www.johnsonandstarley.co.uk
20
4.2 Handing over:
After completion of the commissioning procedure, the installer should hand the appliance over to the occupier of
the house by the following procedure:
•Hand the User Instructions (ZZ1190) to the occupier and explain their responsibilities in respect of current legisla-
tion and regulations, both national and local.
•Explain and demonstrate how to light and shut down the appliance.
•In order to gain the best possible fuel economy in relation to the heating and hot water requirements of the house-
hold, carefully explain the operation of the appliance and the use/adjustment of all the system controls.
•Advise on the precautions required to prevent damage to the appliance; the system and the building in the event
of the appliance being shut down in very cold weather.
•Explain how, in the event of a fault, the appliance will display a fault code, emphasising that if a fault is indicated
they should should note the fault code, turn off the appliance and contact a “competent person” which in normal
circumstances would be a Gas Safe registered engineer.
•Explain and demonstrate the function/operation of time/temperature controls and thermostatic radiator valves,
emphasising the economic use of the appliance.
•If a programmer has been fitted, hand the user instructions that were supplied with the programmer to the occupier.
•Emphasise the importance of a regular service and that servicing of the appliance MUST only be carried out by a
“competent person” which in normal circumstances would be a Gas Safe registered engineer.
•As the installer you may wish to offer a service contract yourself, or alternatively you may wish to explain to the
occupier that they can take advantage of an extended warranty scheme offered by Johnson & Starley Ltd.
Reminder: following the commissioning and handover
of the appliance, complete the Benchmark Log Book
and leave it with the occupier.
5. SERVICING SCHEDULE
To ensure that the appliance gives continued operation
that is both safe and efficient, it is necessary to carry
out regular service checks and whilst the period
between servicing will depend on the installation condi-
tion and the demands placed upon the appliance, it is
recommended that the appliance be serviced annually.
NOTE: it is a statutory requirement that ALL work be
carried out by a “competent person” which in normal
circumstances would be a Gas Safe registered engi-
neer.
5.1 Servicing Sequence:
•Light the boiler and carry out a pre-service check,
noting any operational faults.
•Check the gas consumption.
•Put the appliance in test mode and connect a suit-
able flue gas analyser to the sampling point on the
top of the boiler or into the flue terminal if access is
possible (optional test).
For correct boiler operation, the CO/CO2content of
the flue gas should not be greater than 0.008 ratio.
Check that the gas input is at least 90% of the
nominal. * See test mode inputs.
•Clean the main burner.
•Clean the heat exchanger.
•Check the condition of the combustion chamber
insulation. Any cracked or damaged pieces should
be replaced.
•Wherever possible, remove and clean the condensate
'S' trap (refer to section 6.6) and check the drain for
blockage.
•Check that the flue terminal is unobstructed and
that the flue system is sealed correctly.
Test Mode
To put the appliance in test mode, remove the fixing screw
and drop down the electronics panel so that access can be
gained to the PCB. The supplied jumper (parked) should
be used to jump the two pins marked X7.
Test mode is indicated by the power light flashing. Max
and min test mode can be selected by max and min on
boiler stat.
Whilst in test mode, the appliance overrides all tempera-
ture setting and the temp control allows you to scroll
between maximum and minmum rates, whilst still overrid-
ing all temperature settings*.To take the boiler out of test
mode, remove the jumper and put it back into its parked
position.
When in max test mode the unit will run at 100% fan
speed. This will give an input of-
*On smaller heating systems, running at maximum output MIGHT cause the
boiler to go into lockout. Allow the heating system to cool and turn the temp.
control to RESET until the lockout clears.
Jumper
16H 25H 31H
INPUT NET Kw 16.3 30.6 38.0
GROSS Kw 18.1 34.0 42.1