INVT HT1101S User manual

Rack-online UPS
(1-3kVA)
UserManual

ImportantSafety Instructions
RackOnline 1-3kUPSUserManualI
ImportantSafetyInstructions
Save these instructions
This manualcontainsimportant safetyinstructions.Read allsafetyand operating instructions
before operating theuninterruptiblepower systems (UPS).Adhere toall warnings on the unit
and inthis manual.Followall operating and user instructions. This equipmentcan beoperated
byindividuals without previoustraining.
Maximumload must notexceed thatshownon the UPS rating label.The UPS is designed for
dataprocessingequipment.Ifuncertain,consult your dealer or localrepresentative.
The 1-3kVA@200/208/220/230/240VACisdesigned for usewithathree-wire input (L,N,G).
WARNING
Thebatterycanpresentariskofelectricalshock and high
shortcircuitcurrent.Following precautionsshouldbe
observedbeforereplacing thebattery.
lWear rubber glovesand boots.
lRemoverings,watchesand other metalobjects.
lUsetoolswithinsulated handles.
lDo not lay toolsor other metalobjects on the batteries.
lIf the batteryis damagedinanywayor shows signsofleakage, contactyour local
representativeimmediately.
lDo not disposeofbatteriesinafire.Thebatteriesmayexplode.
lHandle, transport and recyclebatteries inaccordancewithlocalrepresentative.
WARNING
Although theUPS hasbeendesignedand manufacturedto
ensurepersonal safety,improperuse canresultinelectrical
shock orfire.Toensuresafety,observethefollowing
precautions:
lTurn off andunplug theUPS beforecleaningit.
lClean the UPS withadrycloth.Donot useliquidor aerosolcleaners.
lNever block orinsert anyobjects intotheventilation holesor other openings oftheUPS.
lDo not placethe UPS power cord where itmight bedamaged.

Contents
II RackOnline1-3k UPSUser Manual
CONTENTS
Important SafetyInstructions....................................................................................................I
Contents..................................................................................................................................II
1.ElectromagneticCompatibility...............................................................................................1
2. Introduction .........................................................................................................................2
3.SystemDescription...............................................................................................................5
3.1Transient Voltage Surge Suppression(TVSS)and EMI/FRIFilters .........................5
3.2Rectifier/Power Factor Correction (PFC) Circuit.................................................5
3.3Inverter....................................................................................................5
3.4BatteryCharger.........................................................................................5
3.5DC-to-DC Converter...................................................................................6
3.6Battery ....................................................................................................6
3.7DynamicBypass........................................................................................6
4. ProductSpecification and performance...............................................................................7
4.1ModelDescription ......................................................................................7
4.2Product Specification and Performance ...........................................................7
5. Installation...........................................................................................................................9
5.1Unpacking and Inspection............................................................................9
5.2MechanicalInstallation................................................................................9
5.2.1Notesfor installation.............................................................................................9
5.2.2Tower Installation.................................................................................................9
5.2.3RackInstallation.................................................................................................12
5.3Operating procedure for connectingthe long backup timemodelUPS withthe external
battery .......................................................................................................13
6. Controls and Indicators......................................................................................................15
6.1Operation andDisplayPanel ......................................................................15

Contents
RackOnline 1-3kUPSUserManualIII
6.2AudibleAlarm..........................................................................................18
7. Operation..........................................................................................................................19
7.1Operation Mode.......................................................................................19
8. BatteryMaintenance..........................................................................................................20
8.1Battery maintenance.................................................................................20
8.2ReplacingInternalBattery Pack...................................................................20
9. Notesfor batterydisposalandreplacement procedures....................................................24
9.1BatteryDisposal ......................................................................................24
9.2BatteryReplacementProcedures.................................................................24
10.Troubleshooting..............................................................................................................25
10.1Checking UPSstatus ..............................................................................25
10.2Adjustthe factorscaused the problem .........................................................25
AnnexA.IntelligentSlot.........................................................................................................29
AnnexB.EPO.......................................................................................................................30
Annex C. RatedParametersSetting......................................................................................29
Annex D.BatteryKitAssembly (option).................................................................................34


