HY08AC Touch Screen Thermostat User Manual
Many thanks for your selection of our products and services, and also for your trust and support to us.
HY08AC-1 HY08AC-2 HY08AC-3 HY08AC-4
Application
HY08AC fan coil units thermostat is used for control room temperature in central air
conditioning fan coil units system.By comparing room temperature with setting temperature to
open and close fan coil units and motorized valve in the end of air conditioning system,to
achieve purpose of adjusting room temperature,comfort and saving energy. HY08AC uses
microprogrammed control unit,large LCD display,LCD display mode:working mode
(cooling,heating,ventilation), fan speed (high,middle,low, auto),room temperature,setting
temperature,time,7 days 4 period programming,timing turn on/off etc.
Technical Data
Power Supply 220V 50/60Hz
Installation Flush Installation
Rated current 3A
Sensor NTC
Set Point Range 5~35℃
Accuracy ±0.5°C
Ambient 0~50℃
Protection Class IP30
Size 86*86*14
Housing PC+ABS plastic
Ambient temperature 0°C~50°C
Storage temperature -10°C-60°C
Operation Key
NO.
symbols
represent
A
Increase key:adjust temperature and value
B
Setting key
C
Decrease key:adjust temperature and value
D
Fan speed key; +is confirm key
E
Turn ON/OFF
Displays & Buttons
Operation Instruction
Operation
Description
Turn ON/Turn
OFF
Press“ ”key one time to turn on,press it again to turn off and close fan
coil units and motorized valve.
Setting
Temperature
In turn on state,press “ ”to decrease temperature and press“ ”to increase
temperature,press every time,temperature change 0.5℃.
Fan Speed
Choice
In turn on state,press“ ” to choose fan speed
(High ),(Middle),(Low ),( ).
Time Setting
In turn on state,long press“ ”for 3-5seconds to enter into setting screen,
choose “ ” icon,press “ ” confirm to time setting:minute
“mm”flashing,press “ ”or“ ”to adjust value, press “ ” confirm to next
setting;hour “hh”flashing, press“ ”or“ ”to adjust value;press
“ ”confirm to next setting; week “ ”flashing,press“ ”or“ ”to adjust
value.At last press“ ”or no any operation for 5seconds to exit setting.
Timing Turn
on/off Setting
In turn on state,long press“ ”for 3-5 seconds to enter into setting screen,
choose “ ”icon,press“ ”confirm to timing turn on setting,it displays
“ON”and “--;--”or “hh mm”flashing at the same time,press press “ ” to
confirm and press “ ”or“ ”to adjust the hour and press “ ” and
“ ”or“ ” to adjust minute of turn on,adjust to “--;--” and press “ ” to
cancel timing turn on and enter into timing turn off setting,it
displays“OFF ”and “--;--”or “hh mm”flashing at the same time,press press
“ ” to confirm and press “ ”or“ ”to adjust the hour and press “ ” and
“ ”or“ ” to adjust minute of turn off.Cancel timing turn on/off
setting:just to adjust both timing turn on and turn off as“--”;(timing turn
on/off for one time or cycle running,please set it in advanced setting)
Working Mode
Choice
In turn on state,long press“ ”for 3-5seconds to enter into setting
screen,choose “ ” and press “ ”to confirm:switch working mode
between“ ”.Display“ ” means cooling mode,display“ ”means
heating mode,display“ ”means ventilation mode(HY08AC-1-2P no
heating mode);display “ ”means cooling,heating mode switch
automatically(HY08AC-1-4P-A).
Manual And
Programmable
Mode Choice
In turn on state,short press“ ”for one time to run programmable
mode;press “ ” again to run manual mode
HY08AC-4P-M(MODBUS and RS485 version no programmable
function)The time and temperature of programmable mode refer to
Programmable Mode Setting And Working,when working auto
programmable mode,the temperature can’t be adjusted.
Motorized
In cooling(heating)mode,when room temperature higher(lower)setting
Valve Control
temperature 1℃,open motorized valve;when room temperature reach
setting temperature,close motorized valve,fan coil continues to work(it can
be set as fan close together with valve in advanced setting).
Ventilation mode(fan coil unit is not under controlling)
Fan coil unit is under controlling,it is valve and fan coil unit close together.
Key Lock
Function
Key Lock function:if thermostat opens key lock function,no any operation
after 10 minutes will lock keys automatically(screen display “ ”
icon),press “ ” for 5 seconds will unlock(“ ”disappears)
Door Key
Energy Saving
Mode
(HY08AC-K)
Enter into energy saving mode by door card.When pull out door card,
“ ”door card icon flashing,if thermostat is in cooling mode,temperature
set as 26℃automatically,fan run in low speed;if thermostat is in heating
mode,temperature set as 18℃automatically,fan run in low speed
Alarm
Sensor occurs fault,thermostat close fan coil and motorized valve and
display“ ” and“E1”and“E2”.
E1:sensor short circuit alarm E2:sensor open circuit alarm
When temperature higher than 55℃displays “HI”when temperature lower
than 0℃displays“LO”
Programmable Mode Setting And Working
HY08AC fan coil units thermostat can set different time different temperature;there is
“”(manual programmable) and “”(cancel programmable) 2 programs can be chosen.
Manual Programmable
Long press “ ”for 3-5 seconds to enter into setting screen,,short press " ”to choose “ ”
and press “ ”to confirm and enter into manual programmable setting.
After enter into manual programmable,To begin with the first period(“ ” flashing) of
Monday,press “ ” to confirm,starting time(default 6:00),it can press“ ”or“ ”to adjust by
yourself,press every one time to increase or decrease 30 minutes and then press “ ”,press
“ ”or“ ” to adjust temperature,press “ ” enter into the second period “ ” setting,the
same as above to finish 4 periods setting,then enter into Tuesday setting,the same setting
method as Monday,then finish 7 days setting,no any operation for 5 seconds will save and
exit automatically.
Cancel programmable:long press “ ”for 3-5 seconds to enter into setting screen,short press
“ ” to choose “ ”programmable,press “ ”to confirm and to cancel programmable mode
back to upper setting screen.Press “ ”to choose next setting or waiting for 5 seconds to exit
Default Setting
Period
Period Setting
Default Time
Default Temperature
Monday
To
Sunday
1
06:00
23
2
8:00
26
3
17:30
26
4
22:00
23
Advanced Setting
In turn off state,long press “” for 5 seconds to enter into advanced setting.Press“ ”or“ ”to
set,short press “ ”to next option and press“ ”or“ ”to set
Display
Sign
Setting Options
Data Setting Function
Factory
Default
A1
Measure Temperature Calibration
-9-+9℃
(Display room temperature,
Press , to calibrate room
temperature)
0.5℃
Accuracy
Calibration
A2
Children Lock Setting
0:Half Lock;(can turn on/off
and adjust temperature)
1:Full Lock
0
2:Cancel Children Lock
A3
Setting Temperature Lowest Limit
1-25℃
5℃
A4
Setting Temperature Highest Limit
30-70℃
35℃
A5
Fan Coil Units Control
0=Fan Under Control
1=Fan Isn’t Under Control
0
A6
Timing Turn On/Off Running Way
0=Timing Turn On/Off For
One Time
1=Timing Turn On/Off For
Cycle Running
0
A7
Key Card Status
00:S1 Connect S2 Means
Put-in Card Status;
01:S1 Disconnect S2 Means
Pull-out Card Status.
00
A8
After Door Card Pull Out To Cool
Temperature
Setting Range 22 ~32 ℃
26℃
A9
After Door Card Pull Out To Heat
Temperature
Setting Range 10~21℃
18℃
AA
Valve Output Choose
2: 2Pipes 4:4 Pipes
4
AB
Return To Factory Default Setting
Display A o,Long Press Fan
Key To Return To Factory
Default Setting
Wiring Diagram
Cautions on Installation and Use
1. To prevent the thermostat display from a high fluctuation, special treatment has been made
to the program. Therefore, it is normal that the thermostat cannot immediately display the
sudden change of temperature.
2. The thermostat installed on 1.5m above the ground.
3. For the thermostat installed,please take care not to install it to the wall corner, door /
window side or behind the door or in such unheated area as exterior wall. Avoid hot / cold
air duct, radiator, flue or thermal pipe.
4. If you have any problem for the installed ,please contact our company hysen, we will make
a demonstration for you
5. Only the professional technicians are permitted to open the transmitting and receiving box
of the thermostat for installation. When install the power supply, make sure that the power
cable is well insulated.
6. The thermostat is unrepairable product. The user shall not open the internal circuit board.
7. HY08AC series thermostat design for the standard 75x75x 35mm wall mount box installed.
Follow the instructions to open the rear cover base, mount it on the wall and wire it.
8. Before installing the thermostat, make sure that the system is disconnected. The maximum
voltage of the system shall meet the requirements specified in the Instruction Manual (Max.
AC Voltage: 250V).
Warranty:
We offer the warranty of 18 months, from the sales day. The products of our company can have
lifetime warranty ,if it is not the quality problems, or beyond the warranty period, we will charge
for the after-sale service.

