HGI Generators KUMS080HAE1X004 Manual

Ravenstor Road
Wirksworth
DERBYSHIRE
DE4 4FY
:: +44 (0)1629 824284
:: +44 (0)1629 824613
FAX
www.HGIgenerators.com
::
::
::
Email
Operation & Maintenance
Manual
Fuel Proof Limited
Publication No. 498-141
8.0kVA 1500rpm
Single Phase Key Start Diesel Generator
Build Code: KUMS080HAE1X004

Version Control Harrington Generators International
8kVA Diesel Generator Part No: 498-141
Name Position Date
Originator: M. Crowfoot Technical Department Mar 2012
Approved by: K. Croft Technical Department Mar 2012
Document Authorisation
Document History
Date Version Author Reason for change
08.03.12 Provisional M. Crowfoot Draft for review by C. Coulton
14.03.12 A M. Crowfoot First Release
Document Distribution
Name Position Organisation Date Issued Format

Contents Harrington Generators International
8kVA Diesel Generator Part No: 498-141
Section Contents Page
1.0 Certificates and Specification
1.1 EC Declaration of Conformity 7
1.2 Certificate of Conformity 8
1.2 Data Plate 9
2.0 Specification
2.1 General Dimensions 11
2.2 General Specification 12
3.0 Safety
3.1 General Precautions and Warning Labels 13
3.2 Electrical Safety and Earthing 20
3.3 Lifting 20
3.4 Hazards to Health and Electrocution 21
3.5 Electrocution 23
4.0 Operation and User’s Instructions
4.1 Control Panel 24
4.2 Engine Oil and Coolant 25
4.3 Starting Manually 25
4.4 Stopping Manually 25
4.5 Power Output Connections 25
4.6 Shut Down Protection Devices 26
4.7 Fuel Filling 26
5.0 Fault Finding
5.1 Engine Fails to Start 27
5.2 Engine Stops While Running 28
5.3 Other Engine Faults 28
5.4 No Electrical Output 29
6.0 Maintenance
6.1 Service Schedule - Kubota 30
6.2 Engine Oil & Coolant 31
6.3 Fuel System 31
6.4 Engine Valve Clearances 31
6.5 Battery 31
6.6 Alternator 31
6.7 Earth Leakage Unit and Miniature Circuit Breaker ( MCB’s ) 31
6.8 Control Module 31
6.9 Battery Charger 32
6.10 Canopy and Trolley 32
6.11 General Inspections 32
6.12 Maintenance Record Sheet 33
7.0 Spares and Service
7.1 Contact Details 34
7.2 Spares List 35
8.0 Long Term Storage
8.1 Long Term Storage 36
9.0 Warranty Statement
9.1 Warranty Statement 37
10.0 Wiring Diagrams
10.1 Wiring diagrams 39
11.0 Notes 41

Section 1 - Certification Harrington Generators International
8kVA Diesel Generator 7 Part No: 498-141
In accordance with ISO/IEC 17050-1:2004 Conformity Assessment - Suppliers’ Declaration of Conformity
EC DECLARATION OF CONFORMITY
Conforms to the protection requirements of the following EC Council Directives:
98/37/EC Machinery Directive
2006/95/EC Low Voltage Directive
2004/108/EC EMC Directive
2000/14/EC Noise Emission in the Environment by Equipment for use Outdoors Directive Annex VIII
97/68/EC Measures against the emission of gaseous and particulate pollutants from internal combustion
engines to be installed in non-road machinery.
European level Stage 2 (for engines above the minimum kW power threshold).
And has been designed and manufactured to the following Standards :
BS5000 Part 3 Rotating electrical machines of particular types or for particular applications. Generators to
be driven by reciprocating internal combustion engines.
EN60204-1 Safety of machinery. Electrical equipment of machines. General requirements
EN12601 Reciprocating internal combustion engine driven generating sets. Safety
BS EN 61000-6-1 EMC. Generic standards. Immunity for residential, commercial and light-industrial
environments.
BS EN 61000-6-2 EMC. Generic standards. Immunity for industrial environments
BS EN 61000-6-3 EMC. Generic standards. Emission standard for residential, commercial and light-industrial
environments.
BS EN 61000-6-4 EMC. Generic standards. Emission standard for industrial environments
BS ISO 3744 Acoustics. Determination of sound power levels of noise sources using sound
pressure.
I declare that as the authorised representative, the above information in relation to the supply and
manufacture of this product is in conformity with the stated standards and other related documents
following the provision of the above EC Directives.
Signed Ken Croft (Quality Manager) Date: 12.03.12
We:
Harrington Generators International Ltd.
Ravenstor Road
Wirksworth
Derbyshire
DE4 4Y
Declare that
Equipment : Diesel Generator
Model name/Number : KUMS080HAE1X004
Electrical Power Pel : 8kVA / 6.4kWe, PF: 0.8
Measured Sound Power Level : 87 dB(A)
Guaranteed Sound Power Level : 88 dB(A)
As Specified @ 10 mtrs
Notified Body for 2000/14/EC Noise
Emission in the Environment by Equipment
for use Outdoors Directive
Mira UK Ltd
Watling Street
Nuneaton
Warwickshire
CV10 0TU
Notified Body Number : 0888
1.1 EC Declaration

