manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ideal commercial
  6. •
  7. Boiler
  8. •
  9. ideal commercial Evomax 30 User manual

ideal commercial Evomax 30 User manual

INSTALLATION AND
SERVICING
EVOMAX
30 40 60 80 100 120 150
30P 40P 60P 80P
When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal.
For the very latest copy of literature for specification and maintenance practices visit our website www.idealcommercialboilers.com
where you can download the relevant information in PDF format.
June 2018
UIN 206210 A17
2EVOMAX - Installation & Servicing
MODEL
SYMBOL UNITS 30 30P 40 40P 60 60P
Condensing Boiler n/a n/a yes yes yes yes yes yes
Low Temperature Boiler n/a n/a no no no no no no
B1 Boiler n/a n/a no no no no no no
Cogeneration Space Heater n/a n/a no no no no no no
Equipped with a Supplementary Heater n/a n/a no no no no no no
Combination Heater n/a n/a no no no no no no
Nominal Heat Output for Space Heating
Full Load P4kW 30 30 40 40 60 60
Part Load P1kW 9.7 9.7 13 13 19.5 19.5
Auxiliary Electricity Consumption
Full Load elmax kW 0.134 0.134 0.135 0.135 0.092 0.092
Part Load elmin kW 0.03 0.03 0.03 0.03 0.026 0.026
Standby PSB kW 0.006 0.006 0.006 0.006 0.006 0.006
Seasonal Space Heating Energy Efciency
Full Load ƞ4% 89.6 91.6 89.6 91.5 89.7 91.7
Part Load ƞ1% 98.4 99.6 97.8 99.5 97.9 99.7
Standby Loss Pstby kW 0.08 0.08 0.08 0.08 0.11 0.11
Ignition Pign kW000000
Emissions NOxmg/kWh 28 71 35 72 28 73
Annual Energy Consumption QHE GJ 93.0 91.9 123.9 122.6 185.8 181.9
Sound Power Level, Indoors LWA dB 53 53 53 53 52 52
ERP DATA
 
3
EVOMAX - Installation & Servicing
EVOMAX HEAT BOILER
Ideal Boilers
ERP DATA
SYMBOL UNITS MODEL
30 30P 40 40P 60 60P
Condensing boiler Yes
Seasonal Space heating efciency class A
Rated heat output kW 30 30 40 40 60 60
Seasonal space heating energy efciency ƞs% 93* 93* 93* 93* 93* 93*
Annual energy consumption QHE GJ 92.9 91.9 123.9 122.6 185.8 181.9
Sound power level, indoors LWA dB 53 53 53 53 52 52
Seasonal Space Heating Energy Efciency of the Boiler *%
Temperature control (from che of temperature control) %
Class I Class II Class III Class IV Class V Class VI Class VII Class VIII
1% 2% 1.5% 2% 3% 4% 3.5% 5%
PRODUCT FICHE
 
