System Display and Operational LED Light Indicators
The display allows the user to change system parameters and
monitor system outputs.
Gas Valve
Senses suction from the blower, allowing gas to ow only if powered
and combustion air is owing.
Integrated Venturi
Controls air and gas ow into the burner.
Burner
The high grade stainless steel burner uses premixed air and gas to
provide a wide range of ring rates.
Burner Sensor
Continually monitors the temperature of the burner to provide
increased safety. Temperatures outside the allowable range will shut
down the boiler before an unsafe condition occurs.
Spark Ignition
The burner is ignited by applying high voltage through the system
spark electrode. The spark from the electrode ignites mixed gas o
of the burner.
Dual Supply Water Temperature Sensor / High Limit Water ECO
This dual sensor monitors the boiler outlet water temperature
(System Supply). The control adjusts boiler ring rate so the supply
temperature will match the boiler set point. The dual sensor meets
all requirements to function as a safety, eliminating the mechanical
ECO and increasing safety and reliability.
Return Water Temperature Sensor
This sensor monitors boiler return water temperature (System
Return).
Temperature and Pressure Gauge
Allows the user to monitor system temperature and pressure.
Electrical eld connections with terminal strips
The electrical cover allows easy access to the clearly marked line
voltage and low voltage terminal strips to facilitate wiring the boiler.
Supplied Condensate Collection System (Field Installed)
This boiler is a high eciency appliance and will produce condensate.
The condensate collection system has a oat switch which monitors
condensate level and prevents condensate from backing up into
the combustion system. Inside the collection system is a built in trap
which seals the combustion system from the connected drain. This
condensate should be neutralized to avoid damage to the drainage
system or piping.
Flow Protection
The optional ow switch is designed to protect the boiler during low
ow conditions. The boiler control also monitors ow through the
heat exchanger by monitoring the return and supply sensors and
will shut down the burner before overheating occurs.
Outdoor Sensor
The control adjusts unit set point based on the outdoor temperature
measured by this sensor to provide greater eciency.
0-10 Volt Input
Allows the installer to connect a BMS (Building Management
System) to control the boiler.
0-10 Volt Output A (Congured through Control System)
0-10 Volt Output A is congured through the boiler’s control system.
0-10 Volt Output A is related to one of the following boiler values:
boiler power, cascade power, fan speed, alarm status, or temperature
setting based on outdoor reset curve.
UL 353 Internal Low Water Cuto (LWCO)
The supplied internal Low Water Cuto meets UL 353 requirements
to function as a safety, locking out the boiler when water level is
inadequate for safe operation. To test LWCO function, press and hold
v and RESET simultaneously for ve (5) seconds. Press RESET to clear
the error code.
Boost Timer Function
This function temporarily overrides the outdoor reset curve in order
to satisfy a thermostat setpoint in a short amount of time, especially
during a relatively warm day.
Flue Temperature Modulation
As an additional safety feature, if the ue temperature exceeds
200oF, the control will modulate the boiler down based on the
vent temperature, rather than the supply temperature. If the ue
temperature exceeds 210oF the control will lock out the boiler.
System Sensor (Optional)
This sensor is designed to be used in a cascade system. The system pipe
sensor measures the temperature of return water and communicates
with the control system to modulate the ring rate of the connected
boilers.
NOTE: When using a system sensor, pipe insulation must be wrapped
around it to improve temperature measurement accuracy and increase
overall system eciency.
External Low Water Cuto (Optional)
Connection points are provided on the Field Connection Board to
install an external LWCO if required by local codes.
Indirect Tank Sensor (Optional)
Monitors storage tank temperature.
C. Optional Equipment
Optional equipment available from HTP (and Part #):
• System Sensor (7250P-324)
• Indirect Tank Sensor (7250P-325)
• High and Low Gas Pressure Switch Kit with Manual Reset
(6300P-991)
• 6” Stainless Steel Outside Termination Vent Kit (V3000)
• Flow Switch Kit (6300P-990)
• Manual Reset High Temperature Limit (6300P-998)
• Alarm System Kit (to monitor any failure) (7350P-602)
• 928 PC Connection Kit with Software (7450P-330)
• Condensate Neutralizer (7350P-611)
Part 3 - Prepare the Boiler
Remove all sides of the shipping crate to allow the boiler to be moved
into its installation location.The boiler is heavy. At least two individuals
are needed to properly handle the boiler. The boiler is also equipped
with leveling mechanisms on its casters that can be used to level the
boiler properly on an uneven location surface. If surface ooring is
rough, take care when moving the boiler into position, as catching the
casters could damage the boiler.
COLD WEATHER HANDLING - If the boiler has been stored in a very
cold location (BELOW 0oF) before installation, handle with care until
the components come to room temperature. Failure to do so could
result in damage to the boiler.
Carefully consider installation when determining boiler location.
Please read the entire manual before attempting installation. Failure
to properly take factors such as boiler venting, piping, condensate
removal, and wiring into account before installation could result in
wasted time, money, and possible property damage and personal
injury.
This boiler is certied for indoor use only. DO NOT INSTALL
OUTDOORS. Outdoor installations ARE NOT covered by warranty.
Failure to install the boiler indoors could result in property damage,
severe personal injury, or death.
A. Locating the Boiler
Incorrect ambient conditions can lead to damage to the heating
system and put safe operation at risk. Ensure that the installation
location adheres to the information included in this manual. Failure
to do so could result in property damage, serious personal injury,
or death. Failure of boiler or components due to incorrect operating
conditions IS NOT covered by product warranty.