ElectromagneticCompatibility
RackOnline 1-3kUPSUserManual1
1.ElectromagneticCompatibility
*Safety
IEC/EN62040-1-1
*EMI
Conducted Emission.........IEC/EN62040-2 ClassA
Radiated Emission............IEC/EN62040-2 ClassA
*EMS
ESD..................................IEC/EN61000-4-2
Level4
RS....................................IEC/EN61000-4-3
Level3
EFT..................................IEC/EN61000-4-4Level4
SURGE............................IEC/EN61000-4-5
Level4
LowFrequencySignals..............:IEC/EN61000-2-2
Warning: Thisisaproductfor commercialand industrialapplicationinthe second
environment-installation restrictions or additionalmeasuresmaybe needed to
prevent disturbances.
NOTICE
Thisisaproductfor restrictedsalesdistributiontoinformedpartners. Installationrestrictionsor
additionalmeasures maybeneeded toprevent radiointerference.
Operated the UPSinanindoor enviromentonlyinan ambienttemperature range of
0-40°C(32-104°F). Installitinaclean environment,free frommoisture, flammableliquids,
gasesand corrosivesubstance.
ThisUPScontainsno user-serviceablepartsexceptthe internalbatterypack.The UPSon/off
pushbuttonsdo notelectricallyisolateinternalparts.Under nocircumstanceattempttogain
accessinternally, due tothe riskofelectricshock or burn.
Do notcontinue tousethe UPS ifthe panelindicationsare notinaccordancewiththese
operating instructionsor theUPSperformancealtersinuse.Refer allfaulttoyour dealer.
Servicing ofbatteriesshouldbeperformed or supervised bypersonnelknowledgeableof
batteriesand the precautions. Keep unauthorized personnelawayfromthe batteries.Proper
disposalofbatteriesisrequired.Refer toyour locallawsand regulationsfor disposal
requirement.
DONOTCONNECTequipmentthatcouldoverload the UPS or demand DC currentfromthe
UPS,forexample:electricdrills,vacuumcleaners,laser printers, hairdryer oranyappliance
using half-waverectification.
Storing magneticmediaontop ofthe UPS mayresultindatalossor corruption.
Turn off and isolatethe UPSbefore cleaningit. Useonlyasoft cloth,never liquidor aerosol
cleaners.

Introduction
2Rack Online 1-3k UPS User Manual
2. Introduction
Congratulationsonyour choiceofthe uninterruptiblepower system(UPS),the UPScomesin
nominalpower ratingsof1000VA,2000VAand 3000VA.Itisdesigned toprovide conditioned
powertomicrocomputers and other sensitiveelectronic equipment.
When itisgenerated,alternating currentisclean and stable. However,during transmission and
distributionitmaybesubject tovoltage sags, spikesand completepower failure thatmay
interruptcomputer operations,causedatalossandeven damage equipment. The UPS
protects equipmentfromthesedisturbances.
The UPSisacompact,on-line UPS.Anon-line UPScontinuouslyconditionsand regulatesits
outputvoltage,whether utilitypower ispresentornot.Itsuppliesconnectedequipmentwith
clean sinewavepower. Sensitiveelectronic equipment operates best fromsinewavepower.
For easeofuse,the UPSfeaturesaLCD displaytoindicateallinformationforUPS,and
provide kindsoffunction buttons.
Fig.1FrontView

Introduction
RackOnline 1-3kUPSUserManual3
Fig.2Rear View

Introduction
4Rack Online 1-3k UPS User Manual
RS-232 communicationport.DB9type.
EPO.Shorttoactivate.
Intelligentslot
USB port. Btype.
Inputsurge protectionslot.
Inputsocket. 1KVA:IECC14,2K/3K: IECC20
Network surge protection.
OutputSocket IECC13
Externalbatteryport.Optionalfor standard model.
Batteryground
OutputSocket IECC19
Inaddition, inviewof thelong backup timerequirements,Speciallydesigned thebatterypack,
the diagrambelow:
Fig.3-1FrontViewofBatterypack
Fig.3-2 Rear ViewofBatterypack

