KAESER TF 171E User manual

REFRIGERATED
TYPE
COMPRESSED
AIR DRYERS
SERVICE DEPARTMENT: (724) 745-3038
CONTENTS
GENERAL SAFETY INFORMATION .................................. 2
RECEIVING, MOVING, AND UNPACKING ........................ 2
1.0 INSTALLATION......................................................... 3
2.0 OPERATION ............................................................ 5
3.0 MAINTENANCE ...................................................... 8
SIZING............................................................................ 8
ENGINEERING DATA ...................................................... 9
WIRING DIAGRAM
Model TF 171E.......................................................... 10-11
Model TF 210E.......................................................... 12-13
575-460/3/60 Transformer Pack ............................. 14
DIMENSIONS / WEIGHTS................................................ 15
TROUBLESHOOTING GUIDE............................................ 16
PARTS LIST..................................................................... 17
WARRANTY ................................................................... 20
INSTRUCTION MANUAL
Demand Manager Control Series
Models: TF 171E & TF 210E
5002736 Rev. C 12/13

2
GENERAL SAFETY INFORMATION
1. PRESSURIZED DEVICES:
This equipment is a pressure containing
device.
• Donotexceedmaximumoperating
pressure as shown on equipment
serial number tag.
• Makesureequipmentisdepressurizedbefore
working on or disassembling it for service.
2. ELECTRICAL:
This equipment requires electricity to
operate.
• Installequipmentincompliancewith
all applicable electrical codes.
• Standardequipmentissuppliedwithelectrical
enclosuresnotintendedforinstallationinhazardous
environments.
• Disconnectpowersupplytoequipmentwhen
performing any electrical service work.
3. BREATHING AIR:
• Airtreatedbythisequipmentmay
not be suitable for breathing without
further purification.
Refer to applicable standards and
specifications for the requirements for breathing
quality air.
RECEIVING, MOVING, AND UNPACKING
A. RECEIVING
This shipment has been thoroughly checked, packed and
inspected before leaving our plant. It was received in
good condition by the carrier and was so acknowledged.
Check for Visible Loss or Damage. If this shipment shows
evidence of loss or damage at time of delivery to you,
insist that a notation of this loss or damage be made on
the delivery receipt by the carrier’s agent.
B. UNPACKING
Check for Concealed Loss or Damage. When a shipment
has been delivered to you in apparent good order, but
concealed damage is found upon unpacking, notify the
carrier immediately and insist on his agent inspecting
the shipment. Concealed damage claims are not our
responsibility as our terms are F.O.B. point of shipment.
C. MOVING
In moving or transporting dryer, do not tip dryer onto its
side.
D. STORAGE/SHUT DOWN
Dryer should not be stored outside (either
packedorunpacked)orexposedtotheweather.Damageto
electrical and control components may result.
IMPORTANT: WATER-COOLED UNITS - If unit is shut down
belowfreezingtemperatures,thewater-cooledcondenser
mayfreezeandcausepermanentdamage.Condensermust
be drained when the unit is shut down.
IMPORTANT: Do not store dryer in temperatures above 130°F
(54.4°C).

3
IMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT
1.0 INSTALLATION
1.1 Location
A. For typical placement in a compressed air system, see
drawing.
B. Air compressor intake – Locate air compressor so that
contaminants potentially harmful to the dryer (e.g.
ammonia) are not drawn into the air system.
C. Clearances Free air flow
Front 36 inches (914 mm)
Back 6 inches (152 mm)
Sides 36 inches (914 mm)
Service - To facilitate maintenance leave 36 inches
(914 mm) of clearance in front of dryer.
D. Standard units are designed to operate in ambients:
Air-cooled: 45 to 110°F (7 to 43°C).
Water-cooled: 45 to 130°F (7 to 54°C).
E. Installations in altitudes above 4500 feet (1370 meters) –
Dryer is adjusted to operate in altitudes up to 4500 feet
(1370 meters). If dryer is installed in an altitude above
this, and has not been preset at the factory for this
altitude, contact manufacturer’s Service Department.
F. Theinstallationofaexibleconnectionpriortothe
dryer is recommended to prevent possible damage from
vibration.
NOTE: Outdoor installation – Standard units are designed
for indoor installation. Contact manufacturer if installing
outdoors.
Aftercooler
Separator
Dryer
Oil Removal
Filter
Compressor
Electric Demand Drain (EDD)
3-Way Valve
Moisture Separator
Coalescing Filter
(Option)
Control Panel
RS232 Entry
Electrical Entry
Air Outlet
Air Inlet
Condenser
Drain Outlet