This manual suits for next models

3

Popular Thermostat manuals by other brands

Zonex SubZone manual

Zonex

Zonex SubZone manual

Honeywell TH8320ZW1000 installation guide

Honeywell

Honeywell TH8320ZW1000 installation guide

American Standard T010.730 installation instructions

American Standard

American Standard T010.730 installation instructions

Zonex MODSTAT / MODS2 installation instructions

Zonex

Zonex MODSTAT / MODS2 installation instructions

JUMO WTHc Series operating instructions

JUMO

JUMO WTHc Series operating instructions

Honeywell RTHL221 series Quick installation guide

Honeywell

Honeywell RTHL221 series Quick installation guide

sisel Enda EDT5412A quick start guide

sisel

sisel Enda EDT5412A quick start guide

Bpt TH 350 Instructions for use

Bpt

Bpt TH 350 Instructions for use

Cosytoes Vista Timerstat instructions

Cosytoes

Cosytoes Vista Timerstat instructions

Tekmar tekmarNet 552 user manual

Tekmar

Tekmar tekmarNet 552 user manual

Zehnder Rittling Z23015 operating instructions

Zehnder Rittling

Zehnder Rittling Z23015 operating instructions

Osaka F 100 user manual

Osaka

Osaka F 100 user manual

Robertshaw 9420 user manual

Robertshaw

Robertshaw 9420 user manual

Lennox icomfort quick start guide

Lennox

Lennox icomfort quick start guide

Emerson 1F75P-21PR Installation and operating instructions

Emerson

Emerson 1F75P-21PR Installation and operating instructions

iDevices HVAC installation guide

iDevices

iDevices HVAC installation guide

SUNSTONE P-Stat + installation instructions

SUNSTONE

SUNSTONE P-Stat + installation instructions

Hitecsa i-Basic 3 Installation, operation & maintenance manual

Hitecsa

Hitecsa i-Basic 3 Installation, operation & maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.