Hitecsa ACVIBA HE Series Instruction manual

ACVIBA HE
PACKAGED AIR-AIR –COMPACT VERTICAL INVERTER
Models: 35i │ 40i │ 45i │ 55i │ 70i │ 80i
Cooling capacities: from 7.3 kW to 82.3 kW
Heating capacities: from 6.5 kW to 70.2 kW
INSTALLATION, OPERATION & MAINTENANCE MANUAL
SOLO FRIO
IOM_ACVIBA HE_35ia80i_207910_190501_EN

ACVIBA HE
2
IOM_ACVIBA HE_35ia80i_207910_190501_EN
Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for air
conditioning and cooling installations for over 35 years. Our approach is based on efficiency, flexibility and on practical solutions. This
has been the hallmark of our product catalogue.
The versatility of our factory allows us to deliver solutions that can meet any requirement and we endeavour solving any problem that
may arise in designing and implementing air conditioning installations.
From all of us at Hiplus Aire Acondicionado, once again, thank you very much.

ACVIBA HE
3
IOM_ACVIBA HE_35ia80i_207910_190501_EN
INDEX
INTRODUCTION ................................................................................................................5
REGULATIONS AND CERTIFICATIONS ................................................................................6
SAFETY PRECAUTIONS ......................................................................................................7
TECHNICAL SPECIFICATIONS .............................................................................................9
DIMENSIONS...................................................................................................................11
ACVIBA HE 35I –40I........................................................................................................ 11
ACVIBA HE 45I –80I........................................................................................................ 11
REFRIGERATION DIAGRAM .............................................................................................12
ACVIBA HE 35I –40I........................................................................................................ 12
ACVIBA HE 45I –80I........................................................................................................ 13
TRANSPORT ....................................................................................................................14
INSPECTION AT RECEPTION............................................................................................ 14
WEIGHT DISTRIBUTION (KG) ........................................................................................... 14
RIGGING ......................................................................................................................... 15
STORAGE ........................................................................................................................ 16
INSTALLATION ................................................................................................................17
INSTALLATION SITE ........................................................................................................ 17
SERVICE AREA (MM) ........................................................................................................ 17
UNIT SETTLEMENT ......................................................................................................... 17
DRAINAGE ...................................................................................................................... 17
AIR DUCTS ...................................................................................................................... 18
ELECTRICAL INSTALLATION ............................................................................................ 19
ELECTRICAL SPECIFICATIONS .................................................................................... 19
ELECTRICAL CONNECTIONS ...................................................................................... 19
THERMOSTAT CONNECTION .................................................................................... 19
OPERATION ....................................................................................................................21
BEFORE START-UP .......................................................................................................... 21
START-UP ....................................................................................................................... 22
OPERATION LIMITS......................................................................................................... 23
Cooling Mode ........................................................................................................... 23
Heating Mode .......................................................................................................... 23

ACVIBA HE
4
IOM_ACVIBA HE_35ia80i_207910_190501_EN
TH TUNE CONTROLLER ................................................................................................... 24
Display:..................................................................................................................... 24
Start / Stop ............................................................................................................... 24
Setpoint Temperature Adjustment........................................................................... 24
Calibration of the Th-Tune internal temperature probe........................................... 24
Operation modes...................................................................................................... 24
Indoor Fan Modes: ................................................................................................... 24
Time schedule........................................................................................................... 25
Alarms ...................................................................................................................... 26
DIAGNOSIS OF THE ALARMS........................................................................................... 26
TH TUNE - Description of the alarm codes ............................................................... 26
EC MOTOR FANS................................................................................................................. 28
Diagnosis / Failure.................................................................................................... 28
MAINTENANCE ...............................................................................................................30
REFRIGERANT CHARGE................................................................................................... 30
COMPRESSOR LUBRICATION.......................................................................................... 30
CONSERVATION AND CLEANING .................................................................................... 31
REPAIRS.......................................................................................................................... 32
OPTIONS .........................................................................................................................33
APPENDIX: SAFETY DATA R410A .....................................................................................34

