Tools needed
1
Panelboard
User Instructions
Indication position
performa elite400
Note: Only licensed Electrical Installers are
to do any installation to panelboards.
The electrical installer is to ensure that the
panelboard meets site specific requirements.
Final installation is to meet all rules as
described in AS/NZS 3000:2018.
Switchboard Mounting
The electrical installer must ensure that the
support structure or wall is adequate to support
the weight of the panelboard. All cables
entering or exiting the switchboard are to be via
a gland or sealed as required. All panelboards
have lockable doors suitable for restricted areas
as per AS/NZS 61439
Switchgear mounting in Panelboard
The electrical installer is to ascertain that
all installed devices are suitable to meet the
appropriate fault current ratings required.
The chassis on this panel board is suitable for
Hager 10kA type of MCBs and RCBOs and
was designed to suit only Hager MCBs. Hager
recommends tting only Hager approved
switchgear otherwise this may void warranty.
If the fault level at the switchboard is greater
than the MCB fault rating, they must be backed
up by current limiting fuses or current limiting
circuit breakers. For backup protection levels,
refer to Hager. Devices are to be mounted with
the DIN clip toward the centre of the enclosure.
Transportation may cause terminations,
mechanical supports and other connections to
become loose. The electrical installer is
to ensure all these connections are tightened
prior to any energisation.
Final overview prior to Energisation
Review alignment of all devices and ensure
there has been no damage during nal
terminations. The panelboard is to be cleaned
and vacuumed from lings and other foreign
objects after nal terminations are completed.
Board Mounting
Earth and Neutral Links
Neutral bars integrated neutral bars
Neutral bar size (mm) 12x9
Split neutral As standard
Earth bars Earth bars both sides
Earth bar size (mm) 12x9
Earth and neutral
bar tunnels
Single screw tunnel
Ø7mm (up to 25mm2
cable) solid and
stranded conductors
Earth and neutral
bar connection
Single stud
(M6 = 2.5Nm)
Earth and neutral
bar rating
250A
H
D W C
E
A
BF
E = Central keyhole xing point
A
E
Pozidrive
PZ3 4.5mm
performa elite400 user instruction
1
67
8
910
11
12
13
14
15
16
2
3
45
Enclosure dimensions (mm)
Standard
Chassis H W D A B C F
JPE3600 1200 600 250 350 900 560 1222
JPE4800 1200 600 250 350 900 560 1222
JPE6000 1400 600 250 350 1100 560 1422
JPE7200 1400 600 250 350 1100 560 1422
JPE9600 1600 600 250 350 1300 560 1622
JPE0EX
elite extension
400 600 250 350 150 560 422
Hybrid
Chassis H W D A B C F
JPE0612 1000 600 250 350 700 560 1022
JPE0624 1200 600 250 350 900 560 1222
JPE0636 1200 600 250 350 900 560 1222
JPE1248 1400 600 250 350 1100 560 1422