SystemDescription
RackOnline 1-3kUPSUserManual5
3. System Description
3.1TransientVoltageSurgeSuppression(TVSS)and EMI/FRIFilters
TheseUPScomponents provide surge protectionand filter bothelectromagnetic interference
(EMI)and radiofrequencyinterference(RFI).They minimizeany surge or interferencepresent
inthe utilitylineand keep thesensitiveequipment protected.
3.2Rectifier/PowerFactorCorrection (PFC) Circuit
Innormaloperation,the rectifier/powerfactor correction (PFC) circuit converts utilityACpower
toregulated DC power for usebythe inverter whileensuring thatthe waveformoftheinput
currentused bythe UPSisnearideal.Extracting thissinewaveinputcurrentachievestwo
objects:
lThe utilitypower is used as efficiencyaspossiblebytheUPS.
lThe amountofdistortionreflected on the utilityis reduced.
Thisresultsincleaner power being availabletoother devicesinthe building not being
protected bythe UPS.
3.3Inverter
Innormaloperation,the inverter utilizethe DCoutputofthe power factor correction circuit and
inverters itintoprecise,regulated sinewaveACpower. Upon autility powerfailure,the inverter
receivesitsrequired energy fromthe battery through the DC-to-DC converter.Inbothmodes of
operation,the UPSinverter ison-line and continuously generating clean,precise,regulatedAC
output power.
3.4BatteryCharger
The battery charger utilizes energyfromthe utilitypower and preciselyregulatesitto
continuouslyfloatcharge thebatteries. The batteries are beingcharged whenever the UPSis

SystemDescription
6Rack Online 1-3k UPS User Manual
connectedtoutilitypower.
3.5DC-to-DC Converter
The DC-to-DC converter utilizesenergyfromthe batterysystemandraisesthe DC voltage to
the optimumoperating voltage forthe inverter.The converter includesboostcircuitwhichis
alsoused asPFC.
3.6Battery
The standard modelincludevalue-regulated, non-spillable,lead acidbatteriesinside. To
maintainbatterydesign life,operatethe UPSinan ambienttemperature of 14-25°C.
3.7DynamicBypass
The UPSprovides an alternatepathfor utilitypower totheconnectedload inthe unlikelyevent
of aUPS malfunction.Shouldthe UPS havean overload,over temperature or anyother failure
condition,the UPSautomaticallytransferstheconnected load tobypass.Bypassoperationis
indicatedbyan audiblealarmand illuminatedamber Bypass LED.
NOTICE Thebypasspower pathdoes NOTprotect theconnectedequipment from
disturbancesinthe utilitysupply.

Production Specification and Performance
RackOnline 1-3kUPSUserManual7
4. Product Specificationandperformance
4.1ModelDescription
This manualisapplicabletothefollowing models:
L”Model: Longbackup time, S”Model:Standard backup time
4.2Product SpecificationandPerformance
1. GeneralSpecification
Model 1K 2K 3K
PowerRating 1000VA/
800W
1000VA/
900W
2000VA/
1600W
2000VA/
1800W
3000VA/
2400W
3000VA/
2700W
Frequency(Hz)
50/60 50/60 50/60
Input
Voltage
110Vac~288Vac
Current
5.5Amax. 11Amax 16Amax
Battery
Voltage
24VDC
36VDC
48VDC
72VDC
72VDC
96VDC
Numbers
2 3 4 6 6 8
Current
50Amax
35Amax
50Amax
35Amax
50Amax
37Amax
Output
Voltage
200V/208V/220V/230V/240V
Current
5/4.8/4.5/4.3/4.2A
10/9.6/9/8.6/8.4A
15/14.4/13.5/12.9/12.
6A
Dimension
(WxDxH) mm 438*426*86 L/S)
438*477*86 L)
438*477*173 S)
Weight
(kg)
Standard
11.5 13.5 21 25 27 31
Long 7 8 9.5
2. ElectricalPerformance
Input
Model Voltage Frequency Power Factor
1-3KVA Single-phase 40-70Hz >0.98(Full load)
ModelNo. Type
11xxS Standard model
11xxL Long backupmodel