4
1.2 Mounting
Mount on floor or shelf free from vibration.
1.3 Piping connections
A. Air Inlet - Connect compressed air line from air source
to air inlet. (Reference markings on dryer or see callout
drawing on page 14 for air inlet/outlet connection
locations.)
RefertoSerialNumberTagformaximum
workingpressure.Donotexceeddryer’sMaximumWorking
Pressure.
NOTE: Install dryer in air system at highest pressure possible
(e.g. before pressure reducing valves).
NOTE: Install dryer at coolest compressed air temperature
possible.Maximuminletcompressedairtemperature:120°F
(49°C).Ifinletairexceedsthistemperature,precooltheair
with an aftercooler.
B. Air Outlet – Connect air outlet to downstream air lines.
C. Bypass piping – If servicing the dryer without interrupting
the air supply is desired, piping should include inlet and
outlet valves and an air bypass valve.
D. Water cooled models – cooling water inlet and outlet
1. Connect cooling water supply to cooling water inlet.
2. Connect cooling water return line to cooling water
outlet connection.
NOTE: Strainer and water regulating valve are supplied on
water cooled models.
1.4 Electrical connections
IMPORTANT: Use copper supply wires only.
A. Dryer is designed to operate on the
voltage, phase, and frequency listed on
the serial number tag.
B. Connect power source to terminal strip in electrical
enclosure.
NOTE: Refrigeration condensing unit is designed to run
continuously and should NOT be wired to cycle on/off with
the air compressor.
NOTE: CHECK FOR CORRECT PHASING OF UNIT. After starting
the dryer, if an unusual noise is heard, or if the discharge
line does not get hot, the refrigeration compressor may be
running in the reverse direction. Immediately stop the dryer,
reverse two of the power leads, restart the dryer, and verify
the unusual noise is corrected and the refrigerant discharge
line is hot. FAILURE TO DO SO MAY DAMAGE THE COMPRESSOR
AND VOID THE WARRANTY.
1.5 Moisture separator
A. An automatic electric demand drain (EDD)
discharges condensate removed by the
separator. It may be desirable to pipe
the condensate from the EDD outlet to a
suitable drain.
B. Formanualdraining,convenientdryerdepressurization,
and EDD service, a three-way valve assembly has been
installed at the bottom of the moisture separator (and
cold coalescing filter where applicable). Review the
following for proper drain function:
• AutomaticDraining-Valvehandleshouldbe
positioned parallel to the valve body (as shown), with
the arrow on the handle pointing toward the EDD. In
this position, condensate will flow from the bowl to
the EDD.
• DrainIsolation(Shutdown)-Valvehandleshallbe
turned perpendicular to the valve body (rotate 90°). In
this position, condensate flow is shutoff.
• ManualDraining-Drainvalvehandleshallberotated
slightly past the drain isolation position to allow
throttling through the valve for manual discharge and
depressurization.
• NOTE: The quick disconnect fitting allows removal of
the entire drain assembly. However, the unit must
be depressurized prior to disassembly or serious
injury may occur.
NOTE: Discharge is at system pressure. Drain line should be
anchored.
NOTE: Condensate may contain oil. Comply with applicable
laws concerning proper disposal.
1.6 Operation
A. Verify that isolation valves are open. If the drain fails to
dischargeafterthevalveisenergized,theelectronic
controlcircuitwillrepeatedlyenergizethevalveinan
attempt to clear the discharge port. If, after 60 seconds,
the drain still fails to discharge, the control circuit then
switches to the alarm mode. In this mode the valve
isde-energizedandtheredalarmlightisactivatedon
the drain and the dryer controller. The valve is then
automaticallyenergizedevery4minutesfor5seconds.
Check the drain operation. Push drain (push-to-test)
button on the Energy Management Monitor control
boardtoenergizedrain.Aowofcondensateand/orair
should be present at the drain outlet. The alarm mode
automatically clears after the drain returns to normal
operation.
B. Condensate enters the reservoir (1) through the inlet
port. When the condensate level in the reservoir covers
the capacitance sensor, an electronic signal is sent to the
solid state countdown processor. The processor delays
the opening of the solenoid valve for a given period
of time. Once the time has elapsed, the solid state
processortransmitsinformationtoenergizethecoilin
the solenoid valve (2). The magnetic force of the coil