The energy efciency of the package of products provided for in this document may not correspond to its actual energy efciency once installed in a
building, as the efciency is inuenced by further factors such as heat loss in the products in relation to the building size and its characteristics
Collector Size
(in m2)Tank Volume
(in m3)Collector
Efciency
(in %)
Tank rating
A* = 0.95
A = 0.91
B = 0.86
C = 0.83
D-G = 0.81
Solar Contribution (from che of solar device)
Seasonal Space Heating Energy Efciency of Package TOTAL: A+B+C=
Seasonal Space Heating Energy Efciency Class of Package
= (‘III ’x + ‘IV ’ x ) x 0.9 x ( / 100 x = %
%
GG F E D C B A A+ A++ A+++
< 30% ≥ 30% ≥ 34% ≥ 36% ≥ 75% ≥ 82% ≥ 90% ≥ 98% ≥ 125% ≥ 150%
A
B
C
4EVOMAX - Installation & Servicing
5
EVOMAX - Installation & Servicing
6EVOMAX - Installation & Servicing
GENERAL
Note.
Natural gas consumption is calculated using a caloric value of
37.8MJ/m3 (1038Btu/ft3) gross or 34 MJ/m3 (910 Btu/ft3) nett at
15oC and 1013.25 mbar.
a. For l/s divide the gross heat input (kW) by the gross C.V. of the
gas (MJ/m3)
b. For ft/h3 divide the gross heat input (Btu/h) by the gross C.V. of
the gas (Btu/ft3).
c. For m3/h multiply l/s by 3.6.
d. 1kW = 3412 BTU/hr.
e. 1m3 = 35.3ft3
f. 1mg/kWh (NOx) = 0.568 ppm DAF (natural gas).
Propane gas consumption is calculated using a caloric value of
95.7 MJ/m3 (2500 Btu/ft.3) gross or 88.0 MJ/m3 (2300 Btu/ft.3) net
at 15oC and 1013.25 mbar.
To obtain the fuel consumption in liquid form divide the above
gures by 270.
* The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy ratings of dwellings. The test data from which
it has been calculated have been certied by a notied body.
Table 2 General Data
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer’s
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT. These appliances are CE certied for safety
and performance. It is, therefore, important that no external
control devices, e.g. ue dampers, economisers etc., are
directly connected to these appliances unless covered by
these Installation and Servicing Instructions or as otherwise
recommended by Ideal Boilers in writing. If in doubt please
enquire.
Any direct connection of a control device not approved by Ideal
Boilers could invalidate the certication and the normal appliance
warranty. It could also infringe the Gas Safety Regulations and
the above regulations.
Evomax Model 30 30P 40 40P 60 60P 80 80P 100 120 150
Boiler Output
(non-
condensing)
Mean 70°C
Max kW 30 30 40 40 60 60 80 80 100 120 150
Min kW 6 6 8 8 12 15 16 20 20 24 30
Boiler Output
(condensing)
Mean 40°C
Max kW 31.54 30.9 42.0 41.2 63.5 62.1 84.4 82.6 103.9 124.7 158.0
Min kW 6.5 6.4 8.5 8.3 12.7 15.5 17.2 21.2 21.6 26.0 32.5
Boiler Input
Max Rate
Nett kW 30.4 30.4 40.5 40.5 60.8 60.7 82.0 81.9 102.4 122.9 153.7
Gross kW 33.7 33 44.9 44 67.4 66 90.9 88.9 113.6 136.4 170.5
Boiler Input
Min Rate
Nett kW 6.1 6.1 8.1 8.1 12.2 15.2 16.4 20.5 20.5 24.6 30.7
Gross kW 6.7 6.6 9.0 8.8 13.5 16.5 18.2 22.2 22.7 27.3 34.1
Gas Rate Max Rate m3/hr 3.2 1.26 4.3 1.69 6.4 2.53 8.7 3.41 10.8 13.0 16.2
Flue Gas
Flow Rate Max Rate m3/hr 47.6 46.5 63.4 62.1 95.1 93.1 128.3 125.4 160.3 192.5 240.7
CO2 (±0.5%) * Max Rate % 9.7 11.4 9.7 11.4 9.7 11.4 9.7 11.4 9.7 9.7 9.7
Min Rate % 8.7 10.2 8.7 10.2 8.7 10.5 8.7 10.5 8.7 8.7 8.7
NOxweighted mg/kWh 31.0 79 39.1 80 32.3 83.8 39.8 68 39.6 38.8 38.1
Efciency Seasonal % 96.7 97.2 96.2 96.7 96.4 96.9 97.2 97.7 96.7 96.6 96.7
*SEDBUK 2009 % 89.6 90.6 89.3 90.3 89.4 90.5 n/a n/a n/a n/a n/a
*CO2 measurements taken using controlled reference natural gas. Readings on mains gas quality may vary
Evomax Model 30 30P 40 40P 60 60P 80 80P 100 120 150
Gas Supply 2H – G20 – 20mbar / 3P - G31 - 37mbar
Gas Supply Connection G 3/4
Flow Connection G1 1/4
Return Connection G1 1/4
Max Pressure (sealed sys) Bar (psi) 6.0 (87)
Maximum Static Head m61.0
Electricity Supply 230V - 50Hz
Fuse Rating A4.0
Power Consumption W126 207 131 265 370 403 400
IP Rating IP20
Nominal ue dia - Concent. 80/125 100/150
Condensate Drain 25
Water Content L3.0 5.0 7.0 9.2
Dry Weight Kg 49 60.30 75.70 89.75
Table 1 Performance Data (Natural Gas)
7
EVOMAX - Installation & Servicing
GENERAL
CONTENTS
Boiler Assembly - Exploded view..................................15
Boiler Clearances............................................................12
Commissioning and Testing...........................................44
Electrical Connections....................................................29
Electrical Supply..............................................................11
Fault Finding....................................................................55
Flue Installation.................................................................9
Flue Kits...........................................................................19
Gas Safety Regulations ...................................................8
Gas Supply.........................................................................9
Hydraulic Resistance......................................................10
Introduction........................................................................8
Initial Lighting..................................................................45
Installer Connections......................................................30
Installation........................................................................15
Mounting Boiler...............................................................18
Option Kits.........................................................................8
Performance Data..............................................................6
Servicing..........................................................................47
Short List of Parts...........................................................65
Ventilation........................................................................18
Water Circulation.............................................................10
Water Connections..........................................................28
Water System Requirements..........................................13
Water Treatment..............................................................11
Wiring Diagrams..............................................................31
Key to symbols
IE = Ireland, GB = United Kingdom (Countries of destination)
PMS = Maximum operating pressure of water
C13 C33 = A room sealed appliance designed for
