Hydro Instruments VM-150 User manual

VM-150 Rev.8/18/2023
VM-1 5 0 VA C U U M M O N I TO R
I N S T R U C T I O N M A N UA L

2
TABLE OF CONTENTS
SECTION I: Introduction ...............................................................................................................3
SECTION II: Inventory...................................................................................................................3
SECTION III: Specifications ...........................................................................................................3
SECTION IV: Operation Basics......................................................................................................4
A: Digital Display ..............................................................................................................4
B: LED Indicators ..............................................................................................................5
C: Alarm Relays ................................................................................................................5
SECTION V: Installation ................................................................................................................6
A: Opening Unit................................................................................................................6
B: Enclosure Mounting.....................................................................................................6
C: Vacuum Line.................................................................................................................7
D: Power and Alarm Wiring .............................................................................................7
SECTION VI: Set Up and Calibration.............................................................................................8
A: Alarms..........................................................................................................................8
B: Analog Output..............................................................................................................9
C: Maintenance and Calibration ......................................................................................9
SECTION VII: Limited Warranty....................................................................................................10
FIGURE 1: Installation Wiring Diagram........................................................................................11
FIGURE 2: Enclosure Mounting....................................................................................................12
FIGURE 3: Sensor Enclosure Dimensions.....................................................................................13
FIGURE 4: VM-150 Dimensions....................................................................................................14

3
SECTION I: INTRODUCTION
The Series VM-150 is a full featured vacuum monitoring system. The system uses the latest in
integrated circuit technology, which allows a compact design, accuracy and reliability. The
Series VM-150 features both high and low vacuum detection, separate high, low and latch
alarm relays, three digit display of vacuum in inches of Hg, LED status indicators and an analog
output. The high and low alarm levels are user adjustable along with a variable delay timer.
The enclosure has a NEMA 4X rating; therefore, it can be mounted outside. Applications
include water treatment and waste water treatment.
SECTION II: INVENTORY
The following items are included with the Series VM-150:
1. VM-150 controller housed in a NEMA 4X enclosure.
2. Sensor enclosure with oil based protection device.
3. Two (2) liquid tight fittings used for running the power and alarm wires to/from
the controller.
4. ¼” tube fitting attached to the oil based protection device.
5. Power Cord
6. Instruction Manual
7. Warning label attached to the oil based protection device.
SECTION III: SPECIFICATIONS
Input voltage
115V, 60 Hz at 0.1 Amps
230V, 50 Hz at 0.1 Amps
Alarm relays: NO\NC Type
240V AC at 5 Amps Resistive
115V AC at 5 Amps General Use
30V DC at 5 Amps General Use
Gas/Fluid Compatibility: System includes a protection device that uses chemically inert
synthetic oil compatible with chlorine. Other options are available.

4
Enclosure: NEMA 4X rated
Vacuum Measurement range: 0 to 30 in. Hg.
Low Alarm range: 0 to 15 in. Hg.
High Alarm range: 15 to 30 in. Hg.
Over Pressure: 85 PSI
Delay Timer: 1 to 100 seconds
Analog Output
Voltage: 0 to 3 VDC
Current: 0 to 3 mA DC
Reset Switch: IP 65 protection
External connectors: IP 68 protection
Indicators
Vacuum: 3 digit digital LED display
Alarms: 3 LED indicators –High, Low and Latch
Polarity: 1 LED
Temperature range (system)
Storage: -30 C to 70 C
Operating: -20 C to 50 C
Vacuum Temperature Range:-40 C to 50 C
Humidity Relative: 0 to 90% noncondensing
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
SECTION IV: OPERATION BASICS
A. DIGITAL DISPLAY
The three digit display represents the real time vacuum pressure in inches of Hg.

5
Minimum vacuum equals 00.0 and the maximum vacuum reading, depending on altitude, is
approximately 30.9 inches.
B. LED INDICATORS
The Series VM-150 has three LED indicators; High Alarm, Low Alarm, Latch Alarm and
Polarity. See Figure 1 for their location.
HIGH ALARM LED INDICATOR
This LED indicates that the vacuum pressure is exceeding the preset “high alarm” set point.
NOTE: This indicator is real time. It does not wait for the delay timer to time out.
LOW ALARM LED INDICATOR
This LED indicates that the vacuum pressure is below the preset “low alarm” set point.
NOTE: This indicator is real time. It does not wait for the delay timer to time out.
LATCH LED INDICATOR
When either the high or low indicators are active, this starts the delay timer. If the alarm is
active longer that the preset delay time, then the latch LED indicator will become active.
This indicator stays active until the manual reset button (See Figure 2) is pushed. This
indicator implies that either an alarm had occurred or is still active. If the latch indicator is
on and the High/Low indicators are off, then an alarm condition has occurred, but is not
active now. If either the High or Low indicators are active, then this represents that the
alarm condition is still active.
NOTE: The High or Low alarm relays do not become active until the latch alarm indicator is
on.
POLARITY LED INDICATOR
When this LED is on this indicates that the VM-150 is measuring pressure. The digital
display shows this pressure in inches of Hg.
C. ALARM RELAYS
The Series VM-150 has three alarm relay outputs. The alarm relays do not become active
until the delay timer times out, which cause the latch alarm indicator to become active. The
three alarm relays are general purpose and can be used for exterior alarms, load switching
or phone monitoring.