5
1. Temperature Indicator
2. Operator Interface Display
3. Power-on Light
4. Compressor-on Light
5. Alarm / Service Light
6. Schedule On/Off and Enter Button
a. In display mode: Press to toggle between
SCHEDULE RUNNING and MANUAL OVERRIDE.
b. In program mode:
i. Press to move to a lower level menu.
ii. Press to accept a value that has been edited.
7. Program Mode (i) and Esc
a. In display mode: Press and hold to enter program
mode.
b. In program mode: Press to move to a higher level
menu.
8. Up Arrow
a. In display mode: No function
b. In program mode:
i. Presstoviewthenextiteminalistorto
increment a variable to a higher value. Press
and hold for accelerated incrementing.
ii. When the top of the list (or highest value) is
displayed, pressing the up button will cause
the display to wrap to the bottom of the list (or
lowest value).
9. Down Arrow
a. In display mode: No function
b. In program mode:
i. Press to view the previous item in a list or to
increment a variable to a lower value. Press and
hold for accelerated incrementing.
ii. When the bottom of the list (or lowest value) is
displayed, pressing the down button will cause
the display to wrap to the top of the list (or
highest value).
10. 1/0: Press at any time to turn the dryer on/off.
11. Drain test: Press at any time to momentarily the open
drains (like the current emm).
12. Reset: Press at any time to clear the alarm/service
message (if shown) and the alarm LED.
CONTROL PANEL
1234 5
678
91011 12
causes the solenoid core (3) to move, closing the pilot air
supplylineandopeningthepilotairexhaustline.After
the pilot air above the diaphragm (4) is vented, pressure
in the reservoir opens the discharge port and forces
the condensate through the discharge port and outlet
piping.
2.0 OPERATION
2.1 Minimum/Maximum operating conditions
A. Maximuminletairpressure:refertodryerserialnumber
tag
B. Minimum inlet air pressure: 30 psig (2.1 kgf/cm
2
)
C. Maximuminletairtemperature:120°F(49°C)
D. Maximumambienttemperature:
Air-cooled models: 110°F (43°C)
Water-cooled models: 130°F (54°C)
E. Minimum ambient temperature: 45°F (7°C)
2.2 Start-up
A. Energizedryer.Greenpoweronlightwillilluminate.
IMPORTANT:Energizedryerdisconnectswitch(provided
by others, see NEC) 24 hours before refrigeration
compressor is started! Never use the disconnect switch
toshutdownthedryerforaextendedperiodoftime
(exceptforrepair).Failuretofollowtheseinstructions
may result in a non-warrantable compressor failure.
NOTE: If there is no power to the control board for
a period of two weeks or more, it may return to the
default mode.
B. Program Monitor
Press and hold Program Mode button until Main Menu screen
appears. Use the Up and Down arrow buttons to scroll
through the list of submenu choices. Press Enter button to
viewthesubmenuthatisdisplayed.PressESCtoexitthe
Main Menu and return to Display mode.
1. Language selection
a. Use the ‘Up’ and ‘Down’ arrow buttons to scroll
through the list of languages (choice of 10 available:
English, Deutsch, Francais, Espanol, Italiano, Polski,
Dansk, Dutch, Norsk and Suomi).
b. Press ‘Enter’ button to select the language that is
displayed.
c. Push ‘ESC’ at any time to return to the Main Menu.
1
2
3
4

6
2. Setting Date & Time
a. Use the ‘Up’ and ‘Down’ arrow buttons to set minutes
(00 to 59). Press ‘Enter’ to accept new value.
b. Use the ‘Up’ and ‘Down’ arrow buttons to set hours
(00 to 23). Press ‘Enter’ to accept new value.
c. Use the ‘Up’ and ‘Down’ arrow buttons to set year
(00 to 99 representing 2000 to 2099). Press ‘Enter’ to
accept new value.
d. Use the ‘Up’ and ‘Down’ arrow buttons to set month
(three letter abbreviation). Press ‘Enter’ to accept
new value.
e. Use the ‘Up’ and ‘Down’ arrow buttons to set day (01
tomaximumforthemonthandyearselected).Press
‘Enter’ to accept new value.
f. Push ‘ESC’ at any time to return to the Main Menu.
3. Setting Schedule
a. Use the ‘Up’ and ‘Down’ arrow buttons to select
desired “Day of week + on/off”. Press ‘Enter’ to
accept new value
b. Use the ‘Up’ and ‘Down’ arrow buttons to set hour
(00 to 23). Press ‘Enter’ to accept new value
Note: If the hour setting is ‘IGNORE’, Press ‘Enter’
again to move the cursor under the “Day of week +
on/off”. Repeat steps a through b (or c) as needed.
c. Use the Up and Down arrow buttons to set minutes
(00, 10, 20, 30, 40, 50; not shown if hour setting is
‘IGNORE’). Press ‘Enter’ to accept new value and
return to “Day of week + on/off”. Repeat steps a
through c as needed.
d. Push ‘ESC’ at any time to return to the Main Menu.
NOTE: Scheduler will ignore programmed commands
for10minutesafterexitingprogrammode.
4. Hours To Service
a. Use the ‘Up’ and ‘Down’ arrow buttons to scroll
through the range of permissible values (0 to 8760)
before service reminder is initiated. Press ‘Enter’
to accept new value. (Only hours that refrigeration
compressor is operating are counted).
b. Press ‘ESC’ at any time to return to the Main Menu.
NOTE: On dryers with air-cooled condensers, regular
condenser cleaning is recommended. Dirtiness
of ambient air at installation site will determine
frequency of service. Typically once a month is
recommended. Dryers contain an integral 3 micron
filter. As the filter element accumulates solid
contaminants, differential pressure increases. Solid
particulate load in the compressed air supply will
determine frequency of service. Typically element
changeout is recommended at least annually.
5. PushESCbuttontoexitprogrammode
NOTE: If after 60 seconds no button is pressed while in
Program Mode, the audible alarm sounds for five (5)
seconds. Dryer will resume previous operating mode.
6. Manual Operation
a. To manually turn the refrigeration system on or off
use ‘On/Off’ button; Push ‘Schedule On/Off and
Enter’ button to return to schedule.
NOTE:Afterpowerinterruptiondryerwillreenergize
in Manual override, refrigeration system off. To restart
Schedule: Push ‘Schedule On/Off and Enter’ button.
C. Starting dryer
IMPORTANT:Dryermustbeenergized24hoursbeforestart-
ing refrigeration compressor.
NOTE: It is recommended that dryer be started 15 minutes
before compressed air flow begins.
1. On water-cooled models: after 24 hours, begin cooling
water flow.
2. Check for proper electrical voltage.
3. Slowlypressurizeunitairsidebyopeninginletisolation
valve. Check for leaks.
4. After 15 minutes, open outlet isolation valve slowly.
5. Close air bypass valve.
6. Dryer may be operated in Manual or scheduled modes.
NOTE: CHECK FOR CORRECT PHASING OF UNIT. After starting
the dryer, if an unusual noise is heard, or if the discharge
line does not get hot, the refrigeration compressor may be
running in the reverse direction. Immediately stop the dryer,
reverse two of the power leads, restart the dryer, and verify
the unusual noise is corrected and the refrigerant discharge
line is hot. FAILURE TO DO SO MAY DAMAGE THE COMPRESSOR
AND VOID THE WARRANTY.
Manual mode - push On/Off button - refrigeration
compressor will start and run, green Compressor-on
light will illuminate. In this mode compressor will run
continuously and will not be turned on and off by the
monitor. MANUAL OVERRIDE will appear on interface panel.
Schedule mode - push Schedule On/Off and Enter button.
SCHEDULE RUNNING will appear on the interface panel.
The refrigeration compressor will continue to be on or off
(asselectedintheManualOverrideMode)untilthenext
scheduled event. The compressor will then turn on or off
as programmed.
NOTE: Schedule may be returned to the manual mode at any
time using the ‘Schedule On/Off and Enter’ button. MANUAL
OVERRIDE will appear on interface panel. To reinstitute
Schedule, push the ‘Schedule On/Off and Enter’ button again.
NOTE: Restart after the power interruption. Unit will be in
MANUAL OVERRIDE mode, refrigeration compressor, off when
power is restored after power interruption.
7. To reinstitute SCHEDULE RUNNING, push ‘Schedule On/Off
and Enter’ button.
IMPORTANT:Dryermustbeenergized24hoursbefore
refrigeration compressor is started.
D. Operating check points
1. Check that green Power-on light is illuminated
2. Check that green Compressor-on light is illuminated if
dryer is on in the manual mode or it is a scheduled on
time.
IMPORTANT: Refrigeration compressor must be restarted
after power interruption.

