ILLUMISOFT LIGHTING SaniLume SL-36KT-75 User manual

1
SL-OM-ENG-16-09-2021
Upper Room Air
Germicidal Fixture
All Models
Safety Precautions, Site Planning,
Installation, Operation, Maintenance
Safeguards Page 2
Safety Warning Labels
Page 3
Safety Instructions
Page 4
First Aid Page 5
Disclaimers Page 5
Warranty Page 6
Features Page 7
Specifications
Page 8
Certified Laboratory Test Results
Page 9
Site Planning: Installation Considerations
Page 10
Site Planning: Line of Sight Page 12
Site Planning: Electrical
Page 13
Site Planning: Fixture Mounting Height & Aperture Adjustment Page 14
Fixture Quantity Estimation
Page 19
Mounting Hardware & Accessory Kit Page 20
Installation Instructions
Page 21
Maintenance Page 24
UVC Measurement Quick Start Guide Page 27
About Page 28
All contents are subject to change without notice.

2
SL-OM-ENG-16-09-2021
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed
including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
a) This equipment is designed for use with germicidal UV radiation sources and must be
installed incompliance with competent technical directions to prevent risk of personal injury
from UV radiation.
b) UV radiation can pose a risk of personal injury. Over exposure can result in damage to
eyes and bare skin. To reduce the risk of overexposure this equipment must be installed in
accordance with the manufacturer’s site planning recommendations. This may include
instructions on the relative location of each germicidal system component, the minimum
distances between UV-generating devices and other objects or surfaces, and protection
from line-of-sight exposure to UV radiation in occupied spaces located above the equipment
mounting area (e.g., upper floor balconies, open staircases, etc.)
c) UV and optical radiation can be reflected by surrounding surfaces such as ceilings and
walls. Since the reflective properties of surfaces can vary widely, it should be considered as
part of site planning. Follow the manufacturer’s recommendations for selecting appropriate
ceiling and wall finishes.
d) IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE THAT PERSONS
WILL NOT BE EXPOSED TO EXCESSIVE UV OR OPTICAL RADIATION DURING
EQUIPMENTOPERATION. THIS WILL REQUIRE THE INSTALLER TO CONDUCT AN
ASSESSMENT OF IRRANDIANCE OR ILLUMINANCE LEVELS IN THE SURROUNDING
OCCUPIED SPACES PRIOR TO OCCUPANCY.
e) Equipment should be mounted in locations and at heights where it will not readily be
subjected to tampering by unauthorized personnel.
f) Maintenance and servicing of this UV generating equipment shall be performed by
authorized personnel. Service personnel must wear appropriate Personal Protective
Equipment (PPE) if the equipment will be in operation during the maintenance or servicing
work. Contact the Equipment manufacturer for PPE recommendations and guidance.
g) When replacing lamps, replace them only with the lamps for which the equipment is
marked and intended.
h) The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition.
i) Do not use this equipment for other than intended use.
READ AND SAVE THESE INSTRUCTIONS

3
SL-OM-ENG-16-09-2021
All personnel should be alerted to the potential hazards indicated by the product
safety labeling on this unit. The following conventions are used to indicate and
classify precautions in this manual and on product safety labeling. Failure to observe
precautions could result in injury to people or damage to property.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
Danger indicates an IMMINENTLY hazardous situation, which, if not avoided, WILL result in
death or serious injury.
Warning indicates a POTENTIALLY hazardous situation, which, if not avoided, COULD
result in death or serious injury.
Caution indicates a POTENTIALLY hazardous situation, which, if not avoided, MAY result in
minor or moderate injury.
This symbol is used to identify an ELECTRICAL SHOCK or ELECTROCUTION hazard.
This symbol is used to identify an ULTRAVIOLET LIGHT
hazard.
This symbol is used to identify the need to wear approved ultraviolet blocking eyewear.
This symbol is used to identify the need to wear protective gloves.
This symbol is used to identify components which must not be disposed of in
trash