connection via ducts to a horizontal or vertical
terminal, which admits fresh air to the burner
and discharges the products of combustion
to the outside through orices which, in this
case, are concentric. The fan is up stream
of the combustion chamber. Note: Evomax
Room Sealed Flues must be used.
B23 = An appliance intended to be connected
to a ue which evacuates the products
of combustion to the outside of the room
containing the boiler. The combustion air is
drawn directly from the room. The fan is up
stream of the combustion chamber.
Note: Evomax Air Inlet Kit must be used.
II2H3P = An appliance designed for use on 2nd and 3rd
Family gases.
EVOMAX
30, 40, 60, 80, 100, 120, & 150
30P, 40P, 60P & 80P
Natural Gas & LPG
Destination Countries: GB, IE
Boiler size G.C. Appliance No.
(Benchmark No.)
30 41-750-33A
40 41-750-34A
60 41-750-35A
80 41-750-36A
100 41-750-37A
120 41-750-38A
150 41-750-39A
30P 41-750-40
40P 41-750-41
60P 41-750-42
80P 41-750-43
NOTE TO THE INSTALLER:
LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER.
8EVOMAX - Installation & Servicing
GENERAL
INTRODUCTION
The EVOMAX boilers are fully automatically controlled, wall
mounted, fanned, super efcient condensing appliances.
The EVOMAX condensing boilers can be installed either on the
wall or into a prefabricated oor mounted frame.
The boilers are suitable for use with a room sealed ue or open
ue application.
Through a sophisticated control system combined with premix
burner arrangement the boilers are capable of high seasonal
efciencies of >96% and low emissions.
These boilers are certied to meet the requirements of the EC
Gas Appliance Directive, Boiler Efciency Directive, EMC and Low
Voltage Directive.
Note. These boilers cannot be used on systems that include
gravity circulation.
The boiler are suitable for connection to fully pumped, open vented
or sealed water systems. Adequate arrangements for completely
draining the system by provision of drain cocks MUST be provided
in the installation pipework.
OPTIONAL EXTRA KITS
• External Vertical Terminal Extension Kit 80/125
• External Vertical Terminal Extension Kit 100/150
• Vertical Roof Flue Kit 80/125
• Vertical Roof Flue Kit 100/150
•Horizontal Wall Flue Kit 80/125
• Horizontal Wall Flue Kit 100/150
•Open Flue Kit 80
•Open Flue Kit 100
•Cascade Flue Kit
•Pitched and Flat Roof Tiles
•Frame and Header Kits
• Pump Kits
•Programmable Room Thermostat Kit
•Modulating Sequencer Kit
• Sequencer 6 Zone Expansion Kit
•Outside Sensor Kit
•Tank Sensor Kit
• Room Sensor Kit
• Safety Interlock Kit
• Plume Kit
• Propane to Natural Gas Conversion Kit
Please note propane variants of the Evomax are Cat II2H3P (20/37) and
may be converted to natural gas operation only using the approved
conversion kit supplied by Ideal.
Natural gas variants of the Evomax are Cat I2H and cannot be
converted to propane operation.
SAFETY
Current Gas Safety (Installation and Use) Regulations
or rules in force
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force.
In GB, the installation must be carried out by a Gas Safe
Registered Engineer or in IE by a competent person. It must be
carried out in accordance with the relevant requirements of the:
•Gas Safety (Installation and Use) Regulations
•The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
•The Water Fittings Regulations or Water byelaws in Scotland.
•The Current I.E.E. Wiring Regulations.
Where no specic instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a Competent Person
and installed in accordance with the current edition of I.S.813
“Domestic Gas Installations” or I.S. 820 “Non-Domestic Gas
Installations” as appropriate, the current Building Regulations and
reference should be made to the current ETCI rules for electrical
installation.
The Evomax boilers have been tested and certied to;
EN 483, EN 677, PREN 15420, BSEN 15417, BSEN 656, BSEN
60335-2-102, BSEN 55014-1 and BSEN 55014-2 for use with
Natural Gas & LPG.
Detailed recommendations are contained in the following Codes of
Practice:
BS. 6891
Installation of low pressure gas pipework of up to
28mm (R1) in domestic premises (2nd family gas).
BS. 5482 Pt. 1 Domestic butane and propane gas burning
installations.
BS. 5440
Inst. and maintenance of ues and ventilation for gas
appliances of rated input not exceeding 70kW net
(1st, 2nd and 3rd family gases).
Part 1 Specication for installation of ues.
Part 2 Specication for installation and maintenance of
ventilation for gas appliances.
BS. 6644 : 2005 Installation of gas red hot water boilers of rated
inputs between 70kW and 1.8MW (net) (2nd and
3rd family gases).
BS. 6798
Installation and maintenance of gas red hot water
boilers of rated input not exceeding 70kW net.
BS. 6880 Low temperature hot water heating systems of
output greater than 45kW.
Part 1 Fundamental and design considerations.
Part 2 Selection of equipment.
Part 3 Installation, commissioning and maintenance.
BSEN.12828:2003
Heating Systems in buildings: Design for water
based systems.
BSEN.12831:2003
Heating Systems in buildings: Method for
calculation of the design heat load.
BSEN.13831 Specication for: Expansion vessels using an
internal diaphragm, for sealed hot water heating
systems.
BSEN.14336:2004
Heating Systems in buildings: Installation and
commissioning of water based heating systems.
IGEM/UP/1 Soundness testing and purging of industrial and
commercial gas installation.
IGEM/UP/2 Gas installation pipework, boosters and
compressors on industrial and commercial
premises.
IGEM/UP/10 Installation of gas appliances in industrial and
commercial premises.
Where reference is made throughout these instructions I.S.813:2002
“Domestic Gas Installations” reference should also be made to
I.S.820:2000 “Non-Domestic Gas Installations” as applicable.
SAFE HANDLING
This boiler may require 2 or more operatives to move it to its installation
site, remove it from its packaging base and during movement into its
installation location. Manoeuvring the boiler may include the use of a
sack truck and involve lifting, pushing and pulling.
Caution should be exercised during these operations.
Operatives should be knowledgeable in handling techniques when
performing these tasks and the following precautions should be
considered:
9
EVOMAX - Installation & Servicing
GENERAL
• Grip the boiler at the base.
• Be physically capable.
• Use personal protective equipment as appropriate, e.g.
gloves, safety footwear.
During all manoeuvres and handling actions, every attempt should