Section 1 - Certification Harrington Generators International
8kVA Diesel Generator 8 Part No: 498-141
Certificate of Conformity
Customer: Fuel Proof
Customer Purchase Order No(s): Your order no. N/A
HGI Reference: Sales Order 66088
Delivered To:
Fuel Proof Ltd
Middleton Business Park
Middleton Road
Heysham
Delivery Date: March 2012
HGI Part No: Customer’s
Part No: Description Qty
Ordered
Qty
Delivered
KUMS080HAE1X004 --- 8kVA V1105 Mec Alte 230V 50Hz
Bunded Base 26 26
HGI’s Serial No(s): 66088 / 01 to 26
We : Harrington Generators International Ltd.,
Ravenstor Road, Wirksworth, Derbyshire, DE4 4FY.
Declare that:
The articles have been subjected to and satisfactorily completed the tests defined in the OEM
current Specification.
The articles meet the OEM specification.
The articles are in conformity with the following requirements:
The required European Directives and British / European Standards
Approved Deviations and / or
Concessions:
Commercial: None.
Technical: None
Signed: Quality Manager Date: 12/03/12
For and on behalf of Harrington Generators International Limited
1.2 Certificate of Conformity

Section 1 - Certification Harrington Generators International
8kVA Diesel Generator 9 Part No: 498-141
1.3 Data Plate
Below is a blank copy of the generator’s Data Plate which is located on the base on the service door side.
Fill in the data on the blank copy below. There serial number in particular will be needed to order spare
parts etc.
HARRINGTON GENERATORS
INTERNATIONAL LTD
kVA 8.0 pf 0.8
Voltage 230 Hz 50
Amps 34 Ph 1
RPM 1500 Weight 640 kg
Serial No. SOR 66088 Date March 2012
RAVENSTOR ROAD, WIRKSWORTH,
DERBYSHIRE,
ENGLAND DE4 4FY
Tel: +44(0)1629 824284 Fax:+44(0)1629 824613
www.HGIgenerators.com
This Specification shows the following technical information :-
This is the “CE” mark and indicates that the generator complies with the Eu-
ropean Directives as detailed in the Certificate of Conformance.
kVA This is the power in kVA.
the power factor, voltage, current and phase
Pf: This is the power factor generally 0.8 which means the generator is suitable
for most applications.
Voltage: This is the nominal voltage .e.g. 400V, 230V or 110V
Hz: This is the electrical frequency generally 50 Hz
Amps: This is the nominal electrical current of the principal voltage
Ph: This is the number of electrical phases “ 1 “ phase or “ 3 “ phase supply.
rpm: This is the engine speed.
Serial No: This is a unique number which identifies the generator. This is important
when ordering spares or contacting our Technical Help Line.
Date: This is the date of manufacture .e.g. 23 / 11 / 99.
Weight: This includes engine oil and about half a tank of fuel.