6
HIGH ALARM RELAY
The High Alarm relay becomes active from a high alarm condition after the delay timer
times out. This relay stays active as long as the alarm condition exists. Once the alarm
condition goes away, this relay becomes inactive.
LOW ALARM RELAY
The Low Alarm relay becomes active for a low alarm condition after the delay timer times
out. This relay stays active as long as the alarm condition exists. Once the alarm condition
goes away, this relay becomes inactive.
LATCH ALARM RELAY
When either the High or Low Alarm relays become active or the delay time is over, the latch
alarm relay also becomes active. This is indicated by the Latch Alarm indicator. This relay
stays active until the manual reset button is pushed. (See Figure 2)
NOTE: In some applications, like gas chlorination in water and waste water treatment,
special attention needs to be given to the electrical hookup. If your vacuum source under
normal operation is cycled on and off, as is the case when the vacuum is created only when
a well pump is operating, then the AC power to the Series VM-150 should be switched on
and off with the well pump. This will prevent a low alarm condition when the pump is off.
SECTION V: INSTALLATION
Installation should only be performed by trained personnel. Follow any local, state or other
applicable codes that apply when installing this unit.
NOTE: This unit should be wired to a ground fault receptacle.
CAUTION: HIGH VOLTAGE COULD EXIST INSIDE THIS UNIT. DISCONNECT ALL POWER BEFORE
INSTALLATION.
A. OPENING UNIT
Remove the four (4) plastic screws to open the unit. The printed circuit board contains
static sensitive parts, so the installer should wear a grounding strap when handling the
board.
B. ENCLOSURE MOUNTING
IMPORTANT: This unit contains two enclosures. The larger one contains the electronics
(VM-150) and the smaller one contains the sensor. The two enclosures are permanently

7
connected together by a low voltage wire. The sensor enclosure contains an oil based
protection device that is filled with a special fluid. The protection device has a cap over the
¼” fitting to prevent the oil from leaking out during shipping and installation.
THE SENSOR ENCLOSURE MUST BE MOUNTED IN AN UPRIGHT POSITION TO PREVENT THE
FLUID FROM LEAKING OUT.
Once the unit is securely mounted in an upright position, the cap over the ¼” fitting can be
removed.
The recommended mounting method for the VM-150 is to use the four (4) mounting holes
located where the four (4) plastic screws are that hold down the lid. Use the box as a
template for mounting. (See Figure 2)
NOTE: The Series VM-150 should not be mounted where sunlight can directly enter the
cover.
The printed circuit board is designed to have power come in from the bottom of the box.
Remove the knockouts that are needed for power entry. Two (2) liquid tight fittings are
provided for the power and alarm line. If the board must be removed to install a water
tight fitting, care must be taken in handling the board.
NOTE: If you run conduit into the box and do not use the water tight fitting, you must use a
seal around the conduit connection.
Install the printed circuit board after the connectors have been installed. Use the four (4)
#6 screws provided to mount the board in the box and tighten only to a snug fit. Do not
over tighten. (See Figure 2)
C. VACUUM LINE
Connect your ¼” ID vacuum line to the ¼” barb fitting attached to the sensor enclosure.
D. POWER AND ALARM WIRING
CAUTION: BE SURE POWER IS DISCONNECTED BEFORE HANDLING ANY WIRES.
WARNING: IMPROPER WIRING TO THIS UNIT CAN DAMAGE IT AND COULD CAUSE SERIOUS
BODILY INJURIES. OVERPRESSURE ON THIS UNIT IS RATED AT 50 PSI. EXCEEDING THIS
PRESSURE CAN CAUSE A RUPTURE OF THE SENSOR.

