HID Mercury MR16in-S3 User manual

HID®Mercury™ MR16in-S3 Processor Installation and Specifications
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications
PLT-05250, A.1
August 2022

Copyright
© 2020 - 2022 HID Global Corporation/ASSA ABLOY AB. All rights reserved.
This document may not be reproduced, disseminated or republished in any form without the prior written permission of
HID Global Corporation.
Trademarks
HID GLOBAL, HID, the HID Brick logo, and HIDMercury are trademarks or registered trademarks of HID Global, ASSA
ABLOY AB, or its affiliate(s) in the US and other countries and may not be used without permission. All other trademarks,
service marks, and product or service names are trademarks or registered trademarks of their respective owners.
Contacts
For technical support, please visit: https://support.hidglobal.com.
What's new
Date Description Revision
August 2022 New branding. A.1
A complete list of revisions is available in Revision history.
PLT-05250, A.1 2 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

Section 01
Overview

1.1 MR16in processor
The MR16in processor provides a solution to the OEM system integrator for sensor monitoring and output control.
The MR16in has sixteen non-supervised/supervised inputs and two Form-C contact relays for load switching. In addition,
two digital inputs are used for cabinet tamper and power fault status monitoring.
The MR16in processor requires 12 to 24 V DC for power.
PLT-05250, A.1 4 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

Section 02
MR16in wiring and setup

2.1 Supplying power to the MR16in
The MR16in accepts 12 to 24V DC for power. Locate power source as close to the unit as possible.
Connect power with minimum of 18 AWG wire.
Observe POLARITY on VIN!
The VOUT terminal on TB11 is the same as VIN.
2.2 Communication wiring
The MR16in communicates with an intelligent controller (EP2500 for example) via a 2-wire RS-485 interface. The
interface allows multi-drop communication on a single bus of up to 4,000 feet (1,200 m). Shielded cable of 24 AWG with
characteristic impedance of 120Ω is specified for the RS-485 interface. See Specifications.
Install RS-485 termination jumper, J3, on the interface boards at each end of the communication line only.
2-wire RS-485
(only 2-wire RS-485 is supported)
PLT-05250, A.1 6 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

2.3 Alarm inputs wiring
Inputs 1 to 16 may be configured to use or not use End Of Line (EOL) resistors, and to use normally open or normally
closed contacts.
Input CT and input BA are used for monitoring cabinet tamper and power failure, respectively. These two inputs are for
contact closure monitoring only, and do not use EOL resistor(s).
Input configuration is set via host software.
PLT-05250, A.1 7 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

2.4 Relay outputs
Two Form-C contact relays are provided for controlling door strikes or other devices. Load switching can cause abnormal
contact wear and premature contact failure. Switching of inductive loads (strike) also causes EMI (electromagnetic
interference) which may interfere with normal operation of other equipment. To minimize premature contact failure and
to increase system reliability a contact protection circuit must be used. The following two circuits are recommended.
Locate the protection circuit as close to the load as possible (within 12 inches [30 cm]), as the effectiveness of the circuit
will decrease if it is located further away.
Use sufficiently large gauge of wire for the load current to avoid excessive voltage drop.
Diode selection
lDiode current rating > 1x strike current.
lDiode break down voltage: 4x strike voltage.
lFor 12 V DC or 24 V DC strike, diode 1N4002 (100V /1A) typical.
PLT-05250, A.1 8 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

2.5 DIP switch and jumper usage
lSwitches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate.
lSwitch 8 enables encrypted communication. All other configuration settings are set via host software.
S8 S7 S6 S5 S4 S3 S2 S1 Selection
OFF OFF OFF OFF OFF Address 0
OFF OFF OFF OFF ON Address 1
OFF OFF OFF ON OFF Address 2
OFF OFF OFF ON ON Address 3
OFF OFF ON OFF OFF Address 4
OFF OFF ON OFF ON Address 5
OFF OFF ON ON OFF Address 6
OFF OFF ON ON ON Address 7
OFF ON OFF OFF OFF Address 8
OFF ON OFF OFF ON Address 9
OFF ON OFF ON OFF Address 10
OFF ON OFF ON ON Address 11
OFF ON ON OFF OFF Address 12
OFF ON ON OFF ON Address 13
OFF ON ON ON OFF Address 14
OFF ON ON ON ON Address 15
ON OFF OFF OFF OFF Address 16
ON OFF OFF OFF ON Address 17
ON OFF OFF ON OFF Address 18
ON OFF OFF ON ON Address 19
ON OFF ON OFF OFF Address 20
ON OFF ON OFF ON Address 21
ON OFF ON ON OFF Address 22
ON OFF ON ON ON Address 23
ON ON OFF OFF OFF Address 24
ON ON OFF OFF ON Address 25
ON ON OFF ON OFF Address 26
ON ON OFF ON ON Address 27
ON ON ON OFF OFF Address 28
ON ON ON OFF ON Address 29
PLT-05250, A.1 9 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

