iDect FC4A-C10R2C User manual

FC9Y-B902
FC4ASERIES
Analog I/O Module
User’s Manual

PREFACE-1
SAFETY PRECAUTIONS
• Read this user’s manual to make sure of correct operation before starting installation, wiring, operation, maintenance, and
inspection of the FC4A series MicroSmart analog I/O modules.
• All MicroSmart modules are manufactured under IDEC’s rigorous quality control system, but users must add a backup or
failsafe provision to the control system using the MicroSmart in applications where heavy damage or personal injury may
be caused in case the MicroSmart should fail.
• In this user’s manual, safety precautions are categorized in order of importance to Warning and Caution:
•Turn off the power to the MicroSmart before starting installation, removal, wiring, maintenance, and inspection of the
MicroSmart. Failure to turn power off may cause electrical shocks or fire hazard.
•Special expertise is required to install, wire, program, and operate the MicroSmart. People without such expertise must not
use the MicroSmart.
•Emergency stop and interlocking circuits must be configured outside the MicroSmart. If such a circuit is configured inside
the MicroSmart, failure of the MicroSmart may cause disorder of the control system, damage, or accidents.
•Install the MicroSmart according to the instructions described in this user’s manual. Improper installation will result in fall-
ing, failure, or malfunction of the MicroSmart.
• The MicroSmart is designed for installation in a cabinet. Do not install the MicroSmart outside a cabinet.
• Install the MicroSmart in environments described in this user’s manual. If the MicroSmart is used in places where the
MicroSmart is subjected to high-temperature, high-humidity, condensation, corrosive gases, excessive vibrations, and
excessive shocks, then electrical shocks, fire hazard, or malfunction will result.
• The environment for using the MicroSmart is “Pollution degree 2.” Use the MicroSmart in environments of pollution
degree 2 (according to IEC 60664-1).
• Prevent the MicroSmart from falling while moving or transporting the MicroSmart, otherwise damage or malfunction of
the MicroSmart will result.
• Prevent metal fragments and pieces of wire from dropping inside the MicroSmart housing. Put a cover on the MicroSmart
modules during installation and wiring. Ingress of such fragments and chips may cause fire hazard, damage, or malfunc-
tion.
• Use a power supply of the rated value. Use of a wrong power supply may cause fire hazard.
• Use an IEC 60127-approved fuse on the power line outside the MicroSmart. This is required when equipment containing
the MicroSmart is destined for Europe.
•Use an IEC 60127-approved fuse on the output circuit. This is required when equipment containing the MicroSmart is des-
tined for Europe.
• Use an EU-approved circuit breaker. This is required when equipment containing the MicroSmart is destined for Europe.
•Make sure of safety before starting and stopping the MicroSmart or when operating the MicroSmart to force outputs on or
off. Incorrect operation on the MicroSmart may cause machine damage or accidents.
• If relays or transistors in the MicroSmart output modules should fail, outputs may remain on or off. For output signals
which may cause heavy accidents, provide a monitor circuit outside the MicroSmart.
• Do not connect the ground wire directly to the MicroSmart. Connect a protective ground to the cabinet containing the
MicroSmart using an M4 or larger screw. This is required when equipment containing the MicroSmart is destined for
Europe.
• Do not disassemble, repair, or modify the MicroSmart modules.
• When disposing of the MicroSmart, do so as an industrial waste.
Warning Warning notices are used to emphasize that improper operation may cause
severe personal injury or death.
Caution Caution notices are used where inattention might cause personal injury or
damage to equipment.