Section 2 - Specification Harrington Generators International
8kVA Diesel Generator 10 Part No: 498-141 8kVA Diesel Generator 10 Part No: 498-141

Section 2 - Specification Harrington Generators International
8kVA Diesel Generator 11 Part No: 498-141 8kVA Diesel Generator 11 Part No: 498-141
2.1 General Dimensions

Section 2 - Specification Harrington Generators International
8kVA Diesel Generator 12 Part No: 498-141 8kVA Diesel Generator 12 Part No: 498-141
Power Output
Prime Power 8kVA (6.4kW)
Power Factor 0.8
Frequency 50Hz
Voltages 230V AC
Engine
Make Kubota
Model D1105
Cylinders 3
Power 8.4kW
Speed 1500 rpm
Oil Qty 5.1 Litres
Starting System Electric Start 12V
Battery 12V 58Ah 600CCA
Maintenance Free
Battery Charger Engine Driven
Alternator
Make Mecc Alte
Model ECO 28 S/4
Related Output 16kVA
Bearings Single
Poles 4
Insulation Lass Class H
IP Rating IP21
Regulation +/- 1%
Base
Material Mild Steel
Paint White
Dimensions
Length 1620mm
Width 796mm
Height 1131mm
Weight 577kgs
Fuel
Fuel Type Diesel
Tank Capacity 62 litres
Fuel Consumption 4 litres / hour
Running Time 15.5hr
Sound Level dB(A) @ 7 meters
Standard Features
Low Fuel Protection
High Engine Temperature Protection
Low Oil Protection
Under/Over Frequency Monitoring
Under/Over Speed Monitoring
Battery Under/Over Volt Monitoring
Automatic Mains Failure activation
Key Start
Hinged Access Doors
Output Connection
230V 32A Socket and 2 16A Sockets
Neutral tied to generator chassis.
Protection
MCB and Earth Leakage RCD on 230V output for
fixed / long term installation use.
2.2 General Specification

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 13 Part No: 498-141 8kVA Diesel Generator 13 Part No: 498-141
3.1 General Precautions
The generator is fitted with a number of labels that alert the User to the safe operation and safety re-
quirements. A full explanation of these is contained here. If any of the labels are missing or unreadable
a duplicate should be obtained and fitted. All labels are quantity 1 unless otherwise indicated.
Label Location and Part No. Description
May be fitted near control panel
when supplied new.
Label Part No: 499-376/31
NO OIL IN ENGINE
This generator is occasionally
shipped without oil. Suitable oil
must be added before attempting
to start the generator.
This label should be removed
when oil is added.
On the service-side access door.
Label Part No: 499-376/10
CHECK ENGINE OIL LEVEL
DAILY
The oil level should be seen on
the oil dip stick as per the diagram
on the label.
On the service-side access door.
Label Part No: 499-376/03
DIESEL FUEL ONLY
This generator must only be filled
with commercial diesel fuel. If
special grades of diesel e.g. Bio-
Diesel are to be used consult HGI
first to discuss its suitability.
Next to air vents. Qty 2 off.
Label No: 499-376/04
INLET AND OUTLET VENTS TO
BE KEPT CLEAR
These must be kept free from
obstructions to allow a free flow of
cooling air or the engine and
alternator could over heat.
Next to exhaust outlet.
Label part No: 499-376/02
CAUTION HOT EXHAUST
The exhaust pipe is shielded as
much as is practical but the final
outlet is hot.
On side panel
Part of label No: 499-376/11
ELECTRICITY IS
DANGEROUS
If in doubt about the correct use
consult a qualified electrician or
contact our Technical Help Line.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 14 Part No: 498-141 8kVA Diesel Generator 14 Part No: 498-141
On side panel
Part of label No: 499-376/11
CHECK ENGINE OIL LEVEL
DAILY
Check the oil level each day and
top up if necessary to the top
mark given in the oil level diagram
above. If oil consumption is
excessive investigate further.
On side panel
Part of label No: 499-376/11
OPERATING THE GENERATOR
AT LOW LOADS LEVELS FOR
LONG PERIODS OF TIME MAY
CAUSE EXCESSIVE SMOKE
AND REDUCE EFFICIENCY
DUE TO CARBON BUILD UP.
If the generator is not required
switch it off and avoid running
with light or no load wherever
possible.
On side panel
Part of label No: 499-376/11
ENSURE GENERATOR IS AT
LEAST 1 METRE AWAY FROM
BUILDINGS, VEHICLES etc.
WHEN IN USE.
Ensure exhaust and air exit vents
are not restricted or obstructed.
On side panel
Part of label No: 499-376/11
OPERATE ONLY IN WELL
VENTILATED AREAS.
EXHAUST FUMES CAN KILL.
Generally the generator will be
installed in a Welfare Cabin or
similar in accordance with our
separate Installation Guide
available from HGI.
An exhaust extension is normally
supplied with each generator and
should be used to duct the
exhaust gas straight outside.
Sufficient air grilles for ventilation
should be provided. For such
applications consult the Technical
Help Line if in doubt.
Inside service door near
expansion bottle.
Label No: 499-376/34
HOT WATER UNDER
PRESSURE
CHECK WATER LEVEL DAILY
Coolant level must be sufficient to
appear in the filler neck.
DO NOT OPEN
A HOT RADIATOR