ProductSpecification and performance
8Rack Online 1-3k UPS User Manual
3. Operating Environment
Temperature Humidity Altitude Storagetemperature
0°C-40°C <95% <1000m -20°C-70°C
NOTICE IftheUPSisinstalled orused inaplacewherethe altitudeisabovethan 1000m,
the outputpower mustbe derated inuse, pleaserefer tothe following:
Altitude(M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating Power
100%
95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity Crest ratio
±1% 0.9lag
±0.5%of
normal
THD<1%@Fu
ll Linear Load
THD<6%@Fu
ll nonlinear
load
130% load:transfersto
Bypass mode after 1
minutes
150% load:transfersto
Bypass mode after 0.5
minute
3:1
maximum

Installation
RackOnline 1-3kUPSUserManual9
5. Installation
NOTICE UPSoperation insustained temperature outsidethe rangeof 14-25°C(59°-77°F)
reduces batterylife.
5.1Unpacking and Inspection
1) Unpackthe packagingand checkthepackage contents. Theshipping package contains:
1UPS
1user manual
1InputCable
1RS232 Cable
2BracketEar
1BatteryCable(For Longbackupmodelonly)
2) Inspect the appearanceofthe UPS tosee ifthere isanydamageduring transportation.
Do notturn onthe unitandnotify the carrier anddealer immediatelyifthere isany
damageor lackingofsomeparts.
5.2MechanicalInstallation
Twoinstallation modesare available:tower installation and rack installation,depending
on availablespaceanduseconsiderations.You canselectanappropriateinstallation
modeaccording totheactualconditions.
5.2.1Notes for installation
1) The UPSmustbeinstalled inalocationwithgood ventilation,far awayfromwater,
inflammablegas and corrosiveagents.
2) Ensuretheairventson the frontand rearoftheUPSarenotblockedsoasto
ensure good ventilation.
3) Condensation towater dropsmayoccur iftheUPS isunpackedinaverylow
temperature environment.Inthiscaseitisnecessarytowaituntilthe UPSisfully
dried inside outbefore proceeding installation anduse.Otherwisethere are hazards
of electricshock.
5.2.2TowerInstallation
Variousinstallationconfigurationsare available:singleUPS, singleUPSwithsingleor
multiplebatterycabinets. Theirinstallationmethods are all the same.

Installation
10 RackOnline1-3k UPSUser Manual
The installation proceduresare asfollows:
Step 1:Takeoutthe supportbasesfromthe accessories.Theirappearancesare shownin
Fig.4-1.
Fig.4-1 Support bases
Step2:Ifoptionalexternalbattery cabinets are connected totheUPS toprovide
additionalbatteryrun time,assemblethe spacers andthe support bases, asshownin
Fig.4-2.
Fig.4-2 Installing support baseswithspacers
Step3:Adjustthe directionof UPSoperation and displaypanelandLOGO.
1. Removethe frontplastic bezelcover gently, asshowninFig.4-3.
Fig.4-3 Removing the front plastic bezelcover

Installation
RackOnline 1-3kUPSUserManual11
2. Pull the operation anddisplaypanelgently, rotateit 90degreesclockwiseandsnap it
backintoposition,as showninFig.4-4
Fig.4-4 Rotating the operation anddisplaypanel
3. Pull the LOGOon the frontplastic bezelcover gently,rotateit90 degrees clockwise
and snap it backintoposition.Afterrotation,thefrontplastic bezelcover isshownin
Fig.4-5.
Fig.4-5 Rotateit 90 degrees clockwiseand snap it back intoposition
4. Restore thefrontplastic bezelcover tothe UPS.At this point,the UPS operation and
displaypaneland LOGO havebeenrotated 90degreesclockwise,whichprovides
upright viewing for users.