PREFACE-2
About This Manual
This user’s manual primarily describes entire functions, installation, programming, and troubleshooting procedures of the
FC4A series MicroSmart analog I/O modules.
CHAPTER 1: GENERAL INFORMATION
General information about the analog I/O modules, applicable CPU module system program version, and WindLDR ver-
sion.
CHAPTER 2: MODULE SPECIFICATIONS
Specifications of the analog I/O modules.
CHAPTER 3: INSTALLATION AND WIRING
Methods and precautions for installing and wiring the analog I/O modules.
CHAPTER 4: ANALOG I/O CONTROL
General information about programming and setting up various communication systems for the analog I/O modules.
CHAPTER 5: TROUBLESHOOTING
Procedures to determine the cause of trouble and actions to be taken when any trouble occurs while operating the analog
I/O modules.
INDEX
Alphabetical listing of key words.
MicroSmart Modules
Category Modules
CPU modules
All-in-one type FC4A-C10R2, FC4A-C16R2, FC4A-C24R2
FC4A-C10R2C, FC4A-C16R2C, FC4A-C24R2C
Slim type
FC4A-D20K3, FC4A-D20S3
FC4A-D20RK1, FC4A-D20RS1
FC4A-D40K3, FC4A-D40S3
Expansion modules Expansion I/O modules Input modules, output modules, mixed I/O modules
Function modules Analog I/O modules, AS-Interface master module
Option modules HMI module, RS232C communication adapter, RS485 communication
adapter, memor y cartridge, clock cartridge
Communication modules HMI base module, RS232C communication module, RS485 communi-
cation module
IMPORTANT INFORMATION
Under no circumstances shall IDEC Corporation be held liable or responsible for indirect or consequential damages resulting
from the use of or the application of IDEC PLC components, individually or in combination with other equipment.
All persons using these components must be willing to accept responsibility for choosing the correct component to suit their
application and for choosing an application appropriate for the component, individually or in combination with other equipment.
All diagrams and examples in this manual are for illustrative purposes only. In no way does including these diagrams and exam-
ples in this manual constitute a guarantee as to their suitability for any specific application. To test and approve all programs,
prior to installation, is the responsibility of the end user.

i
TABLE OF CONTENTS
CHAPTER 1: GENERAL INFORMATION
About the Analog I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Applicable CPU Modules and WindLDR Version . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Confirming System Program Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
CHAPTER 2: MODULE SPECIFICATIONS
Parts Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Analog I/O Module Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Analog I/O Module Terminal Arrangement and Wiring Diagrams . . . . . . . . . . . . . . . 2-8
Type of Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
CHAPTER 3: INSTALLATION AND WIRING
Mounting Hole Layout for Direct Mounting on Panel Surface . . . . . . . . . . . . . . . . . . 3-1
Terminal Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
CHAPTER 4: ANALOG I/O CONTROL
System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Programming WindLDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Analog I/O Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Data Register Allocation Numbers for Analog I/O Modules . . . . . . . . . . . . . . . . . . . 4-8
Analog Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Analog Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
CHAPTER 5: TROUBLESHOOTING
Troubleshooting Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
INDEX

1-1
1: GENERAL INFORMATION
Introduction
This chapter describes general information and specifications of the FC4A series MicroSmart analog I/O modules.
About the Analog I/O Modules
Analog I/O modules are available in 3-I/O types, 2-, 4-, and 8-input types, and 1- and 2-output types. The input channel
can accept voltage and current signals, thermocouple and resistance thermometer signals, or thermistor signals. The output
channel generates voltage and current signals.
Analog I/O Module Type Numbers
Name I/O Signal I/O Points Category Type No.
Analog I/O Module
Voltage (0 to 10V DC)
Current (4 to 20mA) 2 inputs
END Refresh Type
FC4A-L03A1
Voltage (0 to 10V DC)
Current (4 to 20mA) 1 output
Thermocouple (K, J, T)
Resistance thermometer (Pt100) 2 inputs
FC4A-L03AP1
Voltage (0 to 10V DC)
Current (4 to 20mA) 1 output
Analog Input Module
Voltage (0 to 10V DC)
Current (4 to 20mA) 2 inputs FC4A-J2A1
Voltage (0 to 10V DC)
Current (4 to 20mA)
Thermocouple (K, J, T)
Resistance thermometer
(Pt100, Pt1000, Ni100, Ni1000)
4 inputs
Ladder Refresh Type
FC4A-J4CN1
Voltage (0 to 10V DC)
Current (4 to 20mA) 8 inputs FC4A-J8C1
Thermistor (NTC, PTC) 8 inputs FC4A-J8AT1
Analog Output Module
Voltage (0 to 10V DC)
Current (4 to 20mA) 1 output END Refresh Type FC4A-K1A1
Voltage (–10 to +10V DC)
Current (4 to 20mA) 2 outputs Ladder Refresh Type FC4A-K2C1
END Refresh Type and Ladder Refresh Type
Depending on the internal circuit design for data refreshing, analog I/O modules are categorized into two types.
END Refresh Type
Each END refresh type analog I/O module is allocated 20 data registers to store analog I/O data and parameters for controlling
analog I/O operation. These data registers are updated at ever y end processing while the CPU module is running. WindLDR has
ANST macro to program the analog I/O modules.
The CPU module checks the analog I/O configuration only once at the end processing in the first scan. If you have changed the
parameter while the CPU is running, stop and restart the CPU to enable the new parameter.
Ladder Refresh Type
Each ladder refresh type analog I/O module can be allocated any data registers to store analog I/O data and parameters for con-
trolling analog I/O operation. The data registers are programmed in the ANST macro. Analog I/O data are updated at the ladder
step following the ANST macro. Analog I/O parameters are updated when the ANST macro is executed, so analog I/O parame-
ters can be changed while the CPU is running.
Analog I/O Module Category END Refresh Type Ladder Refresh Type
While CPU
is running
Parameter Refreshing At the end processing in the first scan When executing ANST macro
Analog I/O Data
Refreshing At the end processing In the step after ANST macro
(always refreshed whether input to ANST is on or off)
While CPU
is stopped
Analog Output Data
Refreshing
When M8025 (maintain outputs while CPU
stopped) is on, output data is refreshed.
When off, output is turned off.
Maintains output status when the CPU is stopped.
Output data can be changed using STPA instruction
while the CPU is stopped.
See page 4-21.
Data Register Allocation By default Optionally designated in ANST macro