be made to ensure the following unless unavoidable and/or the
weight is light.
• Keep back straight.
• Avoid twisting at the waist.
• Avoid upper body/top heavy bending.
• Always grip with the palm of the hand.
• Use designated hand holds.
• Keep load as close to the body as possible.
• Always use assistance if required.
SAFE HANDLING OF SUBSTANCES
No asbestos, mercury or CFCs are included in any part of the
boiler or its manufacture.
LOCATION OF BOILER
The boiler must be installed on a at and vertical wall, capable of
adequately supporting the weight of the boiler and any ancillary
equipment or on a boiler frame supplied in kit form by Ideal
Boilers.
The boiler must not be tted outside.
GAS SUPPLY
The local gas supplier should be consulted, at the installation
planning stage, in order to establish the availability of an adequate
supply of gas. An existing service pipe must NOT be used without
prior consultation with the local gas supplier.
A gas meter can only be connected by the local gas supplier or by
a Gas Safe Registered Engineer or in IE by an RGI engineer.
An existing meter should be checked, preferably by the gas
supplier, to ensure that the meter is adequate to deal with the
rate of gas supply required. A minimum working gas pressure of
17.5mbar MUST be available at the boiler inlet for Natural gas
and 37mbar for Propane.
Do not use pipes of smaller size than the boiler inlet gas
connection.
The complete installation MUST be tested for gas soundness and
purged in accordance with the appropriate standards listed on
page 8.
FLUE INSTALLATION
DANGER; ONLY USE IDEAL ROOM SEALED FLUE
GAS SYSTEMS. THE BOILER CE MARK IS VALID
ONLY IF THE APPLIANCE
IS OPERATED WITH IDEAL
ROOM SEALED FLUE KITS. OTHER FLUE SYSTEMS
ARE NOT TESTED WITH THIS APPLIANCE.
The ue kits are suitable for use with the EVOMAX boiler only.
These kits and the associated options are suitable for both roof
and wall mounting applications. The Horizontal Wall Flue Kit
is not for use with Evomax 150 boilers in compliance with the
requirements of the Clean Air Act Memorandom.
The roof ue kits are suitable for both at and pitched roof
termination, using either concentric or ue only terminals.
Connection to the top of the boiler is made using a separately
supplied vertical connector in concentric and open ue
congurations (supplied in our optional extra kits).
Additional information covering the selection and installation can
be found with this booklet.
Weather Proong
Where the ue passes through the roof line an adequate seal
must be made. This can be achieved by using either:
•Flat weather collar
•Pitched weather collar
Flue duct extension kits are available for concentric ue
conguration. These packs contain additional 1 metre ducts and
may be cut to the desired length.
Flue duct extension kits are available for open ue congurations.
These packs contain 2 x 1 metre ducts and may be cut to the
desired length.
If obstructions prevent direct ue routing then both 90oand 45o
elbows can be provided to offset the ue system.
Terminal Position
Due to the high efciency of the boilers pluming will occur. For
this reason, vertical termination is recommended, and in any
case, terminal positions which could cause problems should
where possible be avoided. Particular care should be taken in the
case of large multiple boiler installations, and complying with the
requirements of the Clean Air Act.
IMPORTANT
It is the responsibility of the installer to ensure, in practice, that
products of combustion discharging from the terminal cannot
re-enter the building or any other adjacent building through
ventilators, windows, doors, other sources of natural air inltration,
or forced ventilation / air conditioning.
If this should occur the appliance MUST be turned OFF, labelled
as ‘unsafe’ and corrective action taken.
Where the lowest part of the terminal is tted less than 2m (80”)
above a balcony, above ground or above a at roof to which
people have access then the terminal MUST be protected by a
purpose designed guard. The minimum spacing between the
balcony and the terminal should be 75mm, in order to allow a
terminal guard to be tted.
Terminal guards are available from boiler suppliers - for all
requirements contact:
Grasslin (UK) Ltd., Tower House, Vale Rise,
Tonbridge, Kent TN9 1TB.
Tel: +44 (0) 1732 359 888. Fax: +44 (0) 1732 354 445
www.tfc-group.co.uk
Ensure that the guard is tted centrally.
The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1”) to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS. 5440-1: 2008. In IE refer to
I.S.813:2002.
The ue must be installed in accordance with Building
Regulations and the recommendations of BS. 5440-1:2008 for
inputs up to 70kW nett. For larger installation BS. 6644 should be
complied with. In IE refer to I.S.820:2000.
!
DANGER; ONLY USE OPEN FLUE GAS SYSTEMS
WHERE THE EVOMAX AIR INLET KIT IS USED. THE
BOILER CE MARK IS VALID ONLY IF THE APPLIANCE
IS OPERATED WITH THE IDEAL AIR INLET KIT.
!
10 EVOMAX - Installation & Servicing
GENERAL
WATER CIRCULATION SYSTEM
The system pump MUST be connected to the boiler, see below.
The boiler must NOT be used for direct hot water supply. The hot
water storage cylinder MUST be of the indirect type.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated underoor spaces.
The boiler must be vented.
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 1/2” BSP
nominal size and be in accordance with BS. 2879.
The central heating system should be in accordance with the
relevant standards listed on page 8.
Due to the compact nature of the boiler the heat stored within the
castings at the point of shutdown of the burner must be dissipated
into the water circuit in order to avoid overheating. In order to
allow pump operation after burner shutdown the boiler control box
incorporates a 4 minute pump overrun facility. In order to make use
of this, the pump must be supplied from the terminals inside the
boiler. Note: for pumps requiring a current greater than 1.3 amps
inductive, they must be connected via a relay.
When sizing pumps, reference should be made to the table below
which show the boiler resistance against ow rates, to achieve the
required temperature differential.
Flow rates for common systems using either 11ºC, 15ºC or 20ºC
temperature differentials and hydraulic resistances are given in
the table below.
Flowrate (l/min) Hydraulic Resist-
ance (mbar)
11ºC 15ºC 20ºC 11ºC 15ºC 20ºC
