iSMA CONTROLLI SfAR-S-8DI8DO User manual

www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
SfAR-S-8DI8DO
User Manual
Expansion Module - 8 Digital Inputs, 8
Digital Outputs

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 2 of 25
Table of Contents
1 Introduction ............................................................................................................................. 4
1.1 Revision History................................................................................................................................4
2 Safety Rules.............................................................................................................................. 5
3 Module Features..................................................................................................................... 6
3.1 Purpose and Description of the Module ...................................................................................6
3.2 Technical Specification ...................................................................................................................6
3.3 Dimensions .......................................................................................................................................7
4 Communication....................................................................................................................... 9
4.1 Grounding and Shielding...............................................................................................................9
4.2 Network Termination......................................................................................................................9
4.3 Setting Module Address in RS485 Modbus Network .............................................................9
4.4 Types of Modbus Functions....................................................................................................... 11
4.5 Communication Settings............................................................................................................. 11
4.5.1 Default Settings....................................................................................................................... 11
4.6 Restoring Default Configuration ............................................................................................... 12
4.7 Watchdog........................................................................................................................................ 12
5 Indicators................................................................................................................................ 13
6 Connections........................................................................................................................... 14
6.1 Block Diagram ............................................................................................................................... 14
6.2 Power Supply Connection .......................................................................................................... 14
6.2.1 DC Power Connection ........................................................................................................... 14
6.2.2 AC Power Connection............................................................................................................ 15
6.3 Communication Bus Connection.............................................................................................. 15
6.4 Connection of Digital Inputs ...................................................................................................... 15
6.4.1 Connection of Inputs ............................................................................................................. 15
6.4.2 Connection of Encoder ......................................................................................................... 16
6.5 Connection of Digital Outputs................................................................................................... 16
6.5.1 Connection of Outputs.......................................................................................................... 16
6.5.2 Connection of Relay ............................................................................................................... 16
6.6 Quick Connector........................................................................................................................... 16
7 DIP Switch............................................................................................................................... 18
8 Input Filter .............................................................................................................................. 19
9 Module Registers.................................................................................................................. 20
9.1 Registered Access......................................................................................................................... 20

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 4 of 25
1 Introduction
Thank you for choosing our product.
This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our
professionals and serve as a description of the product without incurring any liability for
the purposes of commercial law. This information does not discharge you from the
liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded
therein.
1.1 Revision History
Rev. Date Description
3.2 25 May 2022 Rebranded
Table 1. Revision history
WARNING!
Failure to follow instructions can result in equipment damage or impede the use of
the hardware or software.

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 5 of 25
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2 Safety Rules
Improper wiring of the product can damage it and lead to other hazards. Make sure
that the product has been correctly wired before turning the power on.
Before wiring or removing/mounting the product, make sure to turn the power off.
Failure to do so might cause an electric shock.
Do not touch electrically charged parts such as power terminals. Doing so might cause
an electric shock.
Do not disassemble the product. Doing so might cause an electric shock or faulty
operation.
Use the product only within the operating ranges recommended in the specification
(temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure
to do so might cause a fire or faulty operation.
Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
Avoid installing the product in close proximity to high-power electrical devices and
cables, inductive loads, and switching devices. Proximity of such objects may cause an
uncontrolled interference, resulting in an instable operation of the product.
Proper arrangement of the power and signal cabling affects the operation of the entire
control system. Avoid laying the power and signal wiring in parallel cable trays. It can
cause interferences in monitored and control signals.
It is recommended to power controllers/modules with AC/DC power suppliers. They
provide better and more stable insulation for devices compared to AC/AC transformer
systems, which transmit disturbances and transient phenomena like surges and bursts
to devices. They also isolate products from inductive phenomena from other
transformers and loads.
Power supply systems for the product should be protected by external devices limiting
overvoltage and effects of lightning discharges.
Avoid powering the product and its controlled/monitored devices, especially high
power and inductive loads, from a single power source. Powering devices from a single
power source causes a risk of introducing disturbances from the loads to the control
devices.
If an AC/AC transformer is used to supply control devices, it is strongly recommended
to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects,
which are dangerous for devices.
Long monitoring and control lines may cause loops in connection with the shared
power supply, causing disturbances in the operation of devices, including external
communication. It is recommended to use galvanic separators.
To protect signal and communication lines against external electromagnetic
interferences, use properly grounded shielded cables and ferrite beads.
Switching the digital output relays of large (exceeding specification) inductive loads can
cause interference pulses to the electronics installed inside the product. Therefore, it
is recommended to use external relays/contactors, etc. to switch such loads. The use
of controllers with triac outputs also limits similar overvoltage phenomena.
Many cases of disturbances and overvoltage in control systems are generated by
switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they
do not have appropriate built-in noise reduction circuits, it is recommended to use
external circuits such as snubbers, varistors, or protection diodes to limit these effects.