1: GENERAL INFORMATION
1-2
Applicable CPU Modules and WindLDR Version
END refresh type analog I/O modules as many as listed below can be used with any FC4A and FC5A MicroSmart CPU
modules and WindLDR versions.
Ladder refresh type analog I/O modules can be used with the FC4A and FC5A MicroSmart CPU module system program
versions and WindLDR versions as listed below.
All-in-one 10- and 16-I/O type CPU modules cannot use either END refresh or ladder refresh type analog I/O modules.
Note: FC5A all-in-one 24-I/O type CPU modules cannot use analog I/O modules in combination with the AS-Interface master
module (FC4A-AS62M) and/or expansion RS232C communication module (FC5A-SIF2). When using these modules in combi-
nation with analog I/O modules, use the slim type CPU module.
Confirming System Program Version
The system program version can be confirmed using WindLDR.
1. Connect a PC to communication port 1 or 2 on the MicroSmart CPU module using the computer link cable 4C
(FC2A-KC4C).
2. From the WindLDR menu bar, select Online > Monitor. The monitor mode is enabled.
3. From the WindLDR menu bar, select Online > PLC Status. The PLC Status dialog box appears and shows the sys-
tem program version.
FC4A MicroSmart
CPU Module
All-in-One Type Slim Type
FC4A-C10R2
FC4A-C10R2C
FC4A-C16R2
FC4A-C16R2C
FC4A-C24R2
FC4A-C24R2C
FC4A-D20K3
FC4A-D20S3
FC4A-D20RK1
FC4A-D20RS1
FC4A-D40K3
FC4A-D40S3
CPU System Program Version — — 204 or higher 204 or higher 203 or higher
WindLDR Version — — 5.0 or higher
Quantity of Analog I/O Modules — — 4 7 7
FC5A MicroSmart
CPU Module
All-in-One Type Slim Type
FC5A-C10R2
FC5A-C10R2C
FC5A-C16R2
FC5A-C16R2C
FC5A-C24R2
FC5A-C24R2C
(Note)
FC5A-D16RK1
FC5A-D16RS1
FC5A-D32K3
FC5A-D32S3
CPU System Program Version — — 100 or higher 100 or higher 100 or higher
WindLDR Version — — 5.0 or higher
Quantity of Analog I/O Modules — — 4 7 7
System Program Version
(Special data register D8029)

2-1
2: MODULE SPECIFICATIONS
Introduction
This chapter describes parts names, functions, specifications, and dimensions of the analog I/O modules.
Parts Description
(1) Expansion Connector Connects to the CPU and other I/O modules.
(The all-in-one 10- and 16-I/O type CPU modules cannot be connected.)
(2) Module Label Indicates the analog I/O module Type No. and specifications.
(3) Power LED (PWR) END refresh type FC4A-L03A1, FC4A-L03AP1, FC4A-J2A1, FC4A-K1A1:
Turns on when power is supplied to the analog I/O module.
(3) Status LED (STAT) Ladder refresh type FC4A-J4CN1, FC4A-J8C1, FC4A-J8AT1, FC4A-K2C1:
Indicates the operating status of the analog I/O module.
(4) Terminal No. Indicates terminal numbers.
(5) Cable Terminal All analog I/O modules have a removable terminal block.
Status LED Analog Input Operating Status
OFF Analog I/O module is stopped
ON Normal operation
Flash
Initializing
Changing configuration
Hardware initialization error
External power supply error
The ter
minal style depends on the model of analog I/O modules.
(1) Expansion Connector
(2) Module Label
(3) Power LED (PWR)
(4) Terminal No.
(5) Cable Terminal
(3) Status LED (STAT)