4
SL-OM-ENG-16-09-2021
To guard against injury, basic safety precautions should be observed, including the following:
1.
Read and follow ALL safety instructions.
2.
Avoid exposure to direct or reflected germicidal ultraviolet rays.
Germicidal ultraviolet rays are harmful to the eyes and skin.
3.
Intended for indoor use only.
4.
Do not alter design or construction.
5.
Do not use this unit for other than its intended purpose, as described in this manual.
6.
Do not mount under any source of moisture or condensation, such as humidifiers, cooling coils, etc.
7.
Germicidal ultraviolet rays may break down plastic, rubber or other non-metallic
materials, with inadequate resistance to ultraviolet rays. Shield these materials which may be exposed to
direct or reflected germicidal ultraviolet rays.
8.
Do not remove any labels or devices.
9.
Do not operate without proper electrical ground.
10.
Do not operate the unit if there is visible or suspected damage to the unit or, if applicable, there is damage
to power cord and/or plug.
11.
Do not operate without lower panel secured.
12.
Utility power supplied to the unit MUST match power requirements listed on the unit label.
13.
Always disconnect power to the unit before performing any service or maintenance.
14.
Read and follow all notices and warnings on the unit.
15.
SAVE THESE INSTRUCTIONS.
NOTICE: These instructions do not claim to cover all details or variations in the equipment, procedure, or process
described, or to provide directions for meeting every possible contingency during installation, operation or
maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s
purpose, please contact your nearest representative.
NOTICE: Proper grounding is required to ensure personal safety. Carefully observe grounding procedure under
installation section.
NOTICE: Fixture may become damaged and/or unstable if not installed properly.
GENERAL: Upon receipt of fixture thoroughly inspect for any freight damage, which should be brought to the
attention of the delivery carrier. Compare the catalog description listed on the packing slip with the fixture label
on the housing to assure you have received the correct merchandise.
See ratings on fixture for appropriate voltage. Any other connection voids the warranty.
It is the user’s responsibility to determine and validate the suitability of this equipment for use in the user’s
system or process. No warranty or representation is made by the manufacturer with respect to suitability
or performance of this equipment or to the results that may be expected from its use. The user should
periodically inspect, clean as necessary and confirm the presence and good legibility of the product.
Safety Instructions

5
SL-OM-ENG-16-09-2021
1.
For UV radiation overexposure of the eye, place a sterile dressing over the eye
and get medical attention.
2.
For UV radiation overexposure of the skin, apply cold water or ice to the skin
burns and get medical attention.
Disclaimer:
This product is not approved or certified as a medical device and
is not intended to be used for medical purposes.
Disclaimer:
Illumisoft Lighting Canada Inc. does not promise or warrant that
the
use of the Products will protect any user from or prevent infection and/or
contamination with any viruses, bacteria, protozoa, fungi, illness or disease. The
Products are not approved and/or certified as a medical device by Health Canada
or any other regulatory body. As such, the Products are not intended for and
must not be used for medical purposes.
DISCLAIMER OF LIABILITY:
Illumisoft Lighting Canada Inc. assumes no
liability
for damages or losses of any kind that may arise from the improper,
careless, or
negligent installation, handling or use of this product, or through any
use of thisproducts outside of their intended use as described.