Installation
12 RackOnline1-3k UPSUser Manual
Step 4:Placethe UPS(and battery cabinet)on the supportbases.EachUPSneedstwo
pairs ofsupportbasestoinstall,asshowninFig.4-6.
Fig.4-6 Tower installation
5.2.3Rack Installation
1.Various installation configurations are available: singleUPS,singleUPSwithsingle
or multiple-battery. Theirinstallationmethods are allthe same.
2.Becausebatterycabinetsare too heavy,theymustbe installed first,and twoor more
installation personnelare required toinstallthematthesametime.Pleaseinstallthem
frombottomtotop.
Rackinstallation:fixthe UPS andbatterycabinet ontotherackthrough brackets.
Installationmethod:
1.Takeouttwobrackets andsixM4 ×10 screws fromtheaccessories,and fixthe
brackets ontothe UPS using the screws through installation hole, asshowninFig.4-7.

Installation
RackOnline 1-3kUPSUserManual13
Fig.4-7 Installing brackets
2.Placethe UPS ontothe guide rail inthe rack, and pushitcompletelyintothe rack
along the guide rail(itisprohibitedtomovethe UPS through the brackets).Andfix
the UPStontothe rack using the screwsthrough installation holeon the bracket, as
showninFig.4-8.
Fig.4-8 Installing UPS
5.3Operating procedurefor connectingthelong backup timemodelUPS withthe
external battery
Notice: Pleaseconnect the externalbattery atleast40AHwhilethe charge currentis 8A,
at least20AHfor 4A.otherwisemaycausedamage tothe battery.

Installation
14 RackOnline1-3k UPSUser Manual
1.The nominalDC voltage ofexternalbatterypackis24VDC/1kVA,36VDC/1kVA,
48VDC/2kVA,72VDC/2kVA,72VDC/3kVA,96VDC/3kVA.Connectinseriesthe
batteriesofthe pack toensure proper batteryvoltage.Toachievelonger backup time,
itispossibletoconnect multi-batterypacks, buttheprincipleof “samevoltage, same
type”shouldbestrictly followed.
Fig.4-9 Battery terminalconnection
2.Takeoutbatterycabledelivered withtheUPS. One endof battery cableisaplugand
the other endhas2open wires.
3.Connect the REDwire tothe “+”terminalofthe battery.Connectthe BLACKwire to
the “-“terminalofthebattery.
Notice: DONOTconnect the batteryplugtothebattery socketofUPSfirst,otherwise,it
may causeelectricshock.
4.Connecttheexternalbatteryplug tothe batterysocketon therear panel.

Controlsand Indicators
RackOnline 1-3kUPSUserManual15
6. ControlsandIndicators
6.1Operation and DisplayPanel
Fig.5Display Panel
Description ofPanel
Controls Description
ON/OFF
1.PressON/OFFtostartUPS when utilityis normal
NOTE
It onlybases on defaultsetting(manualstart)
2.PressON/OFF tostartfrombatterydirectlywhen there isno
maininput, pressagaintostartUPS upon buzzer alarms
3.PressON/OFFtoshutdowninverter whenUPS isinnormal
mode.
4.Press ON/OFFtoshutdownUPScompletelywhen UPS isin
battery mode
5.PressON/OFFtoensurethe rated parameter setting
FUNC
1.PressFUNC button totransfer indifferentmenus
2.PressFUNC button for2.5seconds tomuteoff
3.PressFUNC and ON/OFF together for 2.5secondstosetrated
parameters when onlypower supplyison
Indicators Description
This manual suits for next models
6
Table of contents