2: MODULE SPECIFICATIONS
2-2
Analog I/O Module Specifications
General Specifications (END Refresh Type)
Note: The external current draw is the value when all analog inputs are used and the analog output value is at 100%.
General Specifications (Ladder Refresh Type)
Note: The external current draw is the value when all analog inputs are used and the analog output value is at 100%.
Type No. FC4A-L03A1 FC4A-L03AP1 FC4A-J2A1 FC4A-K1A1
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 28.8V DC
Terminal Arrangement See Analog I/O Module Terminal Arrangement on pages 2-8 to 2-11.
Connector on Mother Board MC1.5/11-G-3.81BK (Phoenix Contact)
Connector Insertion/Removal Durability 100 times minimum
Internal Current Draw 50 mA (5V DC)
0 mA (24V DC)
50 mA (5V DC)
0 mA (24V DC)
50 mA (5V DC)
0 mA (24V DC)
50 mA (5V DC)
0 mA (24V DC)
External Current Draw (Note) 45 mA (24V DC) 40 mA (24V DC) 35 mA (24V DC) 40 mA (24V DC)
Weight 85g
Type No. FC4A-J4CN1 FC4A-J8C1 FC4A-J8AT1 FC4A-K2C1
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 28.8V DC
Terminal Arrangement See Analog I/O Module Terminal Arrangement on pages 2-8 to 2-11.
Connector on Mother Board MC1.5/10-G-3.81BK (Phoenix Contact)
Connector Insertion/Removal Durability 100 times minimum
Internal Current Draw 50 mA (5V DC)
0 mA (24V DC)
40 mA (5V DC)
0 mA (24V DC)
45 mA (5V DC)
0 mA (24V DC)
60 mA (5V DC)
0 mA (24V DC)
External Current Draw (Note) 55 mA (24V DC) 50 mA (24V DC) 55 mA (24V DC) 85 mA (24V DC)
Weight 140g 140g 125g 110g

2: MODULE SPECIFICATIONS
2-3
Analog Input Specifications (END Refresh Type)
For Note 1 through Note 4, see page 2-7.
Type No. FC4A-L03A1 / FC4A-J2A1 FC4A-L03AP1
Analog Input Signal Type Voltage Input Current Input Thermocouple Resistance
Thermometer
Input Range 0 to 10V DC 4 to 20 mA DC
Type K
(0 to 1300°C)
Type J
(0 to 1200°C)
Type T
(0 to 400°C)
Pt 100
3-wire type
(–100 to 500°C)
Input Impedance 1 MΩminimum 10Ω1 MΩminimum 1 MΩminimum
Allowable Conductor Resistance
(per wire) — — — 200Ωmaximum
Input Detection Current — — — 1.0 mA maximum
AD
Conversion
Sample Duration Time 20 ms maximum 20 ms maximum
Sample Repetition Time 20 ms maximum 20 ms maximum
Total Input System
Transfer Time (Note 1) 105 ms + 1 scan time 200 ms + 1 scan time
Type of Input Single-ended
input Differential input
Operating Mode Self-scan
Conversion Method ∑∆ type ADC
Input Error
Maximum Error at 25°C ±0.2% of full scale
±0.2% of full scale
+ reference
junction compen-
sation accuracy
(±4°C maximum)
±0.2% of full
scale
Temperature Coefficient ±0.006% of full scale/°C
Repeatability after
Stabilization Time ±0.5% of full scale
Non-lineality ±0.2% of full scale
Maximum Error ±1% of full scale
Data
Digital Resolution 4096 increments (12 bits)
Input Value of LSB 2.5 mV 4 µA
K: 0.325°C
J: 0.300°C
T: 0.100°C
0.15°C
Data Type in Application
Program
Default: 0 to 4095
Optional: –32768 to 32767 (selectable each channel) (Note 2)
Monotonicity Yes
Input Data Out of Range Detectable (Note 3)
Noise
Resistance
Maximum Temporary
Deviation during Electrical
Noise Tests (Note 4)
±3% maximum Not assured
Input Filter No
Recommended Cable for
Noise Immunity Twisted pair shielded cable —
Crosstalk 2 LSB maximum
Isolation Isolated between input and power circuit
Photocoupler-isolated between input and internal circuit
Effect of Improper Input Connection No damage
Maximum Permanent Allowed Overload
(No Damage) 13V DC 40 mA DC —
Selection of Analog Input Signal Type Using software programming
Calibration or Verification to Maintain
Rated Accuracy Impossible