6
SL-OM-ENG-16-09-2021
ILLUMISOFT LIGHTING CANADA INC.
LIMITED WARRANTY EFFECTIVE Aug. 17, 2021
Subject to the exclusions set forth below, Illumisoft Lighting Canada Inc. (“Illumisoft”) warrants its products to be free from defect
in material and workmanship for a period of five (5) years from the date of shipment from Illumisoft’s facilities, except as follows:
a)
Lamp: 1 years
b)
Fans and Ballast 3 years
Reseller must follow the instructions contained within the Installation and Safety manual. Failure to install any Product properly will
void this Manufacturer’s Warranty as will any tampering with the Product by anyone other than Illumisoft or its authorized agents.
This statement of Limited Warranty (“Warranty”) applies only when the Product(s) are installed in applications in which ambient
temperatures are within the normal range of climate controlled indoor environments. Illumisoft will not be responsible for any
failure of the Product(s) that result from external causes such as: acts of nature; physical damage; exposure to adverse chemicals or
other substances; use of reactive cleaning agents or harsh chemicals to clean the Product(s); environmental conditions; vandalism;
fire; animal or insect activity; fault or negligence of purchaser, any end user of the Product(s)and/or any third party not engaged by
Illumisoft, improper or unauthorized use, installation, handling, storage, alteration, maintenance or service or any other occurrences
beyond Illumisoft’s reasonable control. Adequate records of operating history and maintenance must be kept by the end user and
be provided to Illumisoft upon request to substantiate that the Product(s) have failed to comply with the terms of this Warranty.
If the Product(s) fail to comply with the terms of this Warranty, Illumisoft, at its option, will repair or replace the Product(s) with the
same or functionally equivalent Product(s) or component part(s). This Warranty excludes labor and equipment required to remove
and/or reinstall original or replacement part(s). This Warranty extends only to the Product(s) as delivered to, and is for the sole and
exclusive benefit of, the original end user. The repair of replacement of any Product(s) or component part within the Product(s) is
the sole and exclusive remedy for failure of the Product(s) to comply with the terms of this Warranty and does not extend the
Warranty period. Warranty claims regarding the Product(s) must be submitted in writing within (30) days of discovery of the defect
or failure to an authorized Illumisoft representative. Product(s) or component part(s) may be required to be returned for inspection
and verification of non-conformance by Illumisoft. Illumisoft is not responsible for any costs and expenses incurred in connection
with shipment of Product(s) to Illumisoft, but Illumisoft shall bear all cost and expense incurred in connection with shipment of
replacement Product(s) to the customer.
THE FOREGOING WARRANTY TERMS ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, AND ILLUMISOFT EXPRESSLY
DISCLAIMS ALLOTHER WARRANTIES, EXPRESS OR IMPLIED, RELATING DIRECTLY OF INDIRECTLY TO THE PRODUCT(S), WHETHER
ORAL, WRITTEN OR ARISING BY COURSE OF DEALING OR USAGE OF TRADE, INCLUDING, WITHOUT LIMITATION, ANY WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. NO AGENT, DISTRIBUTOR OR OTHER SUPPLIER OF ILLUMISOFT
PRODUCTS HAS THE AUTHORITY TO MODIFY OR AMEND THIS WARRANTY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROM
ILLUMISOFT.
The total liability of Illumisoft on any and all claims of any kind, whether in contract, warranty, tort (including negligence), strict
liability or otherwise, arising out of or in connection with, or resulting from, Illumisoft’s performance or breach of this Warranty, or
from Illumisoft’s sale, delivery, resale, repair, or replacement of any Product(s) or the furnishing of any services, shall in no event
exceed the purchase price allocable to the Product(s) that give rise to the claim, and any and all such liability shall terminate upon
the expiration of the warranty period specified above.
IN NO EVENT SHALL ILLUMISOFT BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL, CONSEQUENTIAL, EXEMPLARY OR PUNITIVE
DAMAGES, EVEN IF INFORMED OF THE POSSIBILITY OF SUCH DAMAGES, WHETHER AS A RESULT OF BREACH OF CONTRACT,
WARRANTY, TORT (INCLUDING NEGLIGENCE), STRICT LIABILITY, OR ANY OTHER THEORY, INCLUDING WITHOUT LIMITATIONLABOR
OR EQUIPMENT REQUIRED TO REMOVE AND/OR REINSTALL ORIGINAL OR REPLACEMENT PARTS, LOSS OF TIME, PROFITS OR
REVENUES, LACK OR LOSS OF PRODUCTIVITY, INTEREST CHARGES OR COST OF CAPITAL, COST OF SUBSTITUTE EQUIPMENT,
SYSTEMS, SERVICES OR DOWNTIME COSTS, DAMAGE TO OR LOSS OF USE OF PROPERTY OR EQUIPMENT OR ANY EQUIPMENT OR
ANY INCONVENIENCE ARIZING OUT OF ANY BREACH OF THE FOREGOING WARRANTY OR OBLIGATIONS UNDER SUCH WARRANTY.
Illumisoft reserves the right to modify or discontinue this Warranty without notice provided that any such modification or
discontinuance will only be effective with respect to any Product(s) purchased after such modification or discontinuance.