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 15 Part No: 498-141 8kVA Diesel Generator 15 Part No: 498-141
On side panel
Part of label No: 499-376/11
CHECK THE RADIATOR
COOLANT LEVEL AND
EXPANSION BOTTLE LEVEL
DAILY WHEN THE ENGINE IS
COLD. DO NOT REMOVE
PRESSURE CAPS FROM A HOT
ENGINE
Coolant level should reach the
bottom of the radiator filler neck and
should be between the level marks
on the expansion bottle.
Filling the expansion bottle does
NOT refill the cooling system
On side panel
Part of label No: 499-376/11
STOP ENGINE AND ALLOW TO
COOL DOWN FOR A FEW
MINUTES BEFORE REFUELLING.
In addition DO NOT SMOKE while
refuelling, use a funnel or similar to
prevent fuel spillage, avoid over
filling the fuel tank and wipe up any
spilt fuel. Avoid contact of fuel with
skin.
On side panel
Part of label No: 499-376/11
DO NOT SPILL FUEL ONTO HOT
SURFACES
The exhaust system in particular is
hot.
On side panel
Part of label No: 499-376/11
DO NOT ADJUST THE SPEED OF
THE ENGINE UNLESS YOU HAVE
BEEN TRAINED TO DO SO
If the generator is not producing
enough power for the application or
you suspect a problem do not adjust
the engine speed. This may
damage the engine, alternator and
any power equipment plugged into
the generator.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 16 Part No: 498-141 8kVA Diesel Generator 16 Part No: 498-141
On side panel
Part of label No: 499-376/11
KEEP CHILDREN AT A SAFE
DISTANCE FROM THE
EQUIPMENT AND DO NOT
ALLOW THEM TO OPERATE
IT
This is a mandatory Health and
Safety Requirement for this
equipment. A version with a key
switch is available if required.
On side panel
Part of label No: 499-376/11
DO NOT OPERATE WITH ANY
COVERS OPEN
If covers are open (or missing)
the generator may exceed the
European Noise Regulations
and the cooling of the engine
and alternator will be affected
which could cause damage to
them.
On side panel
Part of label No: 499-376/11
ONLY OPERATE ON A LEVEL
SURFACE
Generally the generator will only
be used on a level surface. It
can be used on small inclines
typically 5° maximum.
On control panel.
Label No: 499-376/08
EARTH POINT
If an earth leakage trip (RCD) or
centre tapped to earth alternator
is fitted an M10 brass earth stud
is supplied next to the output
sockets for the external earth
connection.
On the expansion bottle, inside the
main door.
Label No: 499-367/35
EXPANSION BOTTLE
Coolant level should reach the
bottom of the radiator filler neck
and should be between the level
marks on the expansion bottle.
Filling the expansion bottle does
NOT refill the cooling system