2: MODULE SPECIFICATIONS
2-4
Analog Input Specifications (Ladder Refresh Type)
Type No. FC4A-J4CN1 / FC4A-J8C1 FC4A-J4CN1
Analog Input Signal Type Voltage Input Current Input Thermocouple Resistance
Thermometer
Input Range 0 to 10V DC 4 to 20 mA DC
Type K:
0 to 1300°C
Type J:
0 to 1200°C
Type T:
0 to 400°C
Pt100, Pt1000:
–100 to 500°C
Ni100, Ni1000:
–60 to 180°C
Input Impedance 1 MΩ
FC4A-J4CN1:
12Ω1 MΩ—
FC4A-J8C1:
100Ω
Input Detection Current — — — 0.1 mA
AD
Conversion
Sample Duration Time 2 ms maximum
Sample Repetition Time FC4A-J4CN1: 10 ms maximum
FC4A-J8C1: 2 ms maximum 10 ms maximum 30 ms maximum
Total Input System
Transfer Time (Note 1)
FC4A-J4CN1:
40 ms ×channels + 1 scan time
FC4A-J8C1:
8 ms ×channels + 1 scan time
45 ms
×channels
+ 1 scan time
65 ms
×channels
+ 1 scan time
Type of Input Single-ended input
Operating Mode Self-scan
Conversion Method FC4A-J4CN1: ∑∆ type ADC
FC4A-J8C1: Successive approximation register method
Input Error
Maximum Error at 25°C ±0.2% of full scale
±0.2% of full scale
+ reference
junction compen-
sation accuracy
(±3°C maximum)
±0.2% of full
scale
Cold Junction
Compensation Error — — ±3.0°C
maximum —
Temperature Coefficient ±0.005% of full scale/°C
Repeatability after
Stabilization Time ±0.5% of full scale
Non-lineality ±0.04% of full scale
Maximum Error ±1% of full scale

2: MODULE SPECIFICATIONS
2-5
For Note 1 through Note 4, see page 2-7.
Data
Digital Resolution 50000 increments (16 bits)
K: Approx.
24000 increments
(15 bits)
J: Approx.
33000 increments
(15 bits)
T: Approx.
10000 increments
(14 bits)
Pt100: Approx.
6400 increments
(13 bits)
Pt1000: Approx.
64000 increments
(16 bits)
Ni100: Approx.
4700 increments
(13 bits)
Ni1000: Approx.
47000 increments
(16 bits)
Input Value of LSB 0.2 mV 0.32 µA
K: 0.058°C
J: 0.038°C
T: 0.042°C
Pt100: 0.086°C
Pt1000: 0.0086°C
Ni100: 0.037°C
Ni1000: 0.0037°C
Data Type in Application
Program Default: 0 to 50000 Default:
0 to 50000
Pt100, Ni100:
0 to 6000
Pt1000, Ni1000:
0 to 60000
Monotonicity Optional: –32768 to 32767 (selectable for each channel) (Note 2)
Input Data Out of Range — Temperature: Celsius, Fahrenheit
Data Digital Resolution Yes
Input Value of LSB Detectable (Note 3)
Noise
Resistance
Maximum Temporary
Deviation during
Electrical Noise Tests
(Note 4)
±3% maximum Not assured
Input Filter Software
Recommended Cable for
Noise Immunity Twisted pair cable —
Crosstalk 2 LSB maximum
Isolation Isolated between input and power circuit
Photocoupler-isolated between input and internal circuit
Effect of Improper Input Connection No damage
Maximum Permanent Allowed Overload
(No Damage) 11V DC 22 mA DC —
Selection of Analog Input Signal Type Using software programming
Calibration or Verification to Maintain
Rated Accuracy Impossible
Type No. FC4A-J4CN1 / FC4A-J8C1 FC4A-J4CN1
Analog Input Signal Type Voltage Input Current Input Thermocouple Resistance
Thermometer