7
SL-OM-ENG-16-09-2021
Ultra Quiet Fans Move
25,000 Cubic Feet/Hr. of
Air Through The Fixture
All Electronics Mounted In
a Removable End Cap
Features
Light Shaping
Baffle Vents
Adjustable
Apertures For
Different
Ceiling Heights
Removable
Fan Trays

8
SL-OM-ENG-16-09-2021
Upper Room Air Germicidal UVC Technology
•
254 nm germicidal UVC with the industry’s highest UVC output
•
Industry first adjustable apertures to compensate for different ceiling heights
•
Powerful integral air handling circulates room air through the UVC energy field
•
2021 IES Progress Report Winner
Construction
•
All aluminum construction except UV stabilized polycarbonate end caps
Finish
•
Polyester powder coat finish on all visible aluminum parts
Optics
•
Horizontal multicell louvers restrict stray UVC emissions below the fixture
•
Adjustable apertures can be adjusted to increase UVC output from 2.2 watts to 6.98
watts as ceiling height increases
Mounting
•
Minimum mounting height is 7’ 9” from the fixture bottom to the finished floor
•
Recommended to not have obstructions or walls less than 10 ft in front of the fixture’s
apertures
Compliance
•
This GUV product is designed to comply with UL1598 CRD SL4.8 Risk Group 0
•
UL 1598 listed GUV fixture
•
The installer must follow all the safety instructions in this manual
Warnings and Safety
•
All warnings and safety information in this manual must be strictly followed
Order Information
SL-36KT-75 75-watt UVC lamp, covers approx. 700 sq. ft
SL-36KT-75 40-watt UVC lamp, covers approx. 600 sq. ft
SL-36KT-75/40 Specifications
DIMENSIONS LENGTH 38.875" 987 MM
WIDTH 13.88" 352 MM
HEIGHT 9.95" 253MM
WEIGHT 29 LBS/13.15 KG
ELECTRICAL SL-36KT-75 INPUT WATTS @ 120-277V 113W
VOLTS 120-277
AMPS @ 120v 0.58
FREQUENCY 50-60 HZ
LAMP UVC OUTPUT 23
ELECTRICAL SL-36-KT-40 INPUT WATTS @ 120-277V 64
VOLTS 110-277
AMPS @ 120v 0.33
FREQUENCY 50-60 HZ
LAMP UVC OUTPUT 14
FAN PERFORMANCE (8 Fans) CFH 36,000
DBA @ 45
OPTION: 347V INPUT VOLTS 110-347

9
SL-OM-ENG-16-09-2021
Wide
Beam
Narrow
Beam
Set for Higher
Ceiling Heights
Set For 8-9 Ft.
Ceilings

10
SL-OM-ENG-16-09-2021
UVC Light
UVC Light
Top
View
Ceiling
Floor
9 Ft. Minimum
Ceiling Height
Sanilume UVC Distribution
7’ 9” Minimum

11
SL-OM-ENG-16-09-2021
Room Size
As a general guideline, one Sanilume with a 75-watt lamp can disinfect approximately 700 sq. ft.
(65.03 sq. m.) regardless of ceiling height, as Sanilume fixtures have adjustable apertures to emit more
UVC light as ceiling heights increase. (The installation instructions explain setting the adjustable
aperture for different ceiling heights). A Sanilume with a 40-watt lamp can disinfect approximately
600 sq. ft.
(55.7 sq. m.) regardless of ceiling height.
Sanilume Orientation in Rooms
As a general guideline, the apertures that emit the UVC light should face towards the longest
dimension of the space in a single room. For multiple fixtures in a space of various layouts and
dimensions, more light is emitted from the aperture sides of the fixture than the ends (as shown on the
top view diagram on page 3) so the fixture should be oriented to maximize the UVC light distribution
in each space. Below are some examples.