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 6 of 25
3 Module Features
3.1 Purpose and Description of the Module
The SfAR-S-8DI8DO module is an innovative device that provides a simple and cost-
effective extension of the number of lines of input and output in popular PLCs.
The module has 8 digital inputs with configurable timer/counter option and 8 digital
outputs. In addition, terminals IN1 and IN2, and IN3 and IN4 can be used to connect two
encoders. All inputs and outputs are isolated from the logic using optocouplers. Each
channel can be individually configured in one of several modes.
The module is connected to the RS485 bus with a twisted-pair wire. Communication is via
Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast
processing and quick communication. The baud rate is configurable from 2400 to
115200.
The module is designed for mounting on a DIN rail in accordance with DINEN5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs,
power supply, and communication, which is useful for diagnostic purposes and helping to
find errors.
Module configuration is done via USB by using a dedicated computer program. It also
allows for changing the parameters using the Modbus protocol or set the Modbus
address using the DIP switches under the front panel.
3.2 Technical Specification
Power Supply Voltage 10-38 V DC; 10-28 V AC
Power consumption (with active
Modbus transmission and high
state on all outputs)
2.4 W at 24 V DC
3 VA at 24 V AC
Digital Inputs No. of inputs 8
Voltage range 0-36 V
Low state "0" 0-3 V
High state "1" 6-36 V
Input impedance 4 kΩ
Isolation 1500 Vrms
Input type PNP or NPN

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 7 of 25
Digital Outputs No. of outputs 8
Max. voltage 30 V
Max. current 500 mA
Output type PNP
Isolation 1500 Vrms
Output protection 4 A polymer fuse
Counters No. of counters 8
Resolution 32-bits
Frequency 1 kHz (max.)
Impulse width 500 μs (min.)
Temperature Work -10 °C to +50°C (14°F to 122°F)
Storage -40 °C to +85°C (-40°F to 185°F)
Connectors Power supply 2 pin
Communication 3 pin
Inputs 10 pin
Outputs 10 pin
Quick connector IDC10
Configuration mini USB
Size Height 119.1 mm (4.689 in)
Length 110.9 mm (4.366 in)
Width 22.7 mm (0.894 in)
Interface RS485 Up to 128 devices
Table 2. Technical specification
3.3 Dimensions
The appearance and dimensions of the module are shown below. The module is
mounted directly to the rail in the DIN industry standard. Power connectors,
communication, and IOs are at the bottom and top of the module. USB connector
configuration and indicators located on the front of the module.

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 8 of 25
Figure 1. Dimensions

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 9 of 25
•
•
•
•
4 Communication
4.1 Grounding and Shielding
In most cases, I/O modules will be installed in an enclosure along with the other devices,
which generate electromagnetic radiation. Relays, contactors, transformers, motor
invertors, etc., are examples of such devices. Radiation can induce electrical noise into
both power and signal lines, as well as direct radiation into the module. Whether or not
the SfAR modules are immune to such effects, the interferences must be suppressed at
their source if possible to ensure the proper functioning of the entire system.
Appropriate grounding, shielding and other protective steps should be taken at the
installation stage to prevent these effects. It is recommended to at least follow the rules
below:
line power cables must be routed with spatial separation from signal and data
transmission cables;
analog and digital signal cables should also be separated;
it is recommended to use shielded cables for analog signals, cable shields should not
be interrupted by intermediate terminals;
the shielding should be earthed directly after the cable enters the cabinet.
It is recommended to install interference suppressors when switching inductive loads
(e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for
AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must
be connected as close to the coil as possible.
4.2 Network Termination
Transmission line effects often present problems for data communication networks.
These problems include reflections and signal attenuation.
To eliminate the presence of reflections of signal from the end of the cable, the cable
must be terminated at both ends with a resistor across the line adequate to its
characteristic impedance. Both ends must be terminated since the propagation is
bidirectional. In case of an RS485 twisted pair cable, this termination is typically 120 Ω.
4.3 Setting Module Address in RS485 Modbus Network
The following table shows how to set DIP switches to determine the address of the
module. The module address is set with the switches in the range of 0 to 31. Addresses
from 32 to 255 can be set via RS485 or USB and using dedicated software tool.
Addr SW1 SW2 SW3 SW4 SW5
0 OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF
2 OFF ON OFF OFF OFF
3 ON ON OFF OFF OFF

