W100 and W600 Analog Output Card Troubleshooting
Programming the Analog Output card
W100 Menu
Alarm Menu
Inputs Menu (Sensor, Digital inputs)
Outputs Menu (Relays, Analog Output)
Configurations/Settings menu
Press the key below the icon to get to the main menu selections
In this example, I will program the analog output (A1) to send out 50% (12 mA) when put in HAND mode
to prove if the AO card is working.
Press to access the Outputs menu.
Press to scroll down until (A1) is highlighted.
Press to enter the Analog Output menu.
Press to go into the Settings menu.
Press to scroll down until Mode is highlighted.
Press to enter the Mode menu and then scroll down until Manual Control is highlighted.
Press to accept this option.
Press to go into the Settings menu and HOA should be highlighted.
Press to enter the HOA menu and select HAND. Press to accept this option.