12
SL-OM-ENG-16-09-2021
Light Degradable Materials:
UVC light can degrade plastics, fabrics and other light degradable
materials. Any such materials that are within approximately 20 ft of the fixture and 7 ft. above the floor
may degrade over longer periods of time.
Occupant Contact:
Care must be taken that the UVC energy fields not be in any line-of-sight
conditions of any room occupants. Although occupants below 7 ft from the floor will be safe from UVC
over exposure, situations can occur where UVC energy may contact room occupants such as
stairs,
escalators, split-level rooms and rooms with sloped ceilings.
Glass:
UVC is blocked by glass, so occupants in spaces with glass walls will be protected from UVC
exposure
Reflections:
UVC will reflect off walls and ceilings. Ceiling reflections will be discussed in the
installation instructions in conjunction with the adjustable apertures and mounting height. Wall
reflections can potentially cause UVC exposure thresholds to be exceeded if the fixture is mounted too
close to a wall. Avoid this situation and check the UVC intensity with a spectrometer (to be discussed)
near any walls. Sanilume should be mounted to avoid having direct UVC light beams hitting any
hanging light fixtures. Reflected UVC may cause unsafe levels below 7 ft., and also UVC could degrade
any plastic parts on the light fixtures over time.
Avoid Any Potential UVC
Contact By Room Occupants

13
SL-OM-ENG-16-09-2021
Voltage:
Verify the voltage in the electrical circuits supplying the fixtures. Sanilume comes standard
with a universal input voltage of 110-277 VAC. A 347VAC input option is available.
Circuits:
All Sanilume fixtures need to be on a separate dedicated circuit so that they may be turned
off for fixture maintenance, building maintenance, and emergency situations. The wall switches need to
be
readily accessible and clearly marked
so that the fixtures may be turned off when required.
Lamps:
Frequent on/off cycling of UVC lamps significantly lowers the lifespan of the lamp. It is
recommended that the fixtures be left on 24/7 and the lamps be changed once per year.
Sanilume Model Choice:
The Sanilume SL-36KT-75 has a 75-watt UVC lamp, and the Sanilume
SL-36KT-40 has a 40-watt UVC lamp.
Spaces that have walls within 10 ft. of the fixture (not
recommended)
should use the SL-36KT-40
to avoid wall reflections that may exceed safety thresholds.
In general, the higher the UVC output, the greater the efficacy.
We recommend the 75-watt SL-36KT-75
version unless
wall reflections are an issue.
Installation:
Sanilume fixtures have a configuration like that of standard pendant light fixtures. The
mounting and electrical hookup is essentially the same. Qualified electricians should have no problem
installing Sanilume fixtures. Please consult our installation manual and video. All necessary hanging
hardware for drywall ceilings or suspended ceilings is included with every Sanilume. (electrical
connection hardware such as junction boxes, branch circuit wiring etc. are not included)
UVC Checking:
During installation, the UVC intensity levels
need to be verified below 7 ft. and at any areas of concern such
as walls and stairs as previously discussed. A calibrated hand-
held spectrometer will be required to do so. We highly
recommend that the end user purchase their own spectrometer
so that UVC levels may be verified on an ongoing basis.