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 10 of 25
Addr SW1 SW2 SW3 SW4 SW5
4 OFF OFF ON OFF OFF
5 ON OFF ON OFF OFF
6 OFF ON ON OFF OFF
7 ON ON ON OFF OFF
8 OFF OFF OFF ON OFF
9 ON OFF OFF ON OFF
10 OFF ON OFF ON OFF
11 ON ON OFF ON OFF
12 OFF OFF ON ON OFF
13 ON OFF ON ON OFF
14 OFF ON ON ON OFF
15 ON ON ON ON OFF
16 OFF OFF OFF OFF ON
17 ON OFF OFF OFF ON
18 OFF ON OFF OFF ON
19 ON ON OFF OFF ON
20 OFF OFF ON OFF ON
21 ON OFF ON OFF ON
22 OFF ON ON OFF ON
23 ON ON ON OFF ON
24 OFF OFF OFF ON ON
25 ON OFF OFF ON ON
26 OFF ON OFF ON ON
27 ON ON OFF ON ON
28 OFF OFF ON ON ON
29 ON OFF ON ON ON

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 11 of 25
Addr SW1 SW2 SW3 SW4 SW5
30 OFF ON ON ON ON
31 ON ON ON ON ON
Table 3. Setting module address in RS485 Modbus network, using DIP switch
4.4 Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules.
Type Beginning Address Variable Access Modbus Command
1 00001 Digital Outputs Bit
Read & Write
1, 5, 15
2 10001 Digital Inputs Bit
Read
2
3 30001 Input Registers Registered
Read
3
4 40001 Output Registers Registered
Read & Write
4, 6, 16
Table 4. Types of Modbus functions supported by the module
4.5 Communication Settings
The data stored in the module's memory is given in the16-bit registers. The access to
registers is via Modbus RTU or Modbus ASCII.
4.5.1 Default Settings
The default configuration can be restored with the DIP switch, SW6.
Baud Rate 19200
Parity No
Data Bits 8
Stop Bits 1
Reply Delay [ms] 0
Modbus Type RTU
Table 5. Default settings

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 12 of 25
•
•
•
•
4.6 Restoring Default Configuration
To restore the default configuration, follow the steps below:
Turn the power off;
Turn the switch SW6 on;
Turn the power on;
When power and the communication LED are lit, turn the switch SW6 off.
WARNING! After restoring the default configuration, all values stored in the registers are
cleared as well.
Configuration Registers
Modbus Address Decimal Address Hex Address Name Values
40003 2 0x02 Baud Rate 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005 4 0x04 Parity 0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
40004 3 0x03 Stop Bits 1 – one stop bit
2 – two stop bits
40004 3 0x03 Data Bits 7 – 7 data bits
8 – 8 data bits
40006 5 0x05 Response Delay Time in ms
40007 6 0x06 Modbus Mode 0 – RTU
1 – ASCII
Table 6. Configuration registers
4.7 Watchdog
This 16-bits register specifies the time in milliseconds to watchdog reset. If the module
does not receive any valid message within that time, all digital and analog outputs will be
set to the default state.
This feature is useful if there is an interruption in data transmission and for security
reasons. Output states must be set to the appropriate state in order to reassure the
safety of persons or property.
The default value is 0 milliseconds, which means the watchdog function is disabled.