2: MODULE SPECIFICATIONS
2-6
Analog Input Specifications (Ladder Refresh Type)
For Note 1 through Note 4, see page 2-7.
Type No. FC4A-J8AT1
Analog Input Signal Type NTC PTC
Input Range –50 to 150°C
Applicable Thermistor 100 kΩmaximum
Input Detection Current 0.1 mA
AD
Conversion
Sample Duration Time 2 ms maximum
Sample Repetition Time 2 ms ×channels
Total Input System
Transfer Time (Note 1) 10 ms ×channels + 1 scan time (Note 1)
Type of Input Single-ended input
Operating Mode Self-scan
Conversion Method Successive approximation register method
Input Error
Maximum Error at 25°C ±0.2% of full scale
Temperature Coefficient ±0.005% of full scale/°C
Repeatability after
Stabilization Time ±0.5% of full scale
Non-lineality No
Maximum Error ±1% of full scale
Data
Digital Resolution Approx. 4000 increments (12 bits)
Input Value of LSB 0.05°C
Data Type in Application
Program
Default: 0 to 4000
Optional: –32768 to 32767 (selectable for each channel) (Note 2)
Temperature: Celsius, Fahrenheit (NTC only)
Resistance: 0 to 10000
Monotonicity Yes
Input Data Out of Range Detectable (Note 3)
Noise
Resistance
Maximum Temporary
Deviation during
Electrical Noise Tests
(Note 4)
±3% maximum
Input Filter Software
Recommended Cable for
Noise Immunity —
Crosstalk 2 LSB maximum
Isolation Isolated between input and power circuit
Photocoupler-isolated between input and internal circuit
Effect of Improper Input Connection No damage
Selection of Analog Input Signal Type Using software programming
Calibration or Verification to Maintain
Rated Accuracy Impossible

2: MODULE SPECIFICATIONS
2-7
Analog Output Specifications
Note 1: Total input system transfer time = Sample repetition time + Internal processing time
When using the FC4A-J4CN1, FC4A-J8C1, or FC4A-J8AT1, the total input system transfer time increases in proportion to the
number of channels used.
Note 2: The data processed in the analog I/O module can be linear-converted to a value between –32768 and 32767. The
optional range designation, and analog I/O data minimum and maximum values can be selected using data registers allo-
cated to analog I/O modules. See page 4-12.
Note 3: When an error is detected, a corresponding error code is stored to a data register allocated to analog I/O operating
status. See page 4-6.
Note 4: The value is measured when a 500V clamp voltage is applied to the power supply and I/O lines.
Category END Refresh Type Ladder Refresh
Type No. FC4A-L03A1 FC4A-L03AP1 FC4A-K1A1 FC4A-K2C1
Output Range Voltage 0 to 10V DC –10 to +10V DC
Current 4 to 20 mA DC
Load Load Impedance 2 kΩminimum (voltage), 300Ωmaximum (current)
Applicable Load Type Resistive load
DA
Conversion
Settling Time 50 ms 130 ms 50 ms 1 ms/ch
Total Output System
Transfer Time Settling time + 1 scan time 1 ms ×channels
+ 1 scan time
Output Error
Maximum Error at
25°C ±0.2% of full scale
Temperature
Coefficient ±0.015% of full scale/°C ±0.005% of full
scale/°C
Repeatability after
Stabilization Time ±0.5% of full scale
Output Voltage Drop ±1% of full scale
Non-lineality ±0.2% of full scale
Output Ripple 1 LSB maximum ±0.1% of full scale
Overshoot 0%
Total Error ±1% of full scale
Data
Digital Resolution 4096 increments (12 bits) 50000 increments
(16 bits)
Output Value
of LSB
Voltage 2.5 mV 0.4 mV
Current 4 µA 0.32 µA
Data Type in
Application Program
Default: 0 to 4095 (voltage, current)
–25000 to 25000
(voltage)
0 to 50000
(current)
Optional: –32768 to 32767 (selectable for each channel) (Note 2)
Monotonicity Yes
Current Loop Open Not detectable
Noise
Resistance
Maximum Temporary
Deviation during
Electrical Noise Tests
(Note 4)
±3% maximum
Recommended Cable
for Noise Immunity Twisted pair shielded cable Twisted pair cable
Crosstalk No crosstalk because of 1 channel output 2 LSB maximum
Isolation Isolated between output and power circuit
Photocoupler-isolated between output and internal circuit
Effect of Improper Output Connection No damage
Selection of Analog Output Signal Type Using software programming
Calibration or Verification to Maintain
Rated Accuracy Impossible