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 17 Part No: 498-141 8kVA Diesel Generator 17 Part No: 498-141
On side panel
Part of label No: 499-376/11
Information: In the UK it is
currently permissible to use
small mobile generators for short
periods without an external earth
connection being made. But
ONLY double insulated electrical
equipment can be powered by
the generator. All modern
electrical equipment intended for
out doors use should be double
insulated and marked with the
logo:
THIS GENERATOR SHOULD
ONLY BE USED TO POWER
DOUBLE INSULATED CLASS
II ELECTRICAL EQUIPMENT
UNLESS THE OPTIONAL
EARTH LEAKAGE TRIP (RCD)
IS FITTED.
When installed in a Welfare unit
or similar the main electrical
consumer unit will normally
house an RCD.
On side panel
Part of label No: 499-376/11
IF AN EARTH LEAKAGE TRIP
(RCD) IS FITTED THE
GENERATOR’S BRASS
EARTH STUD SHOULD BE
CONNECTED TO AN
EXTERNAL EARTH. THIS
EXTERNAL EARTH CAN BE
AN EARTH SPIKE OR ANY
SUITABLE EARTH POINT.
THE RCD SHOULD BE
TESTED DAILY BY PRESSING
THE TEST BUTTON AND
CHECKING IT DOES TRIP.
If the generator is to be used for
a fixed installation or installed on
the same site for a long period it
should be installed by a
competent person. The User
should be shown where the
TEST button is located and
shown how to use it. An earth
spike kit is available as an
optional extra
On lower RHS of the front
access panel/door
Label part No: 499-325/89
LWA 88 dB
This is the sound level. At this
level the generator should not be
operated in a small space
occupied by people.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 18 Part No: 498-141 8kVA Diesel Generator 18 Part No: 498-141
On the front of the base.
Part of label No: 499-376/06
DANGER ELECTRICITY
The battery is 12 V DC and care
should be taken not to come into
contact with the terminals.
On the front of the base.
Part of label No: 499-376/06
DANGER ACID
The battery contains acid and if any
liquid is seen check the source, but
assume first that it is acid. Care
should be taken in cleaning up acid.
See Section 3 Safety.
On the front of the base.
Part of label No: 499-376/06
WARNING EXPLOSIVE MATERIAL
The battery can under certain
conditions give off small quantities of
hydrogen gas. Do not smoke or use
naked flames while working on a
battery. NEVER attempt to burn a
battery as a method of disposal.
On the front of the base.
Part of label No: 499-376/06
DISCONNECT NEGATIVE LEAD
FIRST AND RECONNECT LAST
This is to ensure that if a spanner
slips you cannot create a circuit from
the live battery post to the generator
chassis.
On the front of the base.
Part of label No: 499-376/06
NO SMOKING OR NAKED LIGHTS
The battery can under certain
conditions give off small quantities of
hydrogen gas. Do not smoke or use
naked flames while working on a
battery.
On the front of the base.
Part of label No: 499-376/06
RECYCLE
The battery contains lead and
sulphuric acid and should be
recycled at an approved facility only
and not put into a dust bin.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 19 Part No: 498-141 8kVA Diesel Generator 19 Part No: 498-141
On control side access
panel
Label part No: 499-376/32
AUTOMATIC MACHINERY – MAY
START WITHOUT WARNING
This is only fitted if the generator is
an AMF (automatic mains failure)
version intended to start the set
automatically if the mains electricity
fails OR a Remote Start Version.
While checking the oil level or doing
any type of maintenance on this
generator it should be made safe
so it cannot start automatically by
removing the control fuse.
On control side access
panel
Label part No: 499-376/20
DANGER – MOVING MACHINERY
INSIDE DOOR
Moving parts will be present whilst
the machine is in operation. Stop
the machine and isolate before
removing the door/access panel.
On base – front RHS
Label No: 499-376/26
ENGINE OIL DRAIN
Engine oil is drained by removing
the cap on the front RHS of the
base. The oil will drain easier from
a warm engine. Observe correct
disposal practices.
On the front panel
Label No 499-376/33
LOW FUEL SHUTDOWN
The fuel gauge also incorporates a
low fuel shutdown facility. The set
will shut down when the level falls
to approximately 10-12% of its
capacity, thus eliminating the need
to bleed the system at restart.
On base near the fork
pods.
Qty 4 off.
Label No: 499-376/01
FORK LIFT POINT
The generator can be lifted from the
sides or from the front or rear using
a fork lift truck with correctly spaced
forks.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 20 Part No: 498-1418kVA Diesel Generator 20 Part No: 498-141
3.2 Electrical Safety
In addition to the information given previously the generator should be installed, earthed and used with
reference to the following available from HMSO:-
I.E.E Regulations 17th Edition (BS 7671:2004)
Health and Safety Executive Publications GS27 Protection Against Electric Shock
Health and Safety Executive Publications GS24 Electricity On Construction Sites
Health and Safety Executive Publications PM53 Emergency Private Generation
Alternatively the HGI Technical Help Line would be pleased to advise on the best measures for your
particular application.
The generator has been designed, wherever possible and practical, to shed rainwater and
condensation, and is paint protected to minimise the effects of rust.
Consideration should be made to the safe operation of the generator to further protect it in
extreme environments.
We would NOT recommend operating hand held electrical equipment in the rain.
DO NOT use a pressure washer to clean the generator as high pressure water may enter the electrical
system

