Description
The Zone Input Device is available in two variants:
The DIN-Rail Mounted Zone Input Device, Item No 4210-0058, is designed to be mounted in an enclosure,
clipped onto a standard 35mm DIN Rail (DIN46277) and secured using the built in fixing. End stops can also
be used to provide additional security. Alternatively, the 4210-0058 can be mounted direct to an enclosure
back panel using the internal preformed fixing holes.
The Enclosed Zone Input Device, Item No 4210-0059, is supplied within a backbox for surface mounting.
Note: Both variants are not intended for outdoor use unless mounted in a suitable weatherproof
enclosure.
The installation must conform to applicable local codes and be carried out such that the Zone Input Device is
not subjected to exposure to temperatures exceeding the maximum ambient, exposure to moisture, dust
and foreign bodies or exposure to a risk of mechanical damage.
The Zone Input Device is loop powered and controlled by the main fire control panel. The address is set using
the onboard DIL switch.
The Zone Input Device incorporates a bi-directional short circuit isolator between the loop input and loop
output terminals which will protect the conventional zone of detectors against a single loop short circuit on
either side of the device.
Installation
DIN Rail - Item No 4210-0058
Clip the Zone Input Device to the standard 35mm DIN rail using the Red locking clip located in the front of
the device. Alternatively, fix direct to the enclosure back panel using appropriate M4 nuts and bolts.
Enclosed - Item No 4210-0059
Remove the clear ABS cover and securely mount the backbox to a wall or suitable structure using the integral
fixing positions then install all external cables using the knock outs and/or cable tray entry points as required.
1. Connect the cables from the detection loop and the conventional detector zone into the device. Ensure
that the earth continuity is maintained.
2. Set the End of Line (EOL) monitoring to match the device used by the conventional zone circuit in
accordance with Table 1. Polling LED indication can also be enabled during commissioning.
3. Set the Device address using the DIL switch in accordance with the address Table 2 and record the
location description of the device itself together with the address setting on the device fascia label.
4. Following commissioning ensure that the device is securely fastened and replace the ABS clear cover.