7
3. Check interface panel.
NOTE: Interface panel will scroll through three screens
(Current Time/Operating Status, Hours to Service and Total
Operating Hours).
a. Verify that current time is correct.
b. Check HRS TO SERVICE: this indicates time remaining
until service is required; allow time for required
maintenance items to be ordered.
c. Check operating status:
MANUAL OVERRIDE - Dryer is either running
continuously (not being controlled by the scheduled
on/off times) or the refrigeration compressor has
been shut off using the ‘On/Off’ button.
SCHEDULE RUNNING - Refrigeration compressor
is being turned on and off by the monitor per-
programmed schedule (see B.3. to set schedule).
d. Check Temperature indicator - indicator should read
in the green area.
e. Check Alarm/Service light If illuminated, check
Interface panel.
1) If SERVICE DRYER appears, scheduled maintenance
time has elapsed (HRS TO SERVICE is 0). Perform
needed service and reset service interval (see B.3.).
2) If ALARM appears, a dryer fault is indicated; see
Troubleshooting Guide for possible remedies.
After fault correction push Reset button to turn
Fault alarm off.
Type of FAULTS:
LOW PRESSURE - the refrigeration compressor
control circuit has opened because of low suction
pressure.
HIGH PRESSURE - the refrigeration compressor
control circuit has opened because of high head
pressure. The high pressure switch must be reset
manually once the fault is corrected. Red reset
button is located on pressure switch inside unit.
HIGH TEMPERATURE - compressed air temperature
is above the set point.
COMPRESSOR-Normallyopen(NO)auxiliary
contact on the compressor contactor is open
when the dryer is on.
HEATER-Normallyclosed(NC)auxiliarycontacton
the compressor contactor is open when the dryer
is off.
TEMP SENSOR - Occurs if the temperature sensor
circuit is open or shorted. If open, the left-most
LED in the temperature display will be illuminated.
If shorted, all the LEDs in the temperature display
will be illuminated.
DRAIN - electric drain contains a high water level
alarm that activates if drain fails to discharge.
f. Check drain operation - push Drain (push-to-
test)buttontoenergizeelectricdrain.Aowof
condensate and/or air should be present at the drain
outlet.
E. Using the RS-232 port
The RS-232 port is used to monitor dryer operation from
a host computer. A (1 to 1) DB-9 cable is required to
connect dryer and computer. For PC connections, data
is transmitted on pin 2, received on pin 3, ground is pin
5, pins 7 and 8 are jumpered at dryer.
Operationisatxedbaudrateof9,600;asynchronous
format is 8 bit, no parity, 1 stop bit (“8,N,1”). No check
sum or error correction values are provided. If required,
request status string two (or more) times and compare
for agreement.
Request data by sending ASCII ? character (3FH).
Response may take up to two seconds as certain
processing functions may require completion before
serial port is acknowledged.
Dryer responds with line feed (0AH), carriage return
(0DH), and character string: (1), (2), (3), (4), (5), (6), (7), (8), (9)
(1)=STX(start-of-textcharacter,mayappearasasmiley
face or some other character
(2) = 108, Control board ID
(3) = 0 or 1, Compressor running status (0=off, 1=on)
(4) = M or S, Operating Mode (M= MANUAL OVERRIDE, S =
SCHEDULE RUNNING)
(5)=xxxx,HOURSTOSERVICE
(6)=xxxxxx,TOTALHOURS
(7)=xx,AlarmorServiceCode(0=noalarm,30=LOW
PRESSURE ALARM, 31=HIGH PRESSURE ALARM,
32=COMPRESSOR ALARM, 36=HIGH EVAP TEMP ALARM,
37=HEATER ALARM, 38=DRAIN ALARM, 39=SERVICE
DRYER, 41=TEMP SENSOR ALARM)
(8) =xx.x,Evaporatortemperature(°F)
(9) =ETX,(end-of-textcharacter,mayappearasaheart
or some other character)