5
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
INTRODUCTION
Purpose of this Manual
The present manual together with any other technical document such as refrigeration or
hydraulic lines drawings, electrical diagrams among others have been issued to provide the
necessary information for the proper installation, start-up and maintenance of the unit. Therefore
it is essential to read the instructions very carefully.
Make sure that all the necessary information for the proper installation of the system is included
in the manuals supplied together with this unit and/or the rest of the indoor units, accessories,
etc. Otherwise the manufacturer declines any responsibility in case of people or animals injuries
or material damages, that may be entailed by an incorrect use of the unit and/or the non-
compliance with these instructions.
In case of different interpretations and/or errors, the priority order of validity of the given
documents will be: 1. Name plate of the unit stating the specifications. 2. IOM (the present
document), 3. EDM, technical catalogue, 4. UM user manuals.
Storage of the Manual
This manual and the electrical diagram of the unit must be preserved and remain available to the operator for any further
consultation.
Updating the Data
The continuous improvement in design and performance to which we are committed to gives us the right to modify the
specifications of our products without prior notice.
Electrical Supply
Check that the electrical network features comply with the data shown in the data nameplate of the unit.
Local Safety Regulations
Observe and analyse all possible causes of accidents that may arise in the place or places of installation of the units,
check means and tools to use, etc. It is not possible to consider every one of the potential circumstances of danger in this
manual. Respect the valid local security standards during installation.
Principles of Security on Installation
The unit has been designed and manufactured to avoid any risk for the health and safety of people. Appropriate solutions
for the project have been adopted to eliminate the possible causes of risk in the installation.
Packaging and Replacement of Equipment
The material of the packaging (plastic bags, insulating materials, nails, etc.) is a potential source of danger.
Therefore, it should be kept out of the reach of children and be recycled properly according to the valid
local safety regulations.
This product shall not be mixed with household waste at the end of its life. Due to the refrigerant, oil and
other components contained in this product, it must be dismantled by professional installers. Depending
on their specifications, all waste should be sent to recycling, composting or treatment plants, or to an
authorized waste management agent in accordance with the current local legislations.

6
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
INTRODUCTION
Utilization
The unit will be used only for the purpose it has been designed for. Any other use does not imply any kind of liability or
responsibility from the manufacturer.
Incorrect Operation
In case of breakdowns or operation faults, turn the unit off.
Periodic Inspections and Maintenance
Carry out periodic inspections to detect possible damaged or broken parts. If these parts are not repaired
it could cause people injuries or material damages. Cut off the power supply to the unit before carrying out
any maintenance operation.
Make sure to leave the maintenance areas open. If these areas have to be necessarily invaded by the
construction of air supply and/or lateral return ducts, verify that the design of the ducts allows the access
to the fans and the change of the filters or that these are accessible from the other side.
All operations should be carried out in accordance with local safety regulations.
Repairing Operations
The reparation operations shall always be carried out by trained personal exclusively and authorized by
the manufacturer using original spare parts. The safety devices of the unit could be damaged in case of
non-compliance with these warnings.
Modifications
The manufacturer will not respond possible warranty claims and to possible damages of theunit in case ofelectrical and/or
mechanical modifications. The unauthorized manipulation, reparation or modification of the unit will automatically
invalidate the warranty.
Refrigerant
This product is hermetically sealed and contains R-410A which is a HFC fluorinated greenhouse gas.
REGULATIONS AND CERTIFICATIONS
ISO 9001 CERTIFICATION: HIPLUS AIRE ACONDICIONADO S.L., by endeavouring to always gain the maximum
satisfaction from their customers, obtained the ISO 9001: Quality System for its production activity. That result shows our
continuous determination to improve quality and the reliability of all our products. Our commercial activities, design, raw
materials, production processes and after-sales service represent the means to reach our goal.
CE MARKING: Our products are CE marked according to the essential requirements of the applicable EC directives and
their last modifications and comply with the national legislation of each country.