Evomax 30/30P 39.1 28.7 21.5 425 225 127
Evomax 40/40P 52.1 38.2 28.7 875 405 225
Evomax 60/60P 78.2 57.3 43.0 435 180 83
Evomax 80/80P 104.2 76.4 57.3 750 420 180
Evomax 100 * 95.6 71.7 * 315 134
Evomax 120 * * 86.0 * * 218
Evomax 150 * * 107.5 * * 230
* Not recommended due to excessive owrates which may cause
erosion of the casting.
Note.
• With the boiler ring at maximum rate, the temperature
differential should not be less than gures quoted in table
above. High ow rates required for lower temperature
differentials could lead to errosion of the heat exchanger water
ways.
• With the boiler ring at minimum rate, the temperature
differential should not be greater than 35oC. Lower ow rates
generating higher temperature differentials will lead to lock out
of the boiler.
• The lower the return temperature to the boiler, the higher the
efciency.
In installations where all radiators have been provided with
thermostatic radiator valves, it is essential that water circulation
through the boiler is guaranteed. This can be best achieved
by means of a differential pressure valve, which is installed in a
bypass between the ow and return pipes. The bypass should
be tted at least 6m from the boiler, and should use a minimum
size of 28mm pipe. The bypass should be capable of allowing
a minimum ow rate to achieve a temperature differential of no
greater than 35oC at minimum rate.
11
EVOMAX - Installation & Servicing
GENERAL
WATER TREATMENT
These boilers incorporate an ALUMINIUM heat exchanger.
IMPORTANT. The application of any other treatment to this
product may render the guarantee of Ideal Boilers INVALID.
Ideal Boilers recommend Water Treatment in accordance with
Guidance Notes on Water Treatment in Central Heating Systems.
If water treatment is used Ideal Boilers recommend only the
use of SCALEMASTER SM-1 PRO, FERNOX, MBI, ADEY MC1,
SENTINEL X100 or CALMAG CM100 inhibitors and associated water
treatment products, which must be used in accordance with the
manufacturers’ instructions.
In hard water areas where mains water can exceed 200ppm
Total Hardness (as dened by BS 7593:2006 Table 2) a scale
reducing device should be tted into the boiler cold supply within
the requirements of the local water company. The use of articially
softened water, however, is not permitted.
Ideal Boilers recommend the use of Fernox Quantomat, Sentinel
Combiguard,Calmag CalPhos I scale reducing devices or
Scalemaster In-line Scale Inhibitor branded Ideal, which must be
used in accordance with the manufacturers’ instructions.
Notes.
1. It is most important that the correct concentration of the water
treatment products is maintained in accordance with the
manufacturers’ instructions.
2. If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
3. In hard water areas, treatment to prevent lime scale may be
necessary - however the use of articially softened water is
NOT permitted.
4. Under no circumstances should the boiler be red before the
system has been thoroughly ushed.
For further information contact:
Fernox Alent Plc
Forsyth Road, Sheerwater, Woking, Surrey GU21 5RZ
+44 (0) 8706 015000
Sentinel Performance Solutions
7560 Daresbury Park, Daresbury,
Warrington, Cheshire WA4 4BS
Tel: 0800 389 4670
Scalemaster Water Treatment Products
Emerald Way, Stone, Staffordshire ST15 0SR
Tel: +44 (0) 1785 811636
Calmag Ltd.
Riverview Buildings, Bradford Road, Riddlesden, Keighley,
West Yorkshire BD20 5JH
Tel: +44 (0) 1535 210320
Adey Professional Heating Solutions
Gloucester Road, Cheltenham GL51 8NR
Tel: +44 (0) 1242 546700
ELECTRICAL SUPPLY
Wiring external to the appliance MUST be in accordance with
the current I.E.E. (BS7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made to
the current ETCI rules for electrical installations
The point of connection to the mains should be readily accessible
and adjacent to the boiler.
CONDENSATE DRAIN
Refer to Frames 22, 23 & 58
A condensate drain is provided on the boiler. This drain must be
connected to a drainage point on site. All pipework and ttings in
the condensate drainage system MUST be made of plastic - no
other materials may be used.
IMPORTANT.
Installation must be in accordance with BS 6798.
The drain outlet on the boiler is sized for standard 21.5mm (3/4”)
overow pipe. It is a universal tting to allow use of different
brands of pipework.
12 EVOMAX - Installation & Servicing
GENERAL
1
BOILER CLEARANCES AND CONNECTIONS
The following minimum clearances must be maintained for operation and servicing.
Front of boiler - 450mm
Sides of boiler - 25mm
Above boiler - dependent upon the ue system see drawings
Below boiler - 300mm
Clearance between multiple boiler installations - 25mm
80/125 Concentric Flue Connector
EVOMAX 30, 40, 60 & 80
Minimum boiler top clearances:
for vertical ue 200mm
for horizontal ue 350mm (415mm for 100/150)
for open ue 350mm
100/150 Concentric Flue Connector
EVOMAX 100, 120 & 150
Minimum boiler top clearances:
for vertical ue 200mm
for horizontal ue 370mm
for open ue 350mm
Flue centre
line
im9245
X=224.5 (80/125)
X=289.5 (100/150)*
* with 100/150 adaptor
(See Frame 13)
Flue centre
line
X=232
RF 2544
500
‘C’
‘B’
‘A’
850
59 59
15581 68
Gas
Flow Return
299
Gas Pipe
Flow/Return
Condensate Drain
Flue Centre Line
Flue Centre Line
206210-10155
500
‘C’ ‘B’
‘A’
850
59 59 15581 68
Gas
Flow Return
299
Gas Pipe
Flow/Return
Condensate Drain
Flue Centre Line
Flue Centre Line
206210-10155
Boiler Dim. A Dim. B Dim. C
30, 40, 60, 80 360 130 118
100, 120 520 226 118
150 610 233 120
Flue centre
line
183mm
128mm
Flue centre
line
153mm
185mm
OPEN FLUE KIT 80 OPEN FLUE KIT 100
13
EVOMAX - Installation & Servicing
GENERAL
Feed/expansion
cistern 500mm
minimum
3000mm
minimum
System
flow to
pump
Inverted cold
feed entry
Cold
Feed
Water
level
(cold)
Open vent
System
return
Connections
to boiler
ima5351
3000
minimum
2
OPEN VENTED SYSTEM REQUIREMENTS
Detail reference should be made to the appropriate standards listed on page 8.
The information and guidance given below is not intended to override any requirements of the above publications or the
requirements of the local authority, gas or water undertakings.
The vertical distance between the pump and feed/expansion cistern MUST comply with the pump manufacturer’s minimum
requirements, to avoid cavitation. Should these conditions not apply either lower the pump position or raise the cistern above the
minimum requirement specied by Ideal Boilers. The isolation valves should be tted as close to the pump as possible.