8
TABLE 2
Air capacity correction factors (Multipliers)
INLET COMPRESSED AIR CONDITIONS
INLET
PRESSURES
INLET TEMPERATURES
80°F 90°F 100°F 110°F 120°F
psig kgf/cm227°C 32°C 38°C 43°C 49°C
50
80
100
125
150
175
200
3.5
5.6
7.0
8.8
10.5
12.3
14.0
1.35
1.50
1.55
1.63
1.70
1.75
1.80
1.05
1.17
1.23
1.31
1.37
1.42
1.47
0.84
0.95
1.00
1.07
1.13
1.18
1.22
0.69
0.79
0.82
0.91
0.95
0.99
1.03
0.56
0.66
0.70
0.74
0.80
0.84
0.89
COOLING MEDIUM*
AMBIENT
TEMPERATURE
MULTIPLIER
°F °C
80
90
100
110
27
32
38
43
1.12
1.06
1.00
0.94
*Air-cooled models; water-cooled models use 1.15 multiplier if cooling
water is below 35°C, 95°F.
SIZING
Determining dryer capacity at actual operating conditions
Todeterminethemaximuminletowcapacityofadryer
at various operating conditions, multiply the rated capacity
from Table 1 by the multipliers shown in Table 2.
Example:Howmanyscfmcananair-cooledmodelTF171E
handle when compressed air to be dried is at 200 psig and
100°F; ambient air temperature is 80°F?
Answer:600x1.22x1.12 = 820 scfm.
TABLE 1
Rated capacity (scfm) and pressure drop @ 100 psig inlet
pressure, 100°F inlet temperature, and 100°F ambient
temperature
MODEL TF 171E TF 210E
Ratedcapacity 60Hz 600 750
ofair-cooled 50Hz 540 630
models (scfm)
3.0 MAINTENANCE
3.1 Condenser coil – Clean off accumulated dust and
dirt monthly.
3.2 Moisture separator – Replace filter element
when pressure drop across dryer is excessive or
annually.
3.3 Check separator daily to be sure automatic drain
is discharging.
3.4 Blow down separator weekly by pushing test
button on control panel.
3.5 Rebuild drain mechanism annually.
To facilitate service, maintenance kits are available.
Head
Element O-Ring
Bowl O-Ring
Element
Bowl
Drain Quick Disconnect
Bowl Support

