Haws 8346 Guide

1/09 Model 8346/8346CRP Page 1 of 5
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
Model 8346/8346CRP Shower & Eye/Face Wash
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
No. 2080177(15)
LIMITED WARRANTY
HAWS®warrants that all of its products are guaranteed against defective material or poor
workmanship for a period of one year from date of shipment. HAWS liability under this
warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any
goods, or part thereof, which shall appear to the Company upon inspection to be of
defective material or not of first class workmanship, provided that claim is made in writing
to company within a reasonable period after receipt of the product. Where claims for
defects are made, the defective part or parts shall be delivered to the Company, prepaid,
for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements,
or for any expense connected therewith made by the owner or his agents, except upon
written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages
caused by defective materials or poor workmanship, except for replacements, as provided
above. Buyer agrees that Haws has made no other warranties either expressed or implied
in addition to those above stated, except that of title with respect to any of the products or
equipment sold hereunder and that HAWS shall not be liable for general, special, or
consequential damages claimed to arise under the contract of sale.
The emergency equipment manufactured by HAWS is warranted to function if installation
and maintenance instructions provided are adhered to. The units also must be used for
the purpose, which they were intended. This product is intended to supplement first-aid
treatment. Due to widely varying conditions HAWS cannot guarantee that the use of this
emergency equipment will prevent serious injury or the aggravation of existing or prior
injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDED
OR GIVEN BY HAWS.
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS
MODEL, PLEASE CALL: 1-800-766-5612
FOR PARTS CALL: 1-800-758-9378
(U.S.A. AND CANADA ONLY) MONDAY-THURSDAY: 6:00 A.M. – 4:00 P.M. PST
FRIDAY: 6:00 A.M – 1:00 P.M. PST

1/09 Model 8346/8346CRP Page 2 of 5
LOCATION OF UNIT: The Model 8346/8346CRP Emergency Shower should be installed in
close proximity to potential accident areas. It should be clearly identified, free from obstructions
and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4” IPS with 30-90 psi (2-6 ATM)
flowing pressure. Where sediment or mineral content is a problem, an inlet filter is
recommended.
PLUMBING CONNECTIONS: Inlet supply is female 1-1/4” IPS. Waste outlet is female 1-1/4”
IPS.
INSTALLATION PROCEDURE
Refer to Installation Drawing for clarification. Check parts list to insure all required parts are
included. Use pipe joint sealant PST #565 (Loctite) on all connections.
Step 1: Prepare the emergency shower foundation by using the floor flange assembly as a
template. Locate the three holes for the 3/8-16 UNC x 6” anchor bolts (not supplied).
They should extend 1” above the floor level.
Step 2: Once the concrete foundation is ready (dry), assemble the floor flange assembly to
the anchor bolts; then securely fasten with 3/8-16 UNC Hex nuts and 3/8” washers
(not supplied), seal and tighten floor flange and tee making certain the waste tee is
facing the proper location and the foot control holes are facing side to side.
Step 3: Assemble nipple (1-1/4” x 21-1/2”) to the floor flange assembly and tighten with a
pipe wrench.
Step 4: Assemble the eyewash loop assembly to the 21-1/2” nipple from step three. Connect
the pipe wrench to the galvanized nipple between the two tees to avoid damage.
Step 5: Assemble in the following order:
Attach nipple (1-1/4” x 24”) onto the loop assembly.
Attach nipple (1-1/4” x 24”) onto the tee.
Attach tee (1-1/4” x 1-1/4” x 1”) onto nipple.
Attach nipple (1x 9”) valve assembly onto tee.
Attach street elbow (1”) onto nipple (1” x 12-1/2”) and insert flow control assembly,
tapered end first, on opposite end of nipple (1”). See SP829 Installation Drawing for
details.
Attach nipple with flow control onto valve.
Step 6: Assemble showerhead onto street el (1”). If necessary, use Dow Corning 832 sealant
placing 5 small beads on the male threads, just above the first thread.
Step 7: Assemble the sign onto the unit. Use the strap, screws, washers and nuts provided
to mount the sign onto the upright. The sign should be positioned for maximum
visibility.
Step 8: Insert the galvanized plug into the optional supply line tee that is not used. Before
connecting the supply water line to the emergency shower; FLUSH THE LINE
THOROUGHLY.

1/09 Model 8346/8346CRP Page 3 of 5
TROUBLESHOOTING
PROBLEM REPAIR CHECKLIST
1. No flow. 1. Check the main shut-off valve.
2. Insufficient water flow, shower and
eyewash. 2. Verify minimum 30 psi (2 ATM) flowing
supply line pressure.
3. Insufficient water flow on eyewash,
however, shower is sufficient. 3. a. Verify minimum 30 psi (2 ATM) flowing
supply line pressure.
b. Probable clogging of flow control due to
inadequate line flushing. Unscrew
eye/face wash head and remove the
four screws to disassemble head.
Clean flow control and reassemble
head. See SP65 Installation Drawing
for details.
c. Remove cap located on L – Strainer
using a 3/8” allen wrench to access and
clean filter screen.
4. Eyewash stream does not meet
desired eye level. 4. Possible blocked flow control, see
above solution. Possible non-leveled
eyewash assembly. Eyewash nozzles
should be at equal heights.
5. Water does not drain properly. 5. Check the main waste line of your
building to see if it does handle the
capacity required for the entire
drainage system.
6. Insufficient water flow at the
showerhead, however, eyewash is
sufficient.
6. Probable clogging of flow control
located between 1” nipple and outlet
side of 1” valve on shower arm
assembly. See SP829 Installation
Drawing for details. Reassemble flow
control with tapered end going into 1”
nipple.
© 2009 Haws®Corporation – All Rights Reserved