7
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
SAFETY PRECAUTIONS
Before starting any installation, service or maintenance operation, turn the main power switch off in
order to avoid electrical shock that may cause personal damages.
In case of folding electrical panels, before folding them up in order to access to the interior of the machine, it is
MANDATORY to disconnect the power supply hose from the electrical voltage, THE LINE MUST ALWAYS BE
FREE OF VOLTAGE for this operation.
It is absolutely forbidden to carry out work on electrical live parts. The protection class of the opened unit is IP00!
Check the safe isolation from the supply using a two-pole voltage detector.
Do not touch or adjust the safety elements inside any unit. For repairs use only original spare parts and install them
properly in the same position of the replaced parts.
The installation and maintenance of air conditioning equipment may be dangerous due to the pressure of the
system, the high temperature of some of its parts and the electrical components.
Do not install the unit in an explosive atmosphere.
If the motor of the fan runs independently after the unit has been switched off because it is pushed by airflow,
dangerous voltage of more than 50 V may be present in some of the internal connections of the motor. In that case
the fan is working as a generator.
When there are EC motors or motors with variable speed control, the protective earthing is conducting high
discharge currents (depending on the switching frequency, the current source voltage and the motor capacity).
Earthing in compliance with EN specifications shall therefore be observed even for testing and trial operations (EN
50 178, Art. 5.2.11). Without earthing, dangerous voltages may be present in the motor housing.
Due to the use of capacitors, danger of death exists even after switching the device off in case of direct contact with
conductive parts or with parts that carry voltage due to fault conditions. To remove or to open the housing of the
controller and the terminal box for example is only allowed after the power supply cable has been disconnected for 3
minutes.
DANGER

8
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
SAFETY PRECAUTIONS
Only qualified and trained service staff (technical service) is authorized to carry out installation, commissioning and
maintenance. Unqualified personnel will carry out basic tasks only such as cleaning and replacement of filters, or
filter cleaning (excluding refrigerant filters), etc.
Prevent access to children so that they cannot play with the appliances.
For each visit, all precautions must be taken into account: those recommended in the installation, operation and
maintenance instructions, as well as the ones indicated in the stickers placed on the unit. Do not forget to strictly
follow any other legal safety precautions.
DO NOT introduce objects into the air inlets or outlets that can be drawn into the fan, people, etc.
The fan / motor may start and stop automatically due to functional reasons.
After a power failure or a main disconnection an automatic restart of the fan takes place when power supply returns!
Never approach the fan until it has stopped completely as it may be rotating even though it is not connected to the
power supply! Strong airflow could push it.
When the motor is provided with an external rotor, the rotor rotates during operation.
Use safety glasses, work gloves and any other safety accessory that may be necessary for the operation.
For brazing operations use a quenching cloth and make sure you have fire extinguisher close to you.
This product contains fluorinated greenhouse gases. In case of leakage air may be displaced which may cause lack
of oxygen when breathing.
The decomposition of fluorinated gases when being burned during brazing operations for example may cause the
presence of highly toxic and corrosive gases.
All the safety recommendations must be followed carefully.
ATTENTION!
The responsibility of all personal and material damages caused by an unplanned or inappropriate
use will be born by the person or the operating company of the unit and not by the manufacturer.
WARNING

9
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
TECHNICAL SPECIFICATIONS
MOSAIC HE RANGE
35i
40i
45i
55i
70i
80i
ACVIBA HE
CAPACITIES
Max. cooling capacity (120 Hz) (1)
kW
35.3
41.0
45.7
56.1
70.7
82.3
Total absorbed power input (120 Hz) (2)
kW
15.1
20.9
17.7
23.8
30.1
41.7
Min. cooling capacity (20 Hz) (1)
kW
7.3
9.6
2.4
5.8
7.3
9.6
EER (120 Hz)
-
2.35
1.96
2.59
2.36
2.35
1.98
Seasonal coefficient SEER (3)
%
4.68
4.13
4.44
4.41
4.65
4.09
Seasonal performance (ηs,c) (3)
-
184.3
162.3
174.6
173.4
183.1
160.5
Max. heating capacity (120 Hz) (4)
kW
30.3
35.3
41.2
48.8
60.7
70.2
Total absorbed power input (120 Hz) (2)
kW
10.2
12.9
12.6
16.2
20.4
25.7
COP (120 Hz)
2.97
2.74
3.26
3.01
2.97
2.73
Min. heating capacity (20Hz) (4)
kW
6.5
7.7
3.7
4.8
6.5
7.7
Seasonal coefficient SCOP (3)
3.33
3.21
3.38
3.21
3.37
3.23
Seasonal performance (ηs,h) (3)
%
130.1
125.3
132.2
126.2
131.7
126.4
REFRIGERATION CIRCUIT
Refrigerant type
R-410A
Number of circuits
1
2
Power stages
Variable
Global Warming Potential (GWP) (5)
2088
CIRCUIT 1
Compressor type
Scroll - BLDCM
Number of compressors
1
1
Oil type
PVE - FV50S
Oil volume
L
2.3
1.7
2.3
CIRCUIT 2
Compressor type
-
Scroll - BLDCM
Number of compressors
-
1
Oil type
-
PVE - FV50S
Oil volume
L
-
1.7
2.3
ELECTRICAL SPECIFICATIONS
Power supply
V / ~ / Hz
400 / 3+N /50
Max. operation current
A
33
49
55
68
66
99
(1). Calculated according to the UNE-EN-14511 standard, for indoor temperature conditions of 27ºC B.S. / 19ºC B.H. and 35ºC
outdoor temperature. Frequency of the compressor as stated above.
(2). Nominal consumption of the entire equipment (compressors and fans) in nominal conditions, calculated according to the EN-
14511 standard.
(3). The seasonal coefficient for the cooling season (SEER) or the heating season (SCOP) has been calculated according to the EN-
14825 standard.
The seasonal area cooling performance ratio (ηs,c) has been calculated according to the (EU) 2281 regulation.
(4). Nominal heating capacity calculated according to the UNE-EN-14511 standard for indoor temperature of 20ºC and outdoor
temperature of 7ºC B.S. / 6ºC BH. Frequency of the compressor as stated above.
(5). GWP: Global warming potential (climatic) of 1 kg of greenhouse gas for 1 kg of CO2, calculated over a period of 100 years.