2: MODULE SPECIFICATIONS
2-8
Analog I/O Module Terminal Arrangement and Wiring Diagrams
FC4A-L03A1 (Analog I/O Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT11P (supplied with the analog I/O module)
FC4A-L03AP1 (Analog I/O Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT11P (supplied with the analog I/O module)
T
erminal No. Channel
+
24V DC–
+OUT
–
NC
IN0+
–
NC
IN1+
–
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.
•Before turn on the power, make sure that wiring to the analog I/O module is correct. If wiring is
incorrect, the analog I/O module may be damaged.
Fuse
+–
24V DC
Analog voltage/current
input device
+
–
+
–
+
–
Analog voltage/current
output device
Analog voltage/current
output device
Terminal No. Channel
+
24V DC–
+OUT
–
NC A
IN0+ B’
– B
NC A
IN1+ B’
– B
Thermocouple
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•When connecting a resistance thermometer, connect the three wires to RTD (resistance temper-
ature detector) terminals A, B’, and B of input channel IN0 or IN1.
•When connecting a thermocouple, connect the two wires to terminals + and – of input channels
IN0 or IN1.
•Do not connect any wiring to unused terminals.
•Do not connect the thermocouple to a hazardous voltage (60V DC or 42.4V peak or higher).
Fuse
+–
24V DC
Resistance
thermometer
+
–
B
+
–
A
B’
Analog voltage/current
input device

2: MODULE SPECIFICATIONS
2-9
FC4A-J2A1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT11P (supplied with the analog input module)
FC4A-J4CN1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT10P (supplied with the analog input module)
Terminal No. Channel
+
24V DC–
NC —
NC
NC
IN0+
–
NC
IN1+
–
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.
Fuse
+–
24V DC
+
–
+
–
Analog voltage/current
output device
Analog voltage/current
output device
T
erminal No. Channel
24V
24V DC0V
NC —
CS
IN0
+
–
I–
CS IN1
+
–IN1
I–
CS
IN2
+
–
I–
CS
IN3
+
–
I–
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the diagram. This is
required when equipment containing the MicroSmart is destined for Europe.
•When connecting a resistance thermometer, connect three wires B, B’, and A to the CS (current sense), +, and – termi-
nals of input channels IN0 through IN3, respectively.
•When connecting a thermocouple, connect the + wire to the + terminal and the – wire to the CS and – terminals.
•Do not connect the thermocouple to a hazardous voltage (60V DC or 42.4V peak or higher).
•Do not connect any wiring to unused terminals.
•– terminals of input channels IN0 through IN3 are interconnected.
Fuse
+–
24V DC
Analog voltage
output device –
+
Resistance
thermometer A
B
B’
Thermocouple
+
–
NC
–
+
NC
NC
Analog current
output device

2: MODULE SPECIFICATIONS
2-10
FC4A-J8C1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT10P (supplied with the analog input module)
FC4A-J8AT1 (Analog Input Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT10P (supplied with the analog input module)
T
erminal No. Channel
24V
24V DC0V
NC —
+IN0
–
+IN1
–
+IN2
–
+IN3
–
+IN4
–
+IN5
–
+IN6
–
+IN7
–
Fuse
+–
24V DC
Analog voltage
output device –
+
Analog current
output device –
+
•Connect a fuse appropriate for the applied voltage and
current draw, at the position shown in the diagram.
This is required when equipment containing the
MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.
•– terminals of input channels IN0 through IN7 are
interconnected.
Terminal No. Channel
24V
24V DC0V
NC —
AIN0
B
AIN1
B
AIN2
B
AIN3
B
AIN4
B
AIN5
B
AIN6
B
AIN7
B
Fuse
+–
24V DC
NTC
Thermistor B
A
PTC
Thermistor B
A
•Connect a fuse appropriate for the applied voltage and
current draw, at the position shown in the diagram.
This is required when equipment containing the
MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.

