manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. IMI
  6. •
  7. Vacuum Cleaner
  8. •
  9. IMI PNEUMATEX Vento Connect V 4 Instruction sheet

IMI PNEUMATEX Vento Connect V 4 Instruction sheet

SAFETY – INSPECTION – DISASSEMBLING – DISPOSAL prescriptions
Compresso
Transfero
Vento
Pleno
Rell
SAFETY – INSPECTION
•••••Personnel
Installing and operating personnel must possess the appropriate knowledge and training.
•••••Follow the instructions
Installation, operation, maintenance and disassembly must be carried out as stated and showed in the di󰀨erent instruction
manualsmaking integral part of the delivery and in accordance with best practice. In addition to the IMI Hydronic Engineering
instructions, additional instructions from other companies may be included for the components used (e.g. backow preventers)
.
Youmust follow these instructions in the same way as the IMI Hydronic Engineering instructions.
Ifanything is unclear, please contact IMI Hydronic Engineering customer service.
•••••Testsfor commissioning and periodic inspections
Testrequired for commissioning and periodic inspections must be performed according to the regulations in the country
where the device is installed and operated. There are no unied international regulations for the acceptance test prior to
commissioning and periodic inspections. It is usually the vessels that determine how the installation is classied.
These are CE type-tested in accordance with guideline PED/2014/68/EU for pressurised equipments. Forperiodic
inspections, openings are provided for ange-type or endoscope inspections.
•In Switzerland, Compresso does not require autorisation from the SVTI if the installation is protected in such a way that
psCH is not exceeded. Vesselswith psv x V up to 3000 bar*litres do not require inspection by the SVTI.
Following combinations withTecBox are recommended:
Primary vessel (2) TecBoxsafety valve (SV)
C 10 C15
≤ 1000 litres 3 bar on request
≤ 800 litres 3.75 bar on request
≤ 700 litres 4.2 bar on request
≤ 600 litres 5 bar on request
≤ 500 litres 6 bar 6 bar
≤ 300 litres – 10 bar
•ForTransfero as many extension vessels as required can be connected to the primary vessel. The CE-approved 2 bar
safety valve protects the vessels from inadmissible pressures. In Switzerland, SVTI inspection is not required for these
types of vessels.
•Backow preventer BA: Perform inspection and maintenance in accordance with EN 1717 and the rules in the operator’s
country. Functional testing, with documentation, must normally be carried out annually. Dirt trap (SF): Inspect and clean if
necessary after a drop in the water make-up capacity or before functional testing of the backow preventer BA. We recommend
including the Pleno P / P R / P CR / BA4R in the maintenance cycle of the connected pressure-maintaining or degassing station.
Follow the maintenance instructions for Rell softening modules. The Pleno P / P R / P CR / BA4R can work as an accessory in
systems requiring technical inspections (Compresso | Transfero) and can be included as part of the inspection.
•••••Place of installation
The access to the place of installation must be restricted to trained and specialised personnel. The oor statics must be able
to support the maximum operating and installation conditions. Connections for electricity,communication, main water and
waste water must correspond to the requirements of the device.The room must be thouroughly ventilated. Do not store
ammable, explosive materials near the pressure vessel. Pressurized containers (eg Compresso expansion vessels) must
be protected against external re, at least according to national regulations.
•••••Waterquality
IMI Hydronic Engineering devices are designed to maintain pressure, to degass or to make-up and/or treat water in closed
heating, solar and cooling systems with water that contains no aggressive or toxic agents.The entire system must be
dimensioned and operated in such a way as to minimise the amount of oxygen admitted through the make-up water or
through permeable components. Water treatment systems are to be dimensioned, installed and operated according to the
current state of the art.
•••• Electrical connection
The electrical and the communication wiring and connections should be carried out by a qualied electrician, in accordance
with current local regulations.The devices and the potential free outputs must be disconnected from the electrical supply
before working on electrical components.
Protection on the supply to be done by the contractor:
Compresso C2.1, C10.1; C10.2; C15; CX: 10 A
Compresso C15.2: 16 A
Transfero range 4, 6, 8, 10, 14 = 1 x 230 V: T.1: 10 A
T.2: 16 A
Transfero 19, 25 = 3 x 400 V: 10 A
Vento range 2, 4, 6, 8, 10, 14 = 1 x 230V: 10 A
Vento range 19, 25 = 3 x 400 V: 10 A
Pleno PI9.1; PI6.1; PIX: 10 A
Pleno PI9.2; PI6.2: 16 A
Pleno P BA4R: not applicable
Residual current device (RCD) following local regulation.
If installed in residential building we recommend a commercially available line lter to the junction box.
WXMOIN00001
07.2019
en
de
fr
nl