10
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
TECHNICAL SPECIFICATIONS
MOSAIC HE RANGE
35i
40i
45i
55i
70i
80i
INDOOR FAN
Type
Plug fan EC
Total number
1
2
Nominal airflow
m³/ h
6,500
8,500
9,600
11,000
13,000
17,000
Available pressure according to standard (1)
Pa
150
200
Available static pressure (Nominal flow)
Pa
500
450
500
Available high pressure (2) (Max. flow)
Pa
1000
900
1000
OUTDOOR FAN
Type
Plug fan EC
Total number
1
2
Max. airflow
m³/ h
13,000
15,000
18,400
22,000
26,000
30,000
Available pressure according to standard (1)
Pa
60
Available static pressure (Max. flow)
Pa
Up to 60 Pa
Available high pressure (2) (Max. flow)
Pa
250
200
550
550
250
200
DIMENSIONS AND WEIGHT
Length
mm
1,423
2,800
Width
mm
854
Height
mm
2,491
Weight
kg
517
523
972
972
1007
1024
SOUND POWER LEVEL (Lw)
Exterior radiation Standard unit
dBA
86.5
90.8
74.6
85.3
89.2
93.7
Exterior radiation Unit running at 50% (4)
dBA
83.0
82.1
64.4
72.5
86.0
86.0
SOUND PRESSURE LEVEL at 5 m (3) (Lp)
Exterior radiation Standard unit
dBA
65.1
69.4
53.1
63.8
67.7
72.3
Exterior radiation Unit running at 50% (4)
dBA
61.5
60.6
43.0
51.1
64.6
64.6
(1) According to the EN 14511 standard.
(2) Option
(3) Directivity = 2 (in semi-sphere)
(4) The unit is running with the fan at the 2nd speed level with a partial charge of 50% of its capacity.

11
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
DIMENSIONS
ACVIBA HE 35i –40i
Units with 1 circuit
ACVIBA HE 45i –80i
Units with 2 circuits
1. Main switch
2. Electrical box
3. Drainage ¾”
4. Outdoor coil
5. Indoor coil
6. Electrical connection plug
Option
Standard

12
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
REFRIGERATION DIAGRAM
ACVIBA HE 35i –40i
Units with 1 circuit
1. Compressor
2. 4-way valve
3. Electronical expansion valve (EEV)
4. Check valve
5. Filter
6. Liquid container
9. Outdoor coil
10. Outdoor fan
11. Indoor coil
12. Indoor fan
HP. High pressure switch
PT. Pressure transductor
TD. Discharge temperature
TE. Outdoor air temperature
TI. Supply air temperature
TS. Temperature probe
VS. Security valve
OPTIONS:
8. Suction accumulator

13
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
REFRIGERATION DIAGRAM
ACVIBA HE 45i –80i
Units with 2 circuits
1. Compressor
2. 4-way valve
3. Electronical expansion valve (EEV)
4. Check valve
5. Filter
6. Liquid container
9. Outdoor coil
10. Outdoor fan
11. Indoor coil
12. Indoor fan
HP. High pressure switch
PT. Pressure transductor
TD. Discharge temperature
TE. Outdoor air temperature
TI. Supply air temperature
TS. Temperature probe
VS. Security valve
OPTIONS:
8. Suction accumulator