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 21 Part No: 498-141 8kVA Diesel Generator 21 Part No: 498-141
3.4 Hazards to Health
A list of the hazards that may affect health are included with safety precautions and first aid instructions
Material /
Location
Hazard
First Aid Measures
Engine Oil
When hot may burn the skin but not
expected to give rise to an acute hazard
under normal conditions of use. May
cause an allergic skin reaction in sensitive
individuals. Continuous skin exposure
may give rise to dermatitis.
Gloves, overalls and eye protection
should be worn when handling this
product.
Do not burn old oil as a method of
disposal as combustion is likely to give
rise to a complex mixture of airborne
solids, liquid particulates and gases
including carbon monoxide and
unidentified organic and inorganic
compounds.
Old engine oil has potential health
implications and should not come into
contact with the skin.
A funnel is supplied with each generator
to make topping up with oil easy and
clean.
Burns: Rinse with clean water, cover with
a sterile pad and obtain medical
assistance.
Skin Contact: Remove contaminated
clothing and wash thoroughly with soap
and water. If persistent irritation occurs
obtain medical attention. If the material is
injected under high pressure into the body
obtain medical assistance immediately.
Inhalation: In the unlikely event of
inhalation of fumes if dizziness or nausea
occurs move the individual to fresh air. If
symptoms persist, obtain medical
attention. If difficulties are experienced
with breathing a qualified person should
administer oxygen. If breathing stops give
artificial respiration.
Eyes: In the unlikely event that the
material enters the eye flush with copious
quantities of clean water. If persistent
irritation occurs obtain medical attention.
Ingestion: In the unlikely event that
ingestion occurs, wash out the mouth with
water and seek medical attention. Do not
induce vomiting.
Diesel Fuel
May cause skin irritation.
Gloves, overalls and eye protection
should be worn when handling this
product.
As for engine oil above.
Fibre Glass
Insulation
(exhaust
parts ).
The User will not normally come into
contact with this material but Service
Technicians may.
May cause skin and respiratory tract
irritation.
Gloves, overalls, dust mask and eye
protection should be worn when handling
this product.
Skin Contact: Remove contaminated
clothing and wash thoroughly with soap
and water. If persistent irritation occurs
obtain medical attention.
Inhalation: In the unlikely event of
inhalation of dust or fibres if irritation of
the mouth and throat occurs rinse with
water. If persistent irritation occurs obtain
medical attention.
Eyes: In the unlikely event that the
material enters the eye flush with copious
quantities of clean water. If persistent
irritation occurs obtain medical attention.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 22 Part No: 498-141 8kVA Diesel Generator 22 Part No: 498-141
Other
insulation,
gaskets and
seals.
No specific hazards under normal use
conditions.
DO NOT burn as a method of disposal as
combustion is likely to give rise to a
complex mixture of airborne solids, liquid
particulates and gases including carbon
monoxide and unidentified organic and
inorganic compounds which may be
hazardous to health.
n/a
Asbestos
This generator is asbestos free. n/a
Battery Acid
Battery is
located in the
battery
compartment
at the front of
the
generator.
The User and Service Technicians will
not normally come into contact with acid
unless a battery has leaked for any
reason.
This is a concentrated sulphuric acid
solution and may cause skin burns.
Protective overalls, rubber gloves and
eye protection should be worn when
handling this product.
If spilt dilute and wash away with copious
quantities of water.
Skin Contact: Rinse skin and
contaminated clothing with copious
quantities of water. If persistent irritation
or blistering occurs obtain medical
attention. If the material is injected under
high pressure into the body obtain
medical assistance immediately.
Inhalation: In the unlikely event of
inhalation of fumes move the individual to
fresh air. Obtain medical attention
immediately. If difficulties are experienced
with breathing a qualified person should
administer oxygen. If breathing stops give
artificial respiration.
Eyes: In the unlikely event that the
material enters the eye flush with copious
quantities of clean water for at least 15
minutes. Place a sterile pad over the eye
and seek medical attention immediately in
all cases.
Ingestion: In the unlikely event that
ingestion occurs, wash out the mouth with
water. Do not induce vomiting. If the
patient is conscious give them water or
milk to drink. Obtain medical attention
immediately.
Exhaust
Fumes
Exhaust fumes are very hot and contain
carbon monoxide which can cause
unconsciousness and death in humans
and animals. It is odourless and tasteless
but diesel exhaust fumes contain other
chemicals and soot which will irritate the
eyes and breathing and will usually alert
the user to the presence of fumes.
Symptoms of carbon monoxide poisoning
are dizziness, nausea, fatigue and
vertigo.
Skin Contact: Rinse skin with water. If
persistent irritation or blistering occurs
obtain medical attention
Inhalation: In the event of inhalation of
fumes move the individual to fresh air. If
difficulties are experienced with breathing
a qualified person should administer
oxygen. If breathing stops give artificial
respiration. Obtain medical attention in all
cases.
Eyes: In the unlikely event that the fumes
enter the eye flush with copious quantities
of clean water for at least 15 minutes.
Place a sterile pad over the eye and seek
medical attention immediately in all cases.