9
ENGINEERING DATA
TF 171E TF 210E
Air System Data (Rated Flow Capacity at 100°F, 100 psig Inlet, 100°F Ambient Temperature)
Maximum/MinimumInletAirPressure(compressedairatinlettodryer) 232 psig (16 barg) / 30 psig (2 barg)
Maximum/MinimumInletAirTemperature(compressedairatinlettodryer) 120°F (49°C) / 40°F (4°C)
Maximum/MinimumAmbientTemperature 110°F (43°C) / 40°F (4°C)
Outlet Air Temperature (nominal at rated conditions) 85°F (29°C)
Refrigeration System Data
Refrigeration Capacity @ 35°F Evaporator & 100°F Ambient (BTU/hr) 60Hz 22000 30500
50Hz 18300 25400
Refrigerant Type R-134A
Refrigerant Charge See Data Tag on Dryer
Suction Pressure Setting - Hot Gas Bypass Valve (psig) 30.5 psig (2.1 barg)
Compressor Control Ranges (out-in) High 281 - 190 psig (19.4 - 13.1 barg)
Low 22 - 34 psig (1.5 - 2.3 barg)
Air-Cooled Condensers
Air Flow Across Condenser (cfm) (air-cooled models) 60Hz 1680 2170
50Hz 1400 1810
Condenser Fan Switch Setting (in-out) Fan 1 113 - 78 psig (7.8 - 5.4 barg)
Fan 2 183 - 124 psig (12.6 - 8.6 barg)
Water-Cooled Condensers
Water Regulating Valve Setting 135 psig (9.3 barg)
Required Available Water Pressure Differential 40 psig (2.8 barg) - minimum
Flow Required with 85°F Cooling Water (gallons per minute) 60Hz 4.9 6.8
50Hz 4.1 5.6
Electrical Data
Nominal Voltage 208-230/3/60
Min.-Max.Voltage 187 - 253
Input Power @ Rated Flow (watts) 2910 4120
Rated Load Amps** 13.9 22.1
Locked Rotor Amps** 88.0 115.0
Minimum Circuit Ampacity 19.7 30.4
BranchCircuitFuseSize(amps) 30 45
Resistance (ohms) 1.0 0.7
Nominal Voltage 460/3/60
Min.-Max.Voltage 414 - 506
Input Power @ Rated Flow (watts) 2910 4120
Rated Load Amps** 7.1 9.6
Locked Rotor Amps** 44.0 63.0
Minimum Circuit Ampacity 10.4 15.2
BranchCircuitFuseSize(amps) 15 20
Resistance (ohms) Main/Start 4.0 2.7
Nominal Voltage 575/3/60
Min.-Max.Voltage 518 - 633
Input Power @ Rated Flow (watts) 2910 4120
Rated Load Amps 7.1 9.6
Locked Rotor Amps 44.0 63.0
Minimum Circuit Ampacity 8.3 12.2
BranchCircuitFuseSize(amps) 15 20
Resistance (ohms) 4.0 2.7
Nominal Voltage 380-420/3/50
Min.-Max.Voltage 342 - 462
Input Power @ Rated Flow (watts) 2040 2860
Rated Load Amps** 7.1 9.6
Locked Rotor Amps** 44.0 63.0
Minimum Circuit Ampacity 10.4 15.2
BranchCircuitFuseSize(amps) 15 20
Resistance (ohms) 4.0 2.7
*For60Hz,35°FEvaporator,100°FAmbient;for50Hz,35°FEvaporator,77°FAmbient
** Compressor Only

10
(4 Terminal Blocks)
H4
H3
H2
H1
FU2
FU3
B100-3683-5
MICRON
L1L3
H5208V
230V H5
400V H5
460V H5
FACTORY SET TO 460V
FU1
24/120 VAC SECONDARY
100VA
208/230/400/460 VAC PRIMARY
H5
COM
H3
230V
H4
208V
H2
400V
X3
X2
X1
H1
120V 24V
460V
COMPRESSOR
Optional Fan
TO LINE 22
21
20
18
19
17
16
15
14
13
L1 L3
L2
PE
HEATER HARNESS
1L2
L3
TB2
TB2
PE
T3
T2
H1
HEATER 1
(for 500-600 models only)
FAN 2 HARNESS
FPS 2
FAN 2
REF SHEET 02 LINE 11
REF SHEET 02 LINE 10
REF SHEET 01 LINE 20
03
10
11
12
09
08
07
06
05
04
L3
L3
L3
L2
L2
02
01
00
PETB1 L1 L2 L3
L1
L1
L1 L2 L3
CONT 1
PE
TB2
T1
T2
T3
T3
T2
T3
TB2
PE
T2
T3
T2
FAN 1 HARNESS
FPS 1
FAN 1
T1
T1
T1
COMPRESSOR HARNESS
43
42
40
41
39
38
37
36
35
25
32
33
34
31
30
29
28
27
26
FROM LINE 21
L3
24
23 L1
22
L3
L1
L3
L1
X
TO SHEET 02
N
TO SHEET 02
TB2
XX
(4 Terminal Blocks)
NTB2
N
ELECTRICAL SUPPLY
480VAC/3PH/60HZ/GND
CONT 1
-1NC -2NC H2
MTR3
L3
L2
T3
T2
L1 T1
MTR2
MTR1
WIRING DIAGRAM
Model TF 171E - 460 VAC
Sheet 1 of 2