8
See Figure 1 for typical electrical wiring. Connect AC power to the connector location
labeled HOT, NEU and GND.
NOTE: A surge suppressor is recommended on the AC power line to prevent damage from
lighting strikes or other power surges. The alarms can be hooked up in many ways. Be sure
the relay specifications are not exceeded. The relay outputs are labeled HIGH ALARM, LOW
ALARM and LATCH ALARM. Remember the latch alarm will stay active until the reset button
is pushed.
NO = Normally open contact
NC = Normally closed contact
COM = Common
SECTION VI: SET UP AND CALIBRATION
The Series VM-150 comes preset at the following default levels.
Delay: 50 seconds
Low Alarm: 5 inches Hg.
High Alarm: 25 inches Hg.
The following is a procedure for changing these values. See Figure 1 for the location of the
adjustment pots.
CAUTION: HIGH VOLTAGE EXISTS INSIDE THE UNIT.
A. ALARMS
DELAY TIMER ADJUSTMENTS
The delay time is adjustable from approximately 1 second to 100 seconds. To adjust the
delay, insert a small screwdriver into pot R24, and rotate until the desired delay is achieved.
The delay value is printed on the board.
LOW LEVEL ALARM
The low level alarm is adjustable from approximately 0.0 to 15 inches of Hg. To adjust the
low level, insert a screwdriver into pot R19 and rotate it to the desired level. MIN = 0 and
MAX = 15 inches of Hg.
NOTE: If you want to disable the low alarm, turn the pot counter clockwise until it stops.
HIGH LEVEL ALARM

9
The high level alarm is adjustable from approximately 15 to 30 inches of Hg. To adjust the
high level, insert a screwdriver into pot R16 and rotate it to the desired level. MIN = 15
inches of Hg. and MAX = 30 inches of Hg.
NOTE: If you want to disable the high alarm, turn the pot clockwise until it stops.
B. ANALOG OUTPUT
The VM-150 has an analog output, which will allow the vacuum to be remotely monitored.
The connection for this is located in the upper left section of the printed circuit board (See
Figure 1). They are labeled GND for ground and OUT for the output. The output is capable
of sourcing 0 to 3 VDC or 0 to 3 mA. If a 4 to 20 mA loop is required, a signal conditioner
can be used to convert the output.
C. MAINTENANCE AND CALIBRATION
Once the Series VM-150 has been in operation for approximately one week, the unit should
be checked for the correct zero reading. This is the reading when no vacuum is present.
Ideally, the zero reading would be 00.0. However, due to the ambient temperature, some
variation is normal. If the zero reading is over 00.7 then an adjustment is needed. The zero
adjustment pots are located in the upper right hand corner of the board. One of the pots, if
looked at from the middle of the board, is rotated all the way to the right and the other pot
is rotated around the 12:00 position. The pot that is close to the 12:00 position is the pot to
adjust. Slowly turn this pot to get the zero calibration. If the reading still does not read 00.0
then slowly adjust the other pot until a reading of 00.0 is set.
NOTE: At least one of the pots must always be rotated all the way to the right.
Once a month the system should be functionally tested, this testing should include all
relays, LED indicators, delay timer and vacuum level accuracy. To perform these tests adjust
your vacuum level up and down to cause the high and low alarms to engage. The delay
timer and reset can also be tested in the same manner. At this time, inspect the board for
any corrosion or loose wires. If corrosion is present check all fittings for a snug fit.
Corrosion can only be removed by a trained technician. The outside of the enclosure can be
cleaned with warm water and a damp cloth.
CAUTION: DO NOT ATTEMPT TO CLEAN ANY CORROSION FROM THE BOARD. HIGH
VOLTAGE EXISTS ON THE BOARD.

10
SECTION VII: LIMITED WARRANTY
Hydro Instruments warrants this product to be free from defects in material and workmanship
for a period of one (1) year from the date of purchase.
Except as specified below, this warranty covers all defects in material and/or workmanship in
this product. The following are NOT covered by the warranty:
1. Any product, on which the serial number has been defaced, modified or removed.
2. Damage, deterioration or malfunction resulting from:
•Accident, misuse, abuse, neglect, fire, water, lightning or any other acts of Nature.
•Any unauthorized product modification or failure to follow instructions supplied
with the product.
•Repair or attempted repair by anyone not authorized by Hydro Instruments.
•Shipment of the product.
•Any other cause which does not relate to a product defect.
EXCLUSION OF DAMAGES
Hydro Instruments’ liability for any defective product is limited only to the repair or
replacement of the product at our option. Hydro Instruments shall not be liable for:
•Damage to other property caused by any defects in this product, damages based
upon inconvenience, loss of use of the product, loss of time.
•Any other damages, whether incidental, consequential or otherwise.

11
FIGURE 1
Installation Wiring Diagram

12
FIGURE 2
Enclosure Mounting

13
FIGURE 3
Sensor Enclosure Dimensions

14
FIGURE 4
VM-150 Dimensions
Table of contents
Other Hydro Instruments Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

HD Electric
HD Electric CDM-50 Operating and instruction manual

LINSHANG
LINSHANG LS108A instruction manual

Keysight
Keysight U1211A User's and service guide

Tektronix
Tektronix KEITHLEY 8606 instruction sheet

Leica
Leica Lino L2P5 Quick start up guide

PCB Piezotronics
PCB Piezotronics 356A70 Installation and operating manual