
Hawken Energy - GX10 | Owners Manual 5
properly supported. If pouring concrete, don’t forget to
leave a space for the underground feed and return pipe.
Although outdoor prevailing wind and smoke considerations
should be given rst priority, your outdoor boiler location
selection may also minimize the amount of purchased pipe
required. Authorized Hawken underground pipe loses very
little heat, so longer distances will not cause signicant heat
loss, but reducing distance will reduce cost of purchased
pipe. Finally, keep in mind that the underground pipe must
enter the home or building to be heated, and plan for this
accordingly.
Preparing the Location for Your Hawken
When preparing the location for your boiler, please consider
the following:
When possible, install underground pipe before delivery and
placement of boiler. This simplies the placement process.
If installing boiler on a cement pad, it is recommended to
install underground pipe before pouring cement pad. Make
sure to leave a hole in cement pad (minimum 12” square)
between rear legs for underground pipe to connect to rear
of boiler. Installation should be performed by a qualied
installer. For customers who require chimney extensions,
insulated pipe is required. Contact Hawken to ensure that
the insulated chimney extensions you purchase mate with
the factory installed chimney on your unit.
Your warranty requires the use of Hawken authorized water
treatment. You MUST take the steps listed below to ensure
the proper operation of your Hawken. Further, your Hawken
and its components will receive better protection against
corrosion, your lter will require cleaning less frequently and
your system will last longer.
First Time Fill - Water Testing
1. Before you ll your boiler the rst time, purchase from
your Hawken Rep the appropriate amount of Hawken autho-
rized water treatment. Follow the directions on the bottle
for how much to add to your system. Your dealer will also
provide you with sample test bottles and labels so that you
can submit a water sample annually for laboratory testing
(follow instructions included with test bottles.)
2. Once your installation is complete, ll your new boiler so
that it is approximately half full of water. Make sure all valves
are closed. Do not ll boiler with water until your installation
is complete, and the drain valve is properly installed.
3. Add the appropriate amount of Hawken authorized water
treatment.
4. Fill your boiler until it is completely full of water. You will
know it is full when water spills out of the vent tube onto the
roof of the boiler.
5. Once full of water, do not start a re in your boiler yet.
6. Open all necessary valves, wait 5 minutes, then turn on
your pump. Allow the pump to circulate the water for at
least 2 to 4 hours.
7. After the pump circulates the water for at least 2 to 4
hours drain a small sample of water FROM THE DRAIN
VALVE LOCATED AT THE BOTTOM OF THE BOILER.
Follow the enclosed directions to send this water sample for
testing. You may now startup your boiler.
8. Once your water sample is received by the laboratory and
tested, you will receive a lab report containing the results
from your water sample test. Please be sure to legibly print
your information on the label provided. Please provide an
E-mail address where you would like your report to be sent.
If your water is found to contain anything harmful to your
Hawken, further action on your part will be specied in this
lab report. If any further action is required on your part,
you must comply with the instructions provided in the lab
report. Once you do so, you will then be required to submit
another water sample to the lab for testing. Please take this
sample according to instructions below under “Periodic
Testing”. A “satisfactory” water sample report must be on
le at Hawken to maintain your warranty and this must
be renewed annually. Please save reports for your own
records.
9. Follow instructions below for Periodic Testing. Your
Hawken authorized water treatment will indicate how often
such testing is necessary (currently once per year). Any
changes to this testing procedure will also be specied
in service bulletins posted at www.HawkenEnergy.com/
servicebulletins/ which you should check semiannually.
Periodic Water Testing
Periodic water testing must be completed at least once
per year. This is a free test, but in order to maintain your
warranty you must comply with the following instructions.
1. First, a sample of water must be taken from the boiler. To
do so, please observe the following steps:
a. The boiler must be turned off and cooled in order to take
the water sample. If the boiler is going to sit idle during the
summer months, it is best that testing and proper amounts
of water treatment chemical are added to the boiler prior to
the idle summer months.
b. NEVER DRAIN YOUR BOILER AND LEAVE IT EMPTY OF
PROPERLY TREATED WATER. Always have your boiler full
of properly treated water.
c. Let the re burn out. Allow the boiler to cool until the
water temperature is below 80 degrees F.
d. Remove the ash. Lightly scrape the inside of the rebox
to remove the ash.
e. Shut off the power to the boiler to stop the pump(s).
f. Make sure the ball valves to the pumps are in the open
position to avoid any air lock upon restart. Never attempt to
operate the pump(s) with the ball valves (to pumps) in the
closed position.
g. If you have a forced air furnace with a second Hawken
thermostat, turn the thermostat off.
h. Attach a hose to the water jacket drain at the bottom of
the boiler.
i. Open the water jacket drain until the water runs clear.
Close the drain. This is an important annual maintenance
item that ushes any sediment buildup from the boiler.