2: MODULE SPECIFICATIONS
2-11
FC4A-K1A1 (Analog Output Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT11P (supplied with the analog output module)
FC4A-K2C1 (Analog Output Module) — Screw Terminal Type
Applicable Terminal Block: FC4A-PMT10P (supplied with the analog output module)
Terminal No. Channel
+
24V DC–
+OUT
–
NC
—NC
NC
NC
—NC
NC
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.
Fuse
+–
24V DC
+
–
Analog voltage/current
input device
Terminal No. Channel
24V
24V DC0V
NC —
V+
OUT0I+
–
V+
OUT1I+
–
Fuse
+–
24V DC
+
–
Analog voltage
input device
+
–
NC
NC
Analog current
input device
•Connect a fuse appropriate for the applied voltage and current draw, at the position shown in the
diagram. This is required when equipment containing the MicroSmart is destined for Europe.
•Do not connect any wiring to unused terminals.
•– terminals of output channels OUT0 and OUT1 are interconnected.

2: MODULE SPECIFICATIONS
2-12
Type of Protection
Input Circuits
Output Circuits
1 k
Ω
NC (A)
Multiplexer
+ (B’)
FC4A-L03A1, FC4A-L03AP1, FC4A-J2A1
– (B)
1 kΩ
1 kΩ
+V2 +V1
–V1
10Ω
Input Data
Input
Selection
Signal
FC4A-J4CN1
15 MΩ
CS
Input Circuit
+
–
I–
15Ω
Current
Source
+
Input Circuit
–
FC4A-J8C1
10 kΩ
Input
Selection
Signal
100Ω
FC4A-J8AT1
A
Input Circuit
B
Current
Source
FC4A-L03A1, FC4A-L03AP1, FC4A-K1A1 FC4A-K2C1
Output Circuit
+
–
Output Circuit
V+
I+
–

2: MODULE SPECIFICATIONS
2-13
Power Supply for Analog I/O Modules
When supplying power to the analog I/O modules, take the following considerations.
•Power Supply for END Refresh Type Analog I/O Modules
Use separate power supplies for the MicroSmart CPU module and END refresh type analog I/O modules. Power up the
analog I/O modules at least 1 second earlier than the CPU module. This is recommended to ensure correct operation of the
analog I/O control.
•Power Supply for Ladder Refresh Type Analog I/O Modules
Use the same power supply for the MicroSmart CPU module and ladder refresh type analog I/O modules to suppress the
influence of noises.
After the CPU module has started to run, ladder refresh type analog input modules perform initialization for a maximum
of 5 seconds. During this period, the analog input data have an indefinite value. Design the user program to make sure that
the analog input data are read to the CPU module after the analog input operating status has changed to 0 (normal opera-
tion). For the analog input operating status, see page 4-13.
Wiring Analog I/O Lines
Separate the analog I/O lines, particularly resistance thermometer inputs, from motor lines as much as possible to suppress
the influence of noises.
T
erminal No. Channel
+
24V DC–
+OUT
–
NC A
IN0+ B’
– B
NC A
IN1+ B’
– B
Fuse
+–
24V DC
Resistance
thermometer B
+
–
A
B’
Analog voltage/current
input device
+
–
Analog voltage/current
output device
Separate the analog I/O line
from the power line.

2: MODULE SPECIFICATIONS
2-14
Dimensions
FC4A-L03A1, FC4A-L03AP1, FC4A-J2A1, FC4A-K1A1, FC4A-K2C1
FC4A-J4CN1, FC4A-J8C1, FC4A-J8AT1
23.5 14.6 70.0
90.04.5*
3.8
*8.5 mm when the clamp is pulled out.
All dimensions in mm.
23.5 14.6 70.0
90.04.5*
3.8
*8.5 mm when the clamp is pulled out.
This manual suits for next models
21
Table of contents
Popular I/O System manuals by other brands

Metz Connect
Metz Connect EWIO2 user manual

M-system
M-system R7C-MS4 instruction manual

ABB
ABB SAM600 Series Operation manual

National Instruments
National Instruments 9225E Operating instructions and specifications

Beckhoff
Beckhoff EJ18 Series manual

Moxa Technologies
Moxa Technologies ioLogik E1200 Series Quick installation guide

Bosch
Bosch Rexroth IndraControl S67 Series manual

Allen-Bradley
Allen-Bradley 1791-0A32 B Series installation instructions

Vacon
Vacon CXS Series installation manual

Rice Lake
Rice Lake ALLEN-BRADLEY Remote I/O Interface Installation and programming manual

Unitronics
Unitronics Uni-I/O UIA-0006 installation guide

olympia electronics
olympia electronics BSR-8020/WP/MAR manual