The boiler is tted with an automatic air vent, located in the left top side of the interior. This air vent must never be shut off, as this
could result in dry ring of the boiler and subsequent damage to the heat exchanger.
14 EVOMAX - Installation & Servicing
GENERAL
CV CV
Resillient
seat control
valves
Supply
pipe
DT
CV = Control Valve
DT = Drain Tap
Air
gap Tundish
Strainer
Type BA backflow
prevention device
(RP2 valve assembly)
primary flow
and return
ima7349
3
SEALED SYSTEM REQUIREMENTS
Note. The method of lling, relling, topping up or ushing sealed primary hot water circuit from the mains for a non-domestic
property is shown below.
1. General
a. Detail reference should be made to the appropriate
standards listed on page 8. The information and
guidance given below is not intended to override any
requirements of these publications or the requirements of
the local authority, gas or water undertakings.
b. The installation should be capable of working with ow
temperatures of up to 90oC and a temperature differential
of up to 20oC.
c. All components of the system, including the heat
exchanger of the indirect cylinder, must be suitable for a
working pressure of 6 bar (87lbf/in2) and temperature of
110oC. Care should be taken in making all connections
so that the risk of leakage is minimised.
d. The boiler is tted with an automatic air vent, located in
the left top side of the interior. This air vent must never
be shut off, as this could result in dry ring of the boiler
and subsequent damage to the heat exchanger.
2. Safety Valve
A spring loaded safety valve complying with the relevant
requirements of BS. 6759 Pt. 1 must be tted in the
ow pipe as close to the boiler as possible and with no
intervening valve or restriction. The valve should have the
following features:
a. A non-adjustable preset lift pressure not exceeding 6 bar
(87lbf/in2).
b. A manual testing device.
c. Provision for connection of a discharge pipe. The valve
or discharge pipe should be positioned so that the
discharge of water or steam is visible, but will not cause
hazard to user or plant.
3. Pressure Gauge
A pressure gauge covering at least the range 0-6 bar must
be tted to the system. The gauge should be easily seen
from the lling point and should preferably be connected at
the same point as the expansion vessel.
IMPORTANT NOTE: If the boilers are installed on to an
Ideal frame & header kit and operated in excess of 3 bar
then all safety relief valves will require upgrading. The
Evomax has a maximum operating pressure of 6 bar.
4. Expansion Vessel
Expansion vessels used must comply with BS. EN 13831.
Connection to the system must not incorporate an isolating
valve.
15
EVOMAX - Installation & Servicing
INSTALLATION
4
BOILER ASSEMBLY - Exploded View
INSTALLATION
206210-10387
308
502
309
304
306
105
302
305
208 232
230 231
310
301
501
Evomax 80 shown
KEY
105 Auto Air Vent
208 Burner Fixings Kit
230 Fan
231 Gas Valve Kit
232 Venturi 30kW Kit
301 Dry Fire Thermistor Kit
302 Lead Ignition Kit
304 Ignitor Unit
305 Electrode Detection Kit
306 Ignition Electrode Kit
308 Fascia Plastic
309 HMI Board
310 Primary PCB
501 Jacket Assembly Evomax Kit
502 Door Assembly Evomax Kit
16 EVOMAX - Installation & Servicing
INSTALLATION
6
UNPACKING
5
PACKAGING REMOVAL
The boiler is supplied fully assembled in one pack. When
unpacking the boiler check the contents against the list
shown. Do not dispose of the packaging until all contents
are accounted for, as some parts are held within the
cardboard packing pieces.
•The boiler should be laying on its back with the straps
removed.
•Carefully read the installation instructions before proceeding.
•Remove the outer packing sleeve.
•Remove the protective cardboard wall mounting template
from the front of the boiler.
•Remove the packing piece from the top of the boiler.
•Check the contents against the list in Frame 6 ‘Unpacking’.
Note: some items are contained within the top packing
piece.
•The boiler may now be stood on its base, with the
cardboard bottom packing piece still in place to protect the
connections. Due care should be taken when standing up
the boilers, with respect to their weights, see Table 2 on
page 6.
INSTALLATION
B
A
C
D
F
E
G
H
J
Pack Contents
A Fully assembled boiler
BInstallation & Servicing/User Instructions
CLog Book
DWall mounting bracket
EWall mounting template
FCondensate Trap
GM10 x 70 Hex Head Coach Screws - 6 off
HM10 Wall Plug - 6 off
JGas cock
17
EVOMAX - Installation & Servicing
INSTALLATION
8
PREPARING THE WALL
7
WALL MOUNTING TEMPLATE
Note. The template shows the positions for the
top xing holes. Care must be taken to ensure
the correct holes are drilled.
1. Tape template into the selected position.
2. Ensure squareness by hanging a plumbline.
3. Mark on to the wall:
a. The top 4 wall mounting plate screw
positions.
b. The 2 boiler lower xing positions using
diagram below
c. The position of the ue duct. Mark
the centre of the hole as well as the
circumference.
4. Remove the template from the wall.
IMPORTANT. Ensure that, during the cutting
operation, masonry falling outside of the building
does not cause damage or personal injury.
1. Cut the ue hole ensuring that the hole
is square to the wall. Both wall faces
immediately around the cut hole should be at.
2. Drill 4 boiler top xing holes with a 12mm
(1/2”) masonry drill and insert the plastic plugs
provided, for the wall mounting plate.
3. Drill the 2 boiler lower xing holes with a 12mm
(1/2”) masonry drill, insert the plastic plugs
provided .
4. Fix the wall bracket into place with 4 M10x70
hex head coach screws provided.
ima5400
X
Y
26 52 78 104
Vertical Offset From X mm
Distance from flue centre line (Y) to outside wall surface.
For lengths greater than 4m, increase offset (X) by 26mm
for every additional 1m.
4m
3m
2m
1m
Note: Horizontal ue runs must be
inclined at 1.5-3o to the horizontal to allow
condensate to drain back to the boiler.
INSTALLATION
850mm to top of boiler18mm
332mm
Ø12mm
BOILER LOWER FIXING POSITIONS
18 EVOMAX - Installation & Servicing
INSTALLATION
10
VENTILATION
9
MOUNTING THE BOILER
The ventilation requirements of these boilers is dependant on
the type of ue system used, and their heat input. All vents must
be permanent with no means of closing, and positioned to avoid
accidental obstruction by blocking or ooding.
EVOMAX 30/30P, 40/40P, 60/60P
Detail reference should be made to BS. 5440 Pt. 2. In IE refer to
the current edition of I.S. 813.