Section 3 - Safety Harrington Generators International
8kVA Diesel Generator 23 Part No: 498-141 8kVA Diesel Generator 23 Part No: 498-141
Electric
Shock
Assess the situation first.
DO NOT touch the person until it is safe for you to do so.
Identify where the electricity is coming from. DO NOT assume it is the generator
Turn off the electricity at the source.
To stop generators in an emergency press the RED stop button on the generator
control panel or remove the plug from the socket. On Automatic Mains Failure
Units (AMF) press the emergency stop button on the main control panel.
If necessary check patients airways, administer artificial resuscitation, move the
person to the recovery position.
Even if the person remains conscious anticipate that they will pass into shock.
Local burns where contact was made should be covered by a sterile dressing.
Obtain medical attention immediately.
3.5 Electrocution
Table of contents
Other HGI Generators Portable Generator manuals
Popular Portable Generator manuals by other brands

Mosa
Mosa GE 40 YR-5-RENTAL Use and maintenance manual

Onan
Onan Emerald Plus BGE Series Operator's manual

Koshin America Corporation
Koshin America Corporation GEH-3100DX user manual

Sony
Sony AC-V60A Service manual

Predator
Predator Predator Generators 4000 Watt Portable... Owner's manual & safety instructions

Hyundai
Hyundai HY2200P owner's manual

Generac Power Systems
Generac Power Systems 04389-0 Installation and owner's manual

Generac Power Systems
Generac Power Systems GP7500E-5943-5 owner's manual

Bryant
Bryant ASPDA1BBL045 owner's manual

Thermo King
Thermo King TriPac 3 Operator's manual

Magnum
Magnum MMG25FHICAN6 operating manual

Taurus
Taurus BT-PG 2000/1 instruction manual