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 13 of 25
5 Indicators
Figure 2. Indicators
Indicator Description
Power Supply The LED indicates that the module is correctly powered
Communication The LED lights up when the unit receives the correct packet and sends
the answer
Inputs State The LED indicates that on the input is high state
Outputs State The LED indicates that the output is on
Table 7. Description of indicators

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 14 of 25
6 Connections
6.1 Block Diagram
Figure 3. Block diagram
6.2 Power Supply Connection
6.2.1 DC Power Connection
Figure 4. DC power connection

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 15 of 25
6.2.2 AC Power Connection
Figure 5. AC power connection
6.3 Communication Bus Connection
Figure 6. Communication bus connection
6.4 Connection of Digital Inputs
6.4.1 Connection of Inputs
Figure 7. Connection of input

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 16 of 25
6.4.2 Connection of Encoder
Figure 8. Connection of encoder
6.5 Connection of Digital Outputs
6.5.1 Connection of Outputs
Figure 9. Connection of digital outputs
6.5.2 Connection of Relay
Figure 10. Connection of relay
6.6 Quick Connector
The Quick Connector is a unique feature of modules that allows for quickly connecting a
group of devices with a flat ribbon cable. Thanks to this solution, it is enough to connect
power and RS485 communication to one of the devices in the group, and the others will

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 17 of 25
be powered and communicated with ribbon cable.The Quick Connector is sufficient to
connect up to 10 devices next to each other. It is important that the various types of
modules in the SfAR-S family can be connected with the ribbon cable.
Figure 11. Quick Connector

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 18 of 25
7 DIP Switch
Figure 12. DIP switch
Switch Function Description
1 Module address +1 Setting module address from 0 to 31
2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
6 Restoring default settings Restoring default settings
Table 8. Description of switches

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 19 of 25
8 Input Filter
Digital inputs allow connection of the AC signal. However, due to the fact that these inputs
are fast and allow counting pulses at 1 kHz frequency, it is not possible to use them to
monitor the presence of a variable frequency signal like 50 Hz because, depending on the
moment at which the input state is read with the Modbus protocol, different results can
be obtained despite the fact that AC voltage is still present. To be able to monitor the AC
signals, the possibility of filtering the digital inputs has been introduced. Filtration works in
a way that the high state occurs if the voltage is maintained for at least 40 ms. The low
state appears when there is no voltage for at least 80 ms.
The filter can be turned on for each input of the device independently using the 40018
register.

SfAR-S-8DI8DO User Manual
www.ismacontrolli.com
DMP275en | 3rd Issue rev. 2 | 05/2022
page 20 of 25
9 Module Registers
9.1 Registered Access
Modbus
Address
Decimal
Address
Hex
Address
Register Name Access Description
30001 0 0x00 Version/Type Read Version and type of the
device
30002 1 0x01 Switches Read Switches state
40003 2 0x02 Baud Rate Read/write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read/write No. of stop bits & data
bits
40005 4 0x04 Parity Read/write Parity bit
40006 5 0x05 Response Delay Read/write Response delay in ms
40007 6 0x06 Modbus Mode Read/write Modbus mode (ASCII
or RTU)
40009 8 0x08 Watchdog Read/write Watchdog
40013 12 0x0C Default Output State Read/write Default output state
(after power on or
watchdog reset)
40018 17 0x11 Inputs Filter Read/write Configuration of the
inputs filter
40033 32 0x20 Received Packets LSR
(Least Significant
Register)
Read/write No. of received packets
40034 33 0x21 Received Packets MSR
(Most Significant
Register)
Read/write
40035 34 0x22 Incorrect Packets LSR Read/write No. of received packets
with error
40036 35 0x23 Incorrect Packets MSR Read/write
40037 36 0x24 Sent Packets LSR Read/write No. of sent packets
40038 37 0x25 Sent Packets MSR Read/write
30051 50 0x32 Inputs Read Inputs state
40052 51 0x33 Outputs Read/write Output state
40053 52 0x34 Counter 1 LSR Read/write 32-bit counter 1
Table of contents
Other iSMA CONTROLLI I/O System manuals
Popular I/O System manuals by other brands

Sony
Sony CBK-SD01 installation guide

Measurement Computing
Measurement Computing PCI-DAC6702 user guide

Acromag
Acromag BusWorks 900EN Series user manual

Beckhoff
Beckhoff EtherCAT EL600x Series Documentation

Johnson Controls
Johnson Controls FX-PCX47 installation instructions

ICP DAS USA
ICP DAS USA IR-712-MTCP quick start

Siemens
Siemens SIMATIC ET 200SP HA manual

National Instruments
National Instruments REM-11154 Getting started guide

Moxa Technologies
Moxa Technologies ioLogik E1210 Quick installation guide

LEGRAND
LEGRAND Wattstopper WIO-4 installation instructions

National Instruments
National Instruments NI 9485 Getting started guide

LabJack
LabJack LJU3-LV user guide