14
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
TRANSPORT
INSPECTION AT RECEPTION
It is advisable to examine the equipment carefully upon reception.
Check that the equipment has not been damaged during transport and that it is complete with all the parts
specified in the order and/or the options stated in the order. If this is not the case please contact the transport
company immediately (within 48h).
Verify the correct voltage of the nameplate and make sure it is in accordance with local power supply.
In case of any flaw or anomaly detected, please contact HITECSA.
WEIGHT DISTRIBUTION (kg)
35i
40i
1
129
130
2
135
137
3
129
131
4
124
125
TOTAL
517
523
45i
55i
70i
80i
1
233
233
244
250
2
238
238
248
254
3
253
253
260
262
4
248
248
255
258
TOTAL
972
972
1007
1024

15
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
TRANSPORT
RIGGING
Before moving the unit, make sure that all panels are fixed properly.
Raise and put the equipment down carefully.
Do not tilt the unit more than 15 degrees during transportation.
Always transport the unit in its original packaging to the place of installation.
All units come with a particular rigging diagram of that model similar to the one shown below. Be sure to hoist
the machine through the points indicated in the diagram.
Make sure that the unit is balanced, stable and without any deformations during lifting operations.
ACVIBA HE 35i –40i
ACVIBA HE 45i –80i

16
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
TRANSPORT
STORAGE
If the equipment is going to be stored before the installation, please follow the following instructions in order to avoid
damages, corrosion or deterioration:
Move it carefully.
Do not place the machine in places exposed to ambient temperatures above 50ºC and preferably keep the unit away
from direct sunlight.
The sun radiation may cause a very high temperature increase that can make the refrigerant pressure reachsuch high
levels that the security valves would be activated.
1. Moreover, when temperatures decrease water condensation may occur inside the machine or between the machine
and the plastic wrap.
Avoid placing objects on top of the unit (unless this is permitted according to the drawings or the overlap diagrams
indicated on the packaging, etc. Follow these indications).
In case of prolonged storage before installation avoid the penetration of water, dust and objects in general caused by
invasion or biological, meteorological and/or human impacts.
Minimum storage temperature: -10ºC.
2. If some components contain water, it is compulsory to empty them or to add an antifreeze solution to make sure that
the freezing point will always be lower than the ambient temperature.
Maximum relative humidity: 90%.
The warranty will not cover any damage caused frozen water.
WARNING

17
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
INSTALLATION
INSTALLATION SITE
Read and comply with the local rules and regulations applying to the installation of air conditioning systems.
Choose a clean place without dust nor debris.
Respect the allocated service area prepared for the equipment.
Verify that the ground or the structure prepared for the equipment is strong enough to support its weight during
operation.
Install shock absorbers throughout the installation to prevent the transmission of noise and vibration.
Check that the direction of the sound level will not annoy anybody.
The standard version of this equipment has been designed for installation inside a building (with a roof). It is not
prepared for installation outside. Please check with Hitecsa if you plan to expose the machine to weather conditions.
SERVICE AREA (mm)
UNIT SETTLEMENT
Make sure that the unit is slightly inclined (~2%) following the direction of the drains.
The bed frame shall be big enough and strong enough to support the unit weight.
DRAINAGE
All the drain devices are prepared with a male 3/4” gas connection (ISO 228-1, BSPP).
The unit is equipped as a standard feature with a condensate drain tray to avoid an excessive water accumulation in
the indoor side and the outdoor side.
The condensate drain pipe diameter shall be equal or larger than the unit connection depending on its length and
inclination.
If the drain line is exposed to air temperatures lower than 0 degree, it is necessary to cover it with thermal insulation
material or to use electrical heating devices to prevent water from freezing that would entail tube damage.
The drainage line shall be inclined by 2% minimum for proper water evacuation.
It is convenient to install a drain trap with proper dimensions (see diagram) or a
draining system with a condensate pump to avoid excessive water accumulation
in the indoor side and the outdoor side.
Recommended dimensions