11
WIRING DIAGRAM
Model TF 171E - 460 VAC
Sheet 2 of 2
OPTIONAL DRAIN
Drain Alarm #2 Input
13 21
W36
W28
W37
W34
W32
W30
FMD #1 In (RJ-11)
FMD #2 In (RJ-11)
J2 RS-232
RED
BLACK
WHITE
22
21
20
19
18
17
16
15
14
W38
Evaporator Thermistor
Evaporator Thermistor
Phase B xfmr Input
Phase A xfmr Input
Phase Com. xfmr Input
W4
N/A
N/A W7
W6
W5
N/A
W35
Gnd. (W28 thru W32)
Remote/Local Input
Remot Start/Stop Input
N/A
N/A
W33
W31
N/A
N/A
N/A
W29
W12
30
37
35
36
34
35
34
33
32
31
TCI
TB2
TB2
25
29
28
27
26
28
27
26
24
23
22
23
22
TB2
28
26
27
EMM INSTRUMENT BOARD
W20
W24
W26
W22
12
11
10
09
07
08
06
05
04
Gnd (W8 thru W14)
Drain Alarm #1 Input
Low Pressure Sw. Input
Heater #1 ON Input
High Pressure Sw. Input
Alarm A Com.
Compressor #1 ON Input
Alarm A N/C
Alarm A N/O
W15
W13
W14
W11
W10
W9
W8
W21
W19
Alarm B N/C
Alarm B Com.
Drain Test Output
Alarm B N/O
Drain Test Output
Compressor #1 Output
Compressor #1 Output
W27
W18
W17
W16
N/A
N/A W25
W23
FROM SHEET 01
01
03
02
00
Chassis Gnd.
TB2
X
24VAC IN
24VAC IN W3
W2
W1
X
TB2
3 X
REMOVE JUMPER IF OPTIONAL DRAIN INSTALLED
TB2
TB2
TB2
TB2
TB2
19
20
21
18
17
19
20
21
18
17
14
16
15
13
12
14
16
15
13
12
16 TB2
TB2
TB2
20
18
19
17
TB2
TB2
14
12
15 15
13
TB2
TB2
TB2
10
11
9
8
10
11
9
8
7
6
4
5
7
4
TB2
TB2
10
8
11
9
TB2
4
7
X
CONT 1 19
16
20
19
18
17
CONT 1 19
4
8
7
BLU
TB2
CONNECTOR
PE
2
1
PE
2
1
PE
BRN
RED BRN
F1
LOAD
LINE WHITE
PE
BLU
TB2
19
18
19
HPS/LPS SENSOR HARNESS
17
19
HPS
LPS
HPS
4
6
3
1
1
3
6
4
TB2
19
TB2 PE
DRAIN 2 HARNESS
X
N
20
19
7
8
5
3
2
8
7
19
20
N
X
5
3
2
DRAIN 1 HARNESS
4
24VAC
ALM
TEST
TEST
ALM
24VAC
COMPRESSOR
CONTACTOR
N
FROM SHEET 01
TB2 N
BLACK
WHITE
DB9 MALE CONNECTOR
(Mounted in Enclosure)
3
89
5
RED
4
67
2 1
-4NO -3NO
-1NC -2NC
CONT 1
A1 A2

12
WIRING DIAGRAM
Model TF 210E - 460 VAC
Sheet 1 of 2
H4
H3
H2
H1
FU2
FU3
B100-3683-5
MICRON
L1L3
H5208V
230V H5
400V H5
460V H5
FACTORY SET TO 460V
FU1
24/120 VAC SECONDARY
100VA
208/230/400/460 VAC PRIMARY
H5
COM
H3
230V
H4
208V
H2
400V
X3
X2
X1
H1
120V 24V
460V
COMPRESSOR
TO LINE 22
21
20
18
19
17
16
15
14
13
L1 L3
L2
PE
HEATER HARNESS
1L2
L3
TB2
TB2
PE
T3
T2
H1
HEATER 1
FAN 2 HARNESS
FPS 2
FAN 2
REF SHEET 02 LINE 11
REF SHEET 02 LINE 10
REF SHEET 01 LINE 20
03
10
11
12
09
08
07
06
05
04
L3
L3
L3
L2
L2
02
01
00
PE
L1
L1
L1
L2
L3
TB1 L1 L3L2
CONT 1
DISCONNECT SWITCH
PE
TB2
T1
T2
T3
T3
T2
T3
TB2
PE
T2
T3
T2
FAN 1 HARNESS
FPS 1
FAN 1
T1
T1
T1
COMPRESSOR HARNESS
43
42
40
41
39
38
37
36
35
25
32
33
34
31
30
29
28
27
26
FROM LINE 21
L3
24
23 L1
22
L3
L1
TO SHEET 02
X
TO SHEET 02
N
(4 Terminal Blocks)
TB2
XX
(4 Terminal Blocks)
TB2
NN
L3
L1
ELECTRICAL SUPPLY
480VAC/3PH/60HZ/GND
CONT 1
-1NC -2NC H2
MTR3
L3
L2
T3
T2
L1 T1
MTR2
MTR1