WVMOIN0005
10.2019
Vento Connect
V 4 - 14
INSTALL
www.imi-hydronic.com
1
2
2
1
3
≥600
+5°C - +40°C
1x230V
≥400
Swm
max. qwm > 1300 l/h
(Rell 6000/12000,
Rell Demin 2000/4000)
max. qwm < 1300 l/h
(Rell 16000/36000/48000,
Rell Demin 13500/18000)
4
Vento V.1
Sin
Sout
Optional
Pleno / Pleno Refill
Swm
Pleno P BA4 R
Pleno P AB 5
Pleno P AB5 R + Pleno Refill
Pleno P BA4 R + Pleno Refill
WM
V 10/14
Sin1 Sout
Vento V.1 E(C)
TecBox
V1
V3
PT
SYS
PT
ECO
PT
W
FL
Swm
Sout
Swm
Sin
V.4_, V.6_, V.8_ V.10_, V.14_
V_4.1 V_6.1 V_8.1 V_10.1 V_14.1
dpu min bar 1 1,5 2 3,5 5,5
dpu max bar 2,5 3,5 4,5 6,5 10
Sin1 Sout Swm
Ts min °C 0 0 0
Ts max °C 90 90 65
5
 tr≤90°C
Vento V.1 E +
Pleno P BA4R
 tr>0°C
Vento V.1 EC +
Pleno P AB5 R +
PlenoRell
DNe
V_4.1 V_6.1 V_8.1 V_10.1 V_14.1
L max 10 m DNe 25 25 25 25 25
L max 20 m DNe 25 25 25 25 25
L max 30 m DNe 32 32 32 32 32
tR
Q
psvs
Hs
t
P
ZUT
tmax
DSV...DGH
> 500 mm
Statico SD/SU
min SD 80
DLV
Zeparo G Force
DNe
Sin1Sout
Swm
pw 2 - 10 bar
tw 5 - 65 °C Vento
Connect
TecBox
Sin1Sout
Swm
DNe
tR
Q
psvs
Hs
t
P
ZUT
tmax
DSV...DGH
> 500 mm
Statico SD/SU
min SD 80
DLV
Zeparo G Force
Sin1
DNe
Sout
Vento
Connect
TecBox
Swm
pw 2 - 8 bar
tw 5 - 30 °C
6
230V/50 Hz
10A / 3 x 1,0 mm²
5
1 2
LPE
N
LPE
N
34
6
1!
BrainCube
Connect!
#1-5
V.1 = 10A
www.imi-hydronic.com
7
P1
Pumpe
Pompe
Pump
V3
Pumpen-
ventil
Vannes de
pompe
Pump valve
WM
Nachspeise-
ventil
Vanne
d`appoint
d`eau
Water make
up valve
V1
Überström-
ventil
Vanne de
decharge
Spill valve
Netzversorgung
Alimentation
electrique
Network supply
230V/50 Hz
10A / 3 x 1,0 mm²
Gerätestecker
Fiche
Main plug
16 A
*A
max. 2A Leitungsabsicherung
bauseits
Protection de la ligne max. 2A par l
`installateur
max. 2A line protection by
contractor
Meldungen Gebäudeleittechnik
Programmierbar, Zuordnung nach „Menü Parameter“
Report de messagevers la GTC, affection siuvant
menu-parametres
Building control reports, allocation acc. to
menu-parameter
C NO C NO C NO
*A
Achtung: Fremdspannung
Attention: tension externe
Attention: external voltage
BN
BU
GNYE
BN
BU
GNYE
BN
BU
GNYE
BN
BU
GNYE
BN
BU
GNYE
M
1 ~
LINE P/C1 V1 V3 V4 WM V2 P/C2 OD1OD2 OD3 OD4
L N PE L N PE L N PE L N PE L N PE 13 14 13 14 13 14 13 14
Klemmen Ausführung V
Version des bornes V
Terminal execution V
230 V 50 Hz
F201
Sicherung/ fusible/ fuse
10 AT / 250V / 5x20
230V/50 Hz
24V
Sensor Anla-
gendruck
PT SYS
Capteur de
pression
PT SYS
Pressure
sensor
PTSYS
Sensor
Vakuum
PT W
Capteur de
vacuum
PT W
Vacuum
sensor PT W
ECO
Schalter
PT ECO
Contacteur
Eco
PT ECO
Eco switch
PT ECO
GN
BN
GN
BN
GN
BN
GND IN + GND IN + GND IN +
Klemmen Ausführung V
Version des bornes V
Terminal execution V
SELV
PE
2
1
PE
2
1
PE
2
1
IA5 IA4 IA3 IA2 IA1 ID4 ID1ID3 ID2 OA2 OA1 IDA2 IDA1
OUT +
P
OUT +
P
OUT +
P
8
www.imi-hydronic.com
We reserve the right to introduce technical alterations without previous notice.
P
umpe 1 Sicherung F20
0
1
0 AT / T
y
p: 5
x
20
q
NPN
S
HIEL
D
S
HIEL
D
R
S 485
US
B
RS
458
L
AN
/
E
t
he
rn
e
t
A B
S
A‘ B‘
S
IN OU
T
Jumper (RS485)
o
ff
=
Off
en
/
stationne‘
/
ope
n
on =
G
esteckt
/
branche‘
/
connect
G
ND
IN
G
ND
IN
G
ND
+
I
N
A B
S
A‘ B‘
S
ID6 ID5 IDA3
q
NP
N
S
HIEL
D
S
HIEL
D
RS
485
ID6 ID5 IDA3
US
B
RS458
LAN
/
E
t
he
rn
e
t
A B
S
A‘ B‘
S
IN OU
T
Jumper (RS485)
off = Offen / stationne‘ / o
p
en
on = Gesteckt / branche‘ / connect
GND
IN
GND
IN
G
ND
+
IN
A B
S
A‘ B‘
S
M
1
~
LINE P/C1 V
1
V
3
V
4
WM V2 P
/C
2OD1OD2
O
D3 OD
4
L
N
PE
L
N
PE
L
N
PE
13 14 13 14 13 14
Klemmen Aus
f
ührung
C
V
ersion des bornes
C
T
e
rmin
a
l
e
x
ecu
ti
o
n
C
230
V 5
0
Hz
F2
0
1
S
icherung
/
f
usible
/
f
use
1
0 A
/
250V
/
5x20
Vento
Vento
Vento
Compresso
Compresso
Compresso Connect