18
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
INSTALLATION
AIR DUCTS
The air duct dimensions will be determined according to the air flow and the available static pressure of the units.
They shall be designed by qualified technicians. An incorrect design may reduce the unit’s performance and may be
a hindrance when access to the unit for maintenance operations is needed (in particular where there is only one
possible access).
Use ducts made of non-inflammable material in order to avoid any risk of fire as a consequence of the deflagration of
gases. It is advisable to use insulated metal ducts.
Use flexible conduits to connect air ducts to the unit so as to avoid vibration and noise transmission.
ACVIBA HE
35i
40i
45i
55i
70i
80i
AIR DUCTS –INDOOR SECTION
Supply ducts
Install 1
Install 1 or 2
Return ducts
Install 1
Install 1 or 2
AIR DUCTS –OUTDOOR SECTION
Supply ducts
Install 1
Install 1 or 2
Return ducts
Install 1
Install 1 or 2

19
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
IOM_ACVIBA HE_35ia80i_207910_190501_EN
INSTALLATION
ELECTRICAL INSTALLATION
ELECTRICAL SPECIFICATIONS
ACVIBA HE
35i
40i
45i
55i
70i
80i
MOSAIC HE RANGE
ELECTRICAL SPECIFICATIONS
Power supply
V / ~ /Hz
400V / 3 Phases + Neutral / 50 Hz.
Max. current
A
33
49
55
68
66
99
Starting current
A
38
54
55
68
76
109
The power supply of the unit shall correspond to the required power supply stated on the unit name plate.
The unit is equipped with frequency inverters. A 300mA differential switch or a superimmunized switch shall be installed
to avoid unprogrammed discharges.
ELECTRICAL CONNECTIONS
The unit power supply shall be within 10% of volts indicated on the unit nameplate. Damage caused by the start-up
of the unit with an incorrect voltage line will not be covered by the Hitecsa’s warranty.
Always refer to the unit wiring diagram when completing electrical connections.
The electrical wiring connections and the line protection devices must be installed by the installer according to the
current local laws that apply to the installation site.
The interconnecting wires shall be protected in a tube or an electrical cable conduit, cable tray, etc..
THERMOSTAT CONNECTION
The serial thermostat model is Th Tune. It is a user interface provided with a room temperature probe.
Connection of Th TUNE
2 wire power supply cable, 230 VAC (L+N)
Control cable, one twisted and shielded pair AWG 20/22 with a drain wire to
GND.
Keep a minimum distance of 15 cm between the control/communication cable
and the 230V power supply cable outside the unit.
Before proceeding to any operation disconnect the unit from the power supply.
WARNING
1. 5 wire supply 400V/3/50Hz (Three-phase + Neutral + Earth)
2. Control cable, twisted and shielded AWG20/22 with drain wire to GND
3. 2 wire power cable 230V 50/60Hz (Phase + Neutral)
The power supply can be either external or coming from the unit.
4. Th Tune remote control (Do not mix the power cables with the control
cables).
5. Time delay fuses or circuit breakers curve D.
6. Main switch of the installation.
7. Cable outlets (The position may vary depending on the model)
8. Main switch of the unit (The position may vary depending on the model)

20
IOM_ACVIBA HE_35ia80i_207910_190501_EN
ACVIBA HE
AIR-AIR PACKAGED UNITS
COMPACT VERTICAL INVERTER
INSTALLATION
Connection of the Th TUNE in units with 1 circuit
Connected to the main controller
Connection of the Th TUNE in units with 2 circuits
Connected to the secondary control board, serial feature with the main controller (Master).
CONNECTION OF THE PGD1 or the Mini PGD controllers (options)
Always connected to the main controller.
CONNECTION of the wall probe (option)
The remote room probe is a NTC thermal resistance placed within a box and connected with 2
copper wires of 0.5mm² to 1,5mm² thickness (the longer the distance is the thicker the wire will
be).
(Refer to the electrical diagram).
This manual suits for next models
6
Table of contents
Popular Inverter manuals by other brands

Solectria Renewables
Solectria Renewables PVI 3800TL Installation and operation manual

enphase
enphase ENV-S-WM230 Installation and operation manual

Giacomini
Giacomini R586S-0 instructions

SUNGOLD POWER
SUNGOLD POWER Hybrid BluePower TP6048 user manual

jeri
jeri V4 user manual

Tsun
Tsun TSOL-Easy Solar Kit 400-U user manual