13
WIRING DIAGRAM
Model TF 210E - 460 VAC
Sheet 2 of 2
OPTIONAL DRAIN
Drain Alarm #2 Input
13 21
W36
W28
W37
W34
W32
W30
FMD #1 In (RJ-11)
FMD #2 In (RJ-11)
J2 RS-232
RED
BLACK
WHITE
22
21
20
19
18
17
16
15
14
W38
Evaporator Thermistor
Evaporator Thermistor
Phase B xfmr Input
Phase A xfmr Input
Phase Com. xfmr Input
W4
N/A
N/A W7
W6
W5
N/A
W35
Gnd. (W28 thru W32)
Remote/Local Input
Remot Start/Stop Input
N/A
N/A
W33
W31
N/A
N/A
N/A
W29
W12
30
37
35
36
34
35
34
33
32
31
TCI
TB2
TB2
25
29
28
27
26
28
27
26
24
23
22
23
22
TB2
28
26
27
EMM INSTRUMENT BOARD
W20
W24
W26
W22
12
11
10
09
07
08
06
05
04
Gnd (W8 thru W14)
Drain Alarm #1 Input
Low Pressure Sw. Input
Heater #1 ON Input
High Pressure Sw. Input
Alarm A Com.
Compressor #1 ON Input
Alarm A N/C
Alarm A N/O
W15
W13
W14
W11
W10
W9
W8
W21
W19
Alarm B N/C
Alarm B Com.
Drain Test Output
Alarm B N/O
Drain Test Output
Compressor #1 Output
Compressor #1 Output
W27
W18
W17
W16
N/A
N/A W25
W23
FROM SHEET 01
01
03
02
00
Chassis Gnd.
TB2
X
24VAC IN
24VAC IN W3
W2
W1
X
TB2
3 X
REMOVE JUMPER IF OPTIONAL DRAIN INSTALLED
TB2
TB2
TB2
TB2
TB2
19
20
21
18
17
19
20
21
18
17
14
16
15
13
12
14
16
15
13
12
16 TB2
TB2
TB2
20
18
19
17
TB2
TB2
14
12
15 15
13
TB2
TB2
TB2
10
11
9
8
10
11
9
8
7
6
4
5
7
4
TB2
TB2
10
8
11
9
TB2
4
7
X
CONT 1 19
16
20
19
18
17
CONT 1 19
4
8
7
BLU
TB2
CONNECTOR
PE
2
1
PE
2
1
PE
BRN
RED BRN
F1
LOAD
LINE WHITE
PE
BLU
TB2
19
18
19
HPS/LPS SENSOR HARNESS
17
19
HPS
LPS
HPS
4
6
3
1
1
3
6
4
TB2
19
TB2 PE
DRAIN 2 HARNESS
X
N
20
19
7
8
5
3
2
8
7
19
20
N
X
5
3
2
DRAIN 1 HARNESS
4
24VAC
ALM
TEST
TEST
ALM
24VAC
COMPRESSOR
CONTACTOR
N
FROM SHEET 01
TB2 N
BLACK
WHITE
DB9 MALE CONNECTOR
(Mounted in Enclosure)
3
89
5
RED
4
67
2 1
-4NO -3NO
-1NC -2NC
CONT 1
A1 A2

14
WIRING DIAGRAM
575-460/3/60 Transformer Pack

15
DIMENSIONS / WEIGHTS
NOTE: Dimensions and Weights are for reference only. Request certified drawings for construction purposes.
FRONT VIEW
BOTTOM VIEW
RIGHT SIDE VIEW
BACK VIEW
DETAIL A
A
"B"
"A"
"D"
"E" "F"
"G"
"H"
"I" "J"
"C"
Ø"K" MOUNTING HOLE
4-PLACES TYP.
"L” - I/O CONNECTIONS
2.500
CONDENSER AIR FLOW
Ø1.00 (25mm) ELECTRICAL ENTRY
Ø.750 (19mm) RS-232 ACCESS
0.25-NPT DRAIN CONNECTION
MODEL TF171E
0.25-NPT DRAIN CONNECTION
MODEL TF210E
Dimensions, inches (mm)
Model TF 171E TF 210E
A 58.06 (1475) 58.06 (1475)
B 32.15 (817) 32.15 (817)
C 2.77 (70) 2.77 (70)
D 30.15 (766) 30.15 (766)
E 39.62 (1006) 39.62 (1006)
F 41.62 (1057) 41.62 (1057)
G 20.44 (519) 20.44 (519)
H 27.79 (706) 27.79 (706)
I 49.06 (1246) 49.06 (1246)
J 44.78 (1137) 44.78 (1137)
K 0.63 (16) 0.63 (16)
L
Inlet/Outlet
Connections
2.5 MPT 2.5 MPT
Weight
lbs (kg) 691 (313) 734 (333)

16
TROUBLESHOOTING GUIDE
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
A) Water downstream of dryer 1. Residual free moisture remaining in
downstream pipelines
2. Air bypass system is open
3. Inlet and Outlet connections are reversed
4. Airlinesdownstreamofdryerareexposed
to temperatures below the dew point.
5. Excessivefreemoisture(bulkliquid)at
dryer inlet.
6. Condensate not being drained
7. Dryer overloaded resulting in elevated
dew point.
8. Refrigeration system not functioning
1. Blow out system with dry air
2. Check valve positions
3. Check for correct connection
4. Insulateorheattraceairlinesexposedto
low ambients or dry air to lower dew point
5. Install separator ahead of dryer
6. See C below
7. See C below
8. See C below
B) High pressure drop across dryer 1. Excessiveairow
2. Freezingofmoistureinevaporator
because of refrigeration system fault
3. Filter loaded with solid particulates
1. Check flow rate
2. See C below
3. Replace filter element
C) Checkpoint faults
1. Power on light off
2. Compressor on light off
3. Alarm/Service alert light on
-check Display for active
conditions
SERVICE DRYER
LOW PRESSURE
HIGH PRESSURE
NOTE: If high refrigerant pressure
occurs, switch must be manually
reset