30303029 Issue 4.03
Features
Electronically addressed. The address can be
modified in field.
Built-in microprocessor processes messages
intelligently.
Insulation technology for input signal, good
anti-interference ability.
Cable checking.
Plug-in structure.
Description
With a microprocessor, I-9301 Addressable Single I/O
Module can communicate with fire alarm control panel
(FACP), check power cut, control output and LED.
The module closes the output relay and illuminates the
LED when receiving start command from fire alarm
control panel.
Connection and Wiring
Terminals on the module are shown as Fig. 1.
910 15 16
8721
D1 D2 Z1 Z2
V+ G COM1NO1 NC1 GST-LD-8301/I-9301
Mounting
Hole Mounting
Hole
Mounting
Direction
Fig. 1
Z1,Z2:Connecting with loop of FACP,
polarity-insensitive.
D1, D2: Polarity-insensitive 24VDC power line.
V+,G:24VDC output terminals, supplying output contact
with +24V output signal . There is 24V output at V+ and
G no matter whether the module is started or not.
NC1, COM1, NO1: Normally closed or normally open
output terminals.
Recommended Wiring
1.5mm2or above fire cable for 24VDC power line,
1.0mm2or above fire cable for other terminals, subject
to local codes.
Installation
The module is simply plugged onto the base after
corresponding terminals are connected.
Conduit Electric Box Module Conduit
B-9310
Back Box
Module
Fig.2 Fig.3
If the cable conduit is inside the wall, the base is
installed onto the electric box (Fig. 2). If the cable
conduit is on the surface of the wall, the B-9310 Back
Box is available.
Note the upward arrow for mounting direction (Fig.1).
Application
The module is designed to connect with the devices
controlled by fire alarm control panel, including smoke
exhauster, fan blower, and fire valve.
Address can be set through P-9910B programmer in
field, refer to P-9910B Hand Held Programmer
Installation and Operation Manual for specific
operation.
Mode of checking feedback signal can be set through
P-9910B programmer. After unlocking the programmer,
press Function and then number “4”, input “13” or “40”.
“13” means checking the feedback signal at any time,
“40” means checking feedback signal only in started
state. Press Program, if Pappears on the screen, the
setting is successful.
The module can directly drive a smoke exhauster
or fire valve (electrical tripping device). System
composition is shown in Fig. 4.
The Intelli