Inovonics EH410R User manual

5.3.19 357-00016-01 Rev A © Inovonics, 2019 - www.inovonics.com
EH4104R Single Zone Fire RF Receiver with
Relays
Installation Instructions
1 Overview
The EH4104R single zone fire RF receiver with relays is designed for use
with the Inovonics EH1115EOL EchoStream single input fire RF transmitter
to monitor water flow and pressure in piping and post indicator valves to
send an alert when a fire protection system has been activated.
The EH4104R single zone fire RF receiver with relays allows you to add a
transmitter to any application. With diversity reception and advanced signal
processing, Inovonics EchoStream technology is designed to minimize
dead spots in transmission areas.
1.1 Installing an Inovonics System
An EchoStream survey kit should be used to establish an EchoStream
system. The EchoStream survey kit measures the signal strength of high-
power repeater and sensor messages to help optimize your EchoStream
system.
Note: For more information about the EchoStream survey kit, see the
EN7017 Survey Kit and App Installation and Site Survey Instructions.
Caution: The EchoStream system should be tested regularly to ensure
operation. To test: place the system in test mode, activate an end device,
and ensure an appropriate response.
1.2 RF Signal Propagation
While wood, drywall and glass usually let the RF signals pass, some
materials may inhibit or attenuate radio frequency (RF) signal propagation
by blocking, reflecting, deflecting or absorbing RF signals.
Consider anything between transmitter and the receiver. Is there concrete
and steel construction? Are there earthen berms or hills? Are there a lot of
trees? The device should be mounted such that it is least affected by these
elements.
For best results, the transmitter should be mounted at the optimal height to
achieve line of sight to the receiver. Usually this means it will be mounted
as high as possible.
Following are some typical obstacles to RF signal propagation:
1.3 Inovonics Wireless Contact Information
If you have any problems with this procedure, contact Inovonics Wireless
technical services:
• E-mail: [email protected].
• Phone: (800) 782-2709; (303) 939-9336.
1.4 EH4104R Front Panel
Figure 1 EH4104R receiver LEDs and buttons
ARF initiating device alarm LED
BRF initiating device tamper LED
CRF initiating device low battery LED
DRF initiating device inactive LED
EPower LED
FRF initiating device number LEDs
GReview button
1.5 EH4104R LEDs
Normal Operating Mode
Review Mode
Press and release button on the EH4104R front cover. Review mode times
out after ten seconds.
Material Affect Recommendation
Metal construction,
including ductwork;
pipes; studs; stucco,
plaster or concrete with
wire mesh; satellite
dishes, metal-lined
rooms such as walk-in
coolers or freezers;
metal siding, safes, etc.
Can reflect,
absorb and/or
disrupt RF
signals.
Perform a site survey
using an Inovonics
wireless survey kit to
verify the RF signal is
acceptable.
Completely enclosed
metal boxes/enclosures.
Can restrict RF
signals.
Solar panels, cinder
block walls, windows
with built-in solar tinting.
Can absorb and/
or reflect RF
signals.
Vegetation. Can attenuate
RF signals. The
RF environment
can alter as
trees shed or
sprout leaves.
Automobile and truck
traffic.
Can disrupt RF
signals.
Mount Inovonics
devices at a height
sufficient to achieve
line of sight above
traffic.
LED Event Relay
Alarm and 1 Alarm activation. Relay 1 is on until the
condition clears.
Tamper Initiating device case
tamper or EOL resistor
trouble.
Relay 5 is latched on
until EH4104R is reset.
Battery Initiating device low
battery warning.
Relay 5 is latched on
until EH4104R is reset.
Inactive Initiating device not heard
for more than three
minutes.
Relay 5 is on until the
condition clears.
Decode Valid message was received. Decode LED is visible
only with the cover removed.
LED Description
Alarm and 1 Last message from initiating device indicated alarm.
Tamper and 1 Last message from initiating device indicated tamper.
Material Affect Recommendation
A
B
D
E
F
G
C