The following notes are for general guidance only:
If installed as a room sealed appliance in a room or internal
space, then no purpose provided ventilation is required.
If installed as an open ued appliance in a room or internal space
then a permanent air vent is required. The sizes given below are for
vents directly communicating with outside air. For other situations
refer to BS. 5440 Pt. 2. In IE refer to the current edition of I.S. 813.
Boiler Size 30 & 30P 40 & 40P 60 & 60P
Minimum vent
free area (cm2)117 167 269
If installed in a compartment, then permanent air vents are
required at high and low level. These vents may communicate
direct to outside air, or to a room/internal space. If to a room/
internal space, it must itself be adequately ventilated as above.
• Due care should be taken
when lifting the boilers, with
respect to their weights, see
Table 2 on Page 6. Also refer
to Safe Handling on Page 8.
1. Lift the boiler onto the wall
mounting plate as shown.
Note: It is not necessary to
hold the boiler at an angle
to engage the wall mounting
plate.
2. Using the remaining coach
screws, secure the bottom of
the boiler to the wall through
the attached brackets.
The temperature within the boiler room shall not exceed 25ºC within 100mm of the oor, 32ºC at mid height and 40ºC within 100mm
of the ceiling.
70kW AND OVER
Evomax 80, 80P, 100, 120, 150 and multiple boiler
applications
Detail reference should be made to BS. 6644 and IGEM/UP/10
for inputs between 70kW and 1.8MW (net). In IE refer to the
current edition of I.S.820. The following notes are for general
guidance only:
If ventilation is to be provided by means of permanent high and
low vents communicating direct with outside air, then reference
can be made to the sizes below. For other ventilation options
refer to BS. 6644 and IGEM/UP/10. In IE refer to the current
edition of I.S.820.
EVOMAX 80, 80P, 100, 120 & 150
Open Flued Installations
Required area (cm2) per kW of total rated input (net)
Boiler Room Enclosure
Low level (inlet) 4 10
High level (outlet) 2 5
Note: Where a boiler installation is to operate in summer months
(e.g. DHW) additional ventilation requirements are stated, if
operating for more than 50% of time (refer to BS6644) and
IGEM/UP/10.
Room Sealed Installations
A minimum of 2cm2free area per kW of net heat input at both
high and low level is required for boiler rooms. For enclosures
refer to BS6644 and IGEM/UP/10.
INSTALLATION
Room Sealed Application - Min. Vent Free Area (cm2)Open Flue Application - Min. Vent Free Area (cm2)
To a room or internal space To outside Air To a room or internal space To Outside Air
Boiler Size 30 40 60 30 40 60 30 40 60 30 40 60
High Level 310 410 610 155 205 305 310 410 610 155 205 305
Low level 310 410 610 155 205 305 620 820 1220 310 410 610
Evomax Ventilation Requirements (not exceeding 70kW net Input) when installed in a compartment
1
2
206210-10388
NOT EXCEEDING 70kW
19
EVOMAX - Installation & Servicing
INSTALLATION
12
HORIZONTAL WALL FLUE KIT
Contents
• Boiler adapter + screws (x6)
• 90oelbow
• Terminal
• Locking collars (x2)
• Wall plates (x2)
13
HORIZONTAL WALL FLUE KIT - For longer ue lengths for the Evomax 60 & 80
Contents
• Boiler adapter + screws (x6)
• Increaser
• 90oelbow
• Terminal
• Locking collars (x2)
• Wall plates (x2)
11
FLUE SYSTEMS
A comprehensive range of ue kits are available from
Ideal Boilers. Examples of horizontal and vertical concentric
and open ue options are demonstrated on the following pages.
Tables are provided with these examples, giving the maximum
extensions which may be added.
For horizontal ues: this is the distance from the ue outlet
centre line on the boiler to the outside wall. Horizontal ues are
not available for Evomax 150.
For vertical ue: this is the distance from the top of the boiler
case to the aperture in the weather collar.
If elbows are to be used, then the equivalent length of that
tting (see page 22) must be subtracted from the maximum ue
extensions allowed for that ue option.
Note: Horizontal terminal resistance includes 1 x 90o elbow.
Worked examples are shown on page 22.
A multiple boiler ue header system is available ‘Ideal Multiline’.
This permits up to 6 Evomax boilers to be connected to a single
ue header with a maximum total output of 600kW.
Other ue header systems should be designed and supplied
by a specialist ue company. BS 6644 and IGE UP/10 provide
guidance on design and the drainage of condensate from ue
stack and headers. Condensate from a ue stack and header
must be collected and drained before entering the boiler.
For room sealed ues Evomax concentric ues must be used.
Note: See Frame 18 for elbow equivalent lengths.
Note: See Frame 18 for elbow equivalent lengths.
FLUE OUTLET
Evomax horizontal concentric ue application ~ maximum lengths and pressure
differentials
Model 30/30P 40/40P 60/60P 80/80P 100 120
Max ue length (m) 42 42 7.5 12 14.3 17.6
Flue Size 80 / 125 100 / 150
Wall ue kit No 213267 213269
Evomax 60 & 80 horizontal concentric ues of
longer length
Model 60/60P 80/80P
Max ue length (m) 30 35
Flue Size 100 / 150
Wall ue kit No 213268
20 EVOMAX - Installation & Servicing
INSTALLATION
16
OPEN FLUE KITS
Contents
158662 / 158663
• Boiler adapter + screws (x6)
• Air inlet grille
158771 / 158772
• Extension tube (x2)*
158769 / 158770
• Terminal
Note: See Frame 18 for elbow equivalent lengths.
RF 2501
14
VERTICAL ROOF FLUE KIT
Contents
• Boiler adapter + screws (x6)
• Terminal
• Locking Collar
• Finishing plates (x2)
• Bracket
RF 2498
Note: See Frame 18 for elbow equivalent lengths.
15
VERTICAL ROOF FLUE KIT -
Contents
• Boiler adapter + screws (x6)
• Increaser
• Terminal
• Locking Collars (x2)
• Finishing plates (x2)
• Bracket
RF 2499
Note: See Frame 18 for elbow equivalent lengths.
FLUE OUTLET
Evomax vertical concentric ue application ~ maximum lengths and pressure differentials
Model 30/30P 40/40P 60/60P 80/80P 100 120 150
Max ue length (m) 42 42 7.5 12 14.3 17.6 7.5
Flue Size 80 / 125 100 / 150
Vertical ue kit No 213264 213266
Evomax 60 & 80 vertical concentric ues of
longer length
Model 60/60P 80/80P
Max ue length (m) 30 35
Flue Size 100 / 150
Vertical ue kit No 213265
Evomax open ue application ~ maximum lengths and pressure differentials
Model 30/30P 40/40P 60/60P 80/80P 100 120 150
Max ue length (m) 65 70 25 22 20 49 32
Max ue press diff (Pa) 140 225 150 312 220 365 430
Flue Size 80/125 100/150
Open ue kit No 158662 + 158771 + 158769 158663 + 158772 + 158770

