual

Caen

Caen N625 Technical information manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.