5.3.19 357-00016-01 Rev A © Inovonics, 2019 - www.inovonics.com 2
1.6 EH4104R Internal Components
Figure 2 EH4104R internal components
1.7 What’s in the Carton
• Two drywall anchors.
• Two mounting screws.
• Three housing screws.
• Two pieces double-sided mounting tape.
• One frequency band selection jumper.
2 Installation and Startup
2.1 Installation Notes
• These products are designed to be maintained by professional
security technicians.
• Products are tested for indoor use.
• All products should be manually tested weekly.
2.2 Connect Cabling
EH4104R Receiver Wiring
Connect Power Cabling
Caution: Incorrect connections may cause damage to the unit.
Note: All wiring shall be installed in accordance with the requirements of
the National Fire Alarm and Signaling Code, NFPA 72.
Before beginning startup, you will have to connect power to the receiver. To
connect power to the receiver:
1. Use a small screwdriver to press the housing release tab on the top or
bottom of the receiver; separate the housing.
2. Connect power cabling to the Power and GND connections.
• Power source shall be 11-14 VDC. Power supply must be listed UL
1481, regulated, power limited power supply.
• Use 18 - 22 gauge wire for all cabling, and ensure torque on the screw
terminals does not exceed 7 inch-pounds.
• Wire lengths must not exceed three feet.
Connect Input/Output Cabling
1. Optionally, connect a momentary switch to the reset input and ground
(Figure 3, “EH4104R terminals”).
• The reset input circuit permits installation of a remote momentary
normally open (N/O) switch to clear faults, unlatch outputs, and reset
the receiver to a normal state.
2. Connect cabling to the output terminals.
• The EH4104R provides five Form-C relays, described below.
Figure 3 EH4104R terminals
Relay 1: Wireless alarm.
Relay 2: RF jam.
Relay 3: Power loss.
Relay 4: Receiver case tamper.
Relay 5: Wireless trouble (tamper, low battery and inactive).
Battery and 1 Last message from initiating device indicated low
battery.
Inactive and 1 Initiating device was not heard for more than three
minutes. Communication has not been restored.
AHousing release
tabs
BPower (11-14
VDC)
CGND connection
DOutput terminals EAdvance button FReset button
GReset input HNot used INot used
JProgram button KDecode LED
LED Description
A
B
C
D
HIG
AA
K
E
J
F
EH4104R
Function
EH4104R
Terminal
Panel
Terminal Description
12VDC power
source
Vs (POS) n/a See note 1
below
Ground GND (NEG) n/a
Relay 1 Com 1 Zone 1 - RF initiating
device alarm;
see note 4
below
NO Zone 1 +
Relay 2 Com 2 Zone 2 - RF receiver
jammed
NO Zone 2 +
Relay 3 NO Zone 3 + Receiver
power loss;
see note 2
below
Com 3 Zone 3 -
Relay 4 Com 4 Zone 4 - RF receiver
tamper
NO Zone 4 +
Relay 5 Com 5 Zone 5 - RF initiating
device trouble
NO Zone 5 +
Not used, use
relay 2
Jam n/a n/a
Not used, use
relay 4
Tamper n/a n/a
Vs
Jam output
Ground
Tamper
Reset input
Caution: Incorrect
connections may cause
damage to the unit
NC
COM 1
NO
NC
COM 2
NO
NO
COM 3
NC
NC
COM 4
NO
NC
COM 5
NO
Do not connect jam and/or tamper
open collector outputs