This manual suits for next models

10

Other ideal commercial Boiler manuals

ideal commercial Evomax 60 User manual

ideal commercial

ideal commercial Evomax 60 User manual

ideal commercial Evomax 40 User manual

ideal commercial

ideal commercial Evomax 40 User manual

ideal commercial HARRIER GTS 5 User manual

ideal commercial

ideal commercial HARRIER GTS 5 User manual

ideal commercial IMAX XTRA E320 User manual

ideal commercial

ideal commercial IMAX XTRA E320 User manual

ideal commercial EVOMOD 250 User manual

ideal commercial

ideal commercial EVOMOD 250 User manual

ideal commercial EVO S User manual

ideal commercial

ideal commercial EVO S User manual

ideal commercial VICEROY GTS 8 User manual

ideal commercial

ideal commercial VICEROY GTS 8 User manual

Popular Boiler manuals by other brands

Ideal Heating LOGIC SYSTEM 2 S15 user guide

Ideal Heating

Ideal Heating LOGIC SYSTEM 2 S15 user guide

Weil-McLain Gold GV manual

Weil-McLain

Weil-McLain Gold GV manual

Crown CRN30 Operating & installation instructions

Crown

Crown CRN30 Operating & installation instructions

Truma B 10 installation instructions

Truma

Truma B 10 installation instructions

Granby B*G-3 Installation, operation and service manual

Granby

Granby B*G-3 Installation, operation and service manual

Kabola HR Series user guide

Kabola

Kabola HR Series user guide

Electro Industries EZB-Eco EZB-T1-05-240-1 Installation & operating instructions

Electro Industries

Electro Industries EZB-Eco EZB-T1-05-240-1 Installation & operating instructions

ACV Delta Performance 25 specification

ACV

ACV Delta Performance 25 specification

ACV delta pro rack Installation, operating and maintenance instructions

ACV

ACV delta pro rack Installation, operating and maintenance instructions

Olsen ODVB Series User's information manual

Olsen

Olsen ODVB Series User's information manual

Lochinvar Crest 1.5 User's information manual

Lochinvar

Lochinvar Crest 1.5 User's information manual

Buderus 600 - 11S user manual

Buderus

Buderus 600 - 11S user manual

Kalvis Kalvis-2-30U Installation and maintenance manual

Kalvis

Kalvis Kalvis-2-30U Installation and maintenance manual

Vaillant VCW GB 242 EH Instructions for installation and servicing

Vaillant

Vaillant VCW GB 242 EH Instructions for installation and servicing

Viessmann Vitodens 222-F Installation and service instructions for contractors

Viessmann

Viessmann Vitodens 222-F Installation and service instructions for contractors

Viessmann Vitomax HS Series installation instructions

Viessmann

Viessmann Vitomax HS Series installation instructions

Radiant SF 16 E user manual

Radiant

Radiant SF 16 E user manual

Roca LAURA 20 Operating and maintenance instructions

Roca

Roca LAURA 20 Operating and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.