S8 S7 S6 S5 S4 S3 S2 S1 Selection
ON ON ON ON OFF Address 30
ON ON ON ON ON Address 31
OFF OFF 115,200 BPS1
OFF ON 9,600 BPS
ON OFF 19,200 BPS
ON ON 38,400 BPS
OFF Encrypted communication not required2
ON Encrypted communication required2
1. Firmware revisions prior to 1.30.1, this setting is 2,400 BPS.
2. Firmware revisions prior to 1.30.1, S8 is not defined. Set to the OFF position.
2.5.1 Jumpers
Jumper Description
J3 RS-485 termination, install in first and last units only.
Note: All other jumpers are for factory use only.
PLT-05250, A.1 10 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

2.6 Status LEDs
2.6.1 Power-up
All LEDs are OFF.
2.6.2 Initialization
Once power is applied, initialization of the module begins.
When initialization is completed, LEDs 1 through 16, CT, BA, A and B are briefly sequenced ON then OFF.
2.6.3 Run time
After the above sequence, the LEDs have the following meanings:
LED Description
A LED
heartbeat and
on-line Status
Off-line: 1 sec rate, 20% ON
On-line: Non-encrypted communication: 1 sec rate, 80% ON
Encrypted communication: .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1
sec ON, .3 sec OFF
A LED Error indication: Waiting for application firmware to be downloaded: .1 sec ON, .1 sec OFF
B LED SIO communication port status: Indicates communication activity on the SIO
communication port.
1 LED Input status: 1
2 LED Input status: 2
3 LED Input status: 3
4 LED Input status: 4
5 LED Input status: 5
6 LED Input status: 6
7 LED Input status: 7
8 LED Input status: 8
9 LED Input status: 9
10 LED Input status: 10
11 LED Input status: 11
12 LED Input status: 12
13 LED Input status: 13
14 LED Input status: 14
15 LED Input status: 15
16 LED Input status: 16
CT Cabinet tamper
PLT-05250, A.1 11 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

BA Power fault
Input in the inactive state: OFF (briefly flashes ON every 3 seconds), Input in the active state: ON (briefly
flashes OFF every 3 seconds), Input in a fault state: Rapid Flash.
LED K1 and K2 Illuminates when output relay RLY 1 (K1) or RLY 2 (K2) is energized.
PLT-05250, A.1 12 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

Section 03
Specifications

Revision E assembly:
The processor is for use in low voltage, class 2 circuit only.
Primary power 12 to 24 V DC ± 10%, 350 mA maximum
Outputs Two Form-C relays
Normally open contact (NO) contact: 5 A @ 30 V DC resistive
Normally closed contact (NC) contact: 3 A @ 30 V DC resistive
Inputs 16 unsupervised/supervised, standard EOL: 1k/1kΩ, 1%, ¼ watt
2 unsupervised, dedicated for cabinet tamper and UPS fault monitoring
Communication RS-485, 2-wire. 9600, 19200, 38400, or 115200 bps
CABLE REQUIREMENTS
Power 18 AWG, 1 twisted pair
RS-485 24 AWG, 120Ω impedance, twisted pair with drain wire and shield, 4,000 feet
(1,200 m) maximum
Alarm inputs 1 twisted pair, 30Ω maximum
Outputs As required for the load
MECHANICAL
Dimension 6 inches (152 mm) W x 8 inches (203 mm) L x 1 inches (25.4 mm) H
Weight 9 oz. (250 g) nominal
ENVIRONMENTAL
Storage temperature -55°C to +85°C
Operating temperature 0°C to +70°C
Humidity 5% to 95% RHNC
UL294, 6th edition Performance Levels
Feature Level
Standby Power I
Endurance IV
Line Security I
Destructive Attack I
These specifications are subject to change without notice.
PLT-05250, A.1 14 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

3.1 Warranty
Mercury Security warrants the product is free from defects in material and workmanship under normal use and service
with proper maintenance for one year from the date of factory shipment. Mercury Security assumes no responsibility for
products damaged by improper handling or installation. This warranty is limited to the repair or replacement of the
defective unit.
There are no expressed warranties other than set forth herein. Mercury Security does not make, nor intends, nor does it
authorize any agent or representative to make any other warranties, or implied warranties, and expressly excludes and
disclaims all implied warranties of merchantability or fitness for a particular purpose.
Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer service, and
prepaid postage and insurance.
3.2 Liability
The Interface should only be used to control exits from areas where an alternative method for exit is available. This
product is not intended for, nor is rated for operation in life-critical control applications. Mercury Security is not liable
under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the
product. Mercury Security’s liability does not extend beyond the purchase price of the product.
3.3 Regulatory
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference
that may cause undesired operation.
PLT-05250, A.1 15 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications

Revision history
Date Description Revision
August 2022 New branding. A.1
October 2020 Initial release. A.0
PLT-05250, A.1 16 August 2022
Powering
Trusted Identities
HID®Mercury™ MR16in-S3 Processor
Installation and Specifications
Table of contents
Other HID Computer Hardware manuals