5.3.19 357-00016-01 Rev A © Inovonics, 2019 - www.inovonics.com 3
1. Listed UL 1481, regulated, power limited power supply.
2. Relay 3 is kept activated to monitor power. Note that the NO and NC
terminal positions are reversed.
3. Optional remote reset can be activated by a momentary short between
ground and reset terminals.
4. The zone type (point function) shall be set at fire alarm or supervisory,
depending on application.
3 Registering the Transmitter
3.1 Quick Setup
1. Press the advance button one time to select the first initiating device.
2. Press the program button once to select the default programming
options.
3. The first initiating device number will be flashing, indicating it is awaiting
the transmitter’s reset message; press the transmitter’s reset button.
Note: After registering the transmitter, there is no need to exit programming
mode. The receiver is normal operation once the transmitter’s reset button
has been pressed.
Note: The registration is not complete until all LEDs turn off and the
initiating device number lights.
All of the alert LEDs will turn off when the receiver has received the
transmitter’s registration message, and the initiating device number LED
will light for two seconds. This indicates the receiver has received the
transmitter’s registration message. If this does not occur, press reset on the
transmitter again.
3.2 Mount the Receiver
Caution: Mount the receiver in a location removed from metal. Metal
objects (duct work, wire mesh screens, boxes) will reduce RF range.
Note: The EH4104R must be in the same room as the control panel.
1. Use the provided anchors and screws to mount the receiver in a
location accessible for future maintenance, making sure the housing is
flush with the wall and the back tamper switch is actuated.
2. After the transmitter has been registered, perform a walk test, activating
each transmitter assigned to the receiver and ensuring a good signal.
4 Return to Factory Configuration
The EH4104R can be returned to factory defaults using the following .
Caution: The factory config will erase all programmed initiating device,
output, and language information.
To restore the factory configuration defaults to the receiver:
1. Hold down the reset and advance buttons.
2. With the buttons held down, cycle power.
3. Wait for the switch LED to light, then release buttons.
5 Specifications
Compatible transmitter: EH1115EOL.
Compatible control panel: Compatible listed UL 864 control panel with a
minimum of five conventional initiating device circuits (IDC).
Housing: 6.38" x 3.60" x 1.10" (162 mm x 92 mm x 28 mm).
Operating environment: 32°- 140°F (0°- 60°C), 93% relative humidity, non-
condensing.
Power requirement: 11 - 14 VDC; 400 mA; listed UL1481, regulated, power
limited power supply.
Current consumption: Approx. ~400 mA max with all five relays energized.
Output specifications: Form C relay 1A @ 28 VDC, 0.5A @ 30 VAC
resistive load.
Reset input: Contact closure, momentary low.
Receiver type: Frequency hopping spread spectrum.
Operating frequency: 902-928 MHz.
Number of initiating devices/transmitters: One.
Number of alarm outputs: One Form C relay output.
Number of trouble outputs: Four form C relay outputs.
UL listings: UL 864 10th Edition.
6 UL Requirements
• The receiver tamper and transmitter tamper cannot be combined in
one loop.
7 Television and Radio Interference
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance
with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Optional
remote reset:
External reset
circuit
Reset Aux relay: NO Reset RF
receiver
Ground GND (NEG) Aux relay:
Common
See note 3
below
EH4104R
Function
EH4104R
Terminal
Panel
Terminal Description

This page left intentionally blank.

5.3.19 357-00016-01 Rev A © Inovonics, 2019 - www.inovonics.com
EH4104R Single Zone Fire RF Receiver with Relays
Caution: This document must be framed and mounted in view adjacent to the EH4104R single zone fire RF receiver with relays
Normal Operating Mode
Review Mode
Press and release button on the EH4104R front cover. Review mode times out after ten seconds.
LED Event Relay
Alarm and 1 Alarm activation. Relay 1 is on until the condition clears.
Tamper Initiating device case tamper or EOL resistor trouble. Relay 5 is latched on until EH4104R is reset.
Battery Initiating device low battery warning. Relay 5 is latched on until EH4104R is reset.
Inactive Initiating device not heard for more than three minutes. Relay 5 is on until the condition clears.
LED Description
Alarm and 1 Last message from initiating device indicated alarm.
Tamper and 1 Last message from initiating device indicated tamper.
Battery and 1 Last message from initiating device indicated low battery.
Inactive and 1 Initiating device was not heard for more than three minutes. Communication has not been
restored.
Alarm
Tamper
Battery
Inactive
Initiating device number
Review
button
Power
Table of contents
Other Inovonics Security System manuals
Popular Security System manuals by other brands

Risco
Risco lightsys 2 Quick installation guide

Honeywell
Honeywell LYNX Touch L5210 Series Installation and startup guide

Trend Micro
Trend Micro TippingPoint Series Hardware Installation and Safety Guide

Honeywell
Honeywell VISTA-128FBP user guide

Hidden
Hidden COVSMDVR user manual

Eaton
Eaton Symphoni LX Base product manual