This manual suits for next models

4

Popular Vacuum Cleaner manuals by other brands

IKH XK8002 instruction manual

IKH

IKH XK8002 instruction manual

Sencor SVC 52BK user manual

Sencor

Sencor SVC 52BK user manual

Russell Hobbs 14045 Instructions, troubleshooting guide and guarantee

Russell Hobbs

Russell Hobbs 14045 Instructions, troubleshooting guide and guarantee

Mastervac 054-0339-8 instruction manual

Mastervac

Mastervac 054-0339-8 instruction manual

Hyundai VC 615B instruction manual

Hyundai

Hyundai VC 615B instruction manual

LG LRV5900 owner's manual

LG

LG LRV5900 owner's manual

Kenmore AllergenSeal DU2109 user manual

Kenmore

Kenmore AllergenSeal DU2109 user manual

Kenmore ASPIRADORA 116.34728 owner's manual

Kenmore

Kenmore ASPIRADORA 116.34728 owner's manual

Montgomery Ward V2811 instruction manual

Montgomery Ward

Montgomery Ward V2811 instruction manual

Argos VCB32A13S instruction manual

Argos

Argos VCB32A13S instruction manual

Kärcher IVR-L 100/24-2 manual

Kärcher

Kärcher IVR-L 100/24-2 manual

Shark HV300NZ owner's guide

Shark

Shark HV300NZ owner's guide

PRIXTON THUNDER manual

PRIXTON

PRIXTON THUNDER manual

Rowenta AIR FORCE RH8657GA manual

Rowenta

Rowenta AIR FORCE RH8657GA manual

Windsor Sensor 10120220 instructions

Windsor

Windsor Sensor 10120220 instructions

Black & Decker 90510266 instruction manual

Black & Decker

Black & Decker 90510266 instruction manual

Vax W91-RS-S Series instruction manual

Vax

Vax W91-RS-S Series instruction manual

Simplicity S20EZM owner's manual

Simplicity

Simplicity S20EZM owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.