14
SL-OM-ENG-16-09-2021
The
Sanilume
fixture is recommended for use in rooms with a ceiling height of 9 feet or more and where
occupants remain for prolonged periods.
The minimum ceiling height under any circumstances is 9 ft with a
fixture mounting height of 7’ 9” from the finished floor to the bottom of the fixture.
Mounting Height & Ceiling Reflections
1.
The minimum ceiling height for Sanilume installation is 9 ft
.
2.
Sanilume fixtures come from the factory set for a ceiling height of 9’, with their apertures set to the
4th hole and a mounting height of 7’ 9” from the finished floor to the bottom of the fixture tip. Table
1 shows the recommended mounting heights and aperture settings for various ceiling heights.
These settings were calculated using a Sanilume SL-36KT-75 in a room having a suspended ceiling
grid with ceiling tiles. Measurements using a laboratory quality UV irradiance meter were taken, with
the readings being under 0.2 /2below 7 ft. in height from the finished floor.
Important Note: There are wide variations in reflectivity between different ceiling surfaces which will affect the
amount of UVC that is reflected downwards towards room occupants. It is mandatory to verify that the
maximum UCV irradiance levels are below 0.2
/
at any place in the room below 7
ft. in height from
the finished floor.
3.
The aperture settings on Sanilume fixtures dictate both the amount of UVC emitted from the fixture
and the upward angle of distribution. As the aperture is opened, UVC output increases, and the beam
width is increased (the angle of the upper side of the beam increases). Accordingly, a wider aperture will
cause more UVC energy to strike the ceiling and at steeper angles, which will increase the UVC levels
below the fixture. This can cause unsafe levels of UVC below the 7 ft. height if the aperture setting are
too wide and/or the ceiling reflectivity is too high.

15
SL-OM-ENG-16-09-2021
Floor
7 ft.
Ceiling
Wide Aperture Setting
Un-Safe: Over 0.2 /2
Floor
7 ft.
Ceiling
Narrow Aperture Setting
Safe: Under 0.2 /2
Fixture Mounting Heights
& Aperture Adjustment
Site Planning:

16
SL-OM-ENG-16-09-2021
Thoroughly Review the Site Planning Guide Before Beginning.
There are several factors that must be considered before
installing Sanilume fixtures.
General Rule #1.
The optimal Sanilume mounting height for spaces with higher ceiling heights will
be the height that maximizes the irradiated space above the Sanilume, while not exceeding the
irradiance thresholds below 7 ft. If the fixtures need to be mounted higher for aesthetic reasons,
the effectiveness of the fixture may be a bit lower but will still give excellent performance.
General Rule #2.
If the ceiling reflections are too high, lower the aperture setting.
General Rule #3.
If the reflections from the top louvers in the fixture are too high, then raise the
Sanilume closer to the ceiling.
Low Aperture Setting.
A small amount of UVC
reflects downwards from the top louvers. For a 9 ft.
ceiling height and the bottom of the fixture
mounted at the recommended 7’ 9” from the floor,
the maximum UVC reflections will be in the safe
range.
Cut-Away View
High Aperture Setting.
When the apertures are fully
open, the fixture will reflect a lot more UVC at a
much shallower angle and much further out from
the fixture. High aperture settings require high
ceiling heights.
High Aperture Setting
Fixture Mounting Heights &
Aperture Adjustment
Site Planning:

17
SL-OM-ENG-16-09-2021
Ceiling reflections.
Reflective ceiling and exposed duct materials such as aluminum will greatly
increase the potential for ceiling reflections being at an unsafe level. In such cases, ceiling to
fixture distances can be increased and the aperture can be at a lower opening setting.
Suspended Light Fixtures.
Suspended light fixtures near the Sanilume and in line-of-sight of the
UVC can reflect UVC downwards. It may be better to mount Sanilumes above any suspended
light fixtures.
Ceiling
Cut-Away View
With low ceiling heights (9 ft. min) and a high aperture setting, the ceiling
reflections will be relatively steep, which will cause a shorter travel distance with
much higher UVC reflected intensity closer to the fixture. This would cause unsafe
levels below 7 ft from the floor with lower ceiling heights. Floor
Ceiling
With low ceiling heights (9 ft. min) and a low aperture setting, the ceiling
reflections will be relatively shallow, which will cause a longer travel distance with
lower UVC reflected intensity further out from the fixture. Floor
Fixture Mounting Heights
& Aperture Adjustment
Site Planning
:

18
SL-OM-ENG-16-09-2021
Aperture Adjustment & Mounting Height
Ceiling
The fixture will come from the
factory with the apertures set at a
factory recommended setting for
the minimum ceiling height of 9
ft, with the aperture screws
installed on the 3rd hole from
the bottom of the aperture, and a
recommended mounting height
of 7’ 9” from the finished floor to
the bottom tip of the fixture.
Table 1
Ceiling
Height
"A"
Aperture
Screw
Hole
"B"
Ceiling to
Bottom of
Fixture
"C"
Floor to
Bottom of Fixture "D"
9'
3
1' 3"
7' 9"
9'6"
4
1' 6"
8'
10'
5
1' 9"
8' 3"
10'6"
6
2'
8' 6
11'
7
2' 3"
8' 9"
11'6"
7
2' 6"
9'
12'
8
3'
9'
12'6
9
3' 6"
9'
13'
10
4'
9'
14'
11
5'
9'
15'
12
6'
9'
16'
13
7'
9'
17'
14
8'
9'
18'
15
9'
9'
19'
16
10'
9'
20'
17
11'
9'
21'
18
12'
9'
22'
19
13'
9'
FOR CEILING HEIGHTS ABOVE 11' 6": FLOOR TO BOTTOM OF THE FIXTURE "D" SHOULD STAY AT 9'
FOR CEILING HEIGHTS ABOVE 22': APERTURE SCREW HOLE "B" SHOULD REMAIN AT 19
FOR CEILING HEIGHTS IN BETWEEN THOSE SHOWN, CHOOSE THE NEXT CLOSEST SETTING
If UVC levels exceed the safety limits, please make the appropriate adjustments.
Bottom
Important Note:
The fixture mounting heights and aperture settings in Table 1 are
recommended
setting only. The user/installer is responsible for ensuring that UVC levels are safe in occupied spaces.

19
SL-OM-ENG-16-09-2021
Below is a copy of our Excel Site Planning spreadsheet. You can
download this from our website sanilume.ca under the “Resources” section.
AREA #1:
CEILING HEIGHT (FT.)
9 FT. MIN
SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #2: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #3: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #4: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #5: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #6: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #7: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #8: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #9: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
AREA #10: CEILING HEIGHT (FT.) 9 FT. MIN SQ. FT. QTY 40W QTY 75W
36KT-40 40 WATTS UVC LAMP, 64 WATTS POWER - 100-277 VAC
1
36KT-75 75 WATTS UVC LAMP, 113 WATTS POWER - 100-277 VAC
Customer Requirements
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'
under 18'
18' to 23'
23' to 28'
28'-33'

20
SL-OM-ENG-16-09-2021
Installation Accessory Kit: What’s Included
1.
UVC Meter
2.
7 ft. Collapsible Rod for UVC Meter Sensor Mounting
3.
Digital level
4.
Eye & Face Protection
5.
Protective Gloves
6.
Aperture Pins (to hold an aperture open during installation and maintenance)
7.
Denatured Alcohol
Mounting Hardware Kit: What’s Included
1.
2 x 1/16” Aircraft Cables
2.
2 x T-Bar Hangers (15/16”)
3.
2 x ¼-20 Bolts/Nuts for Hangers
4.
2 x 5” Canopies
5.
2 x Bracket Bars With ¼” Studs
6.
2 x Cable Couplers for Canopies
7.
1 x Cable Gland for Canopy
8.
4 x Cable Ties
9.
UVC Measurement Quick Start Guide
10.
Guide to: Safety Precautions,
Site Planning,
Installation,
Operation,
Maintenance
This manual suits for next models
1
Table of contents
Popular Accessories manuals by other brands

Nyce
Nyce NCZ-3010 user manual

Siemens
Siemens TA1Q300 installation instructions

Galvin Engineering
Galvin Engineering CliniMix Lead Safe 100.30.79.00 Product installation guideline

Endress+Hauser
Endress+Hauser Liquiphant M FTL51C operating instructions

Hach
Hach 5740sc user manual

Enerlites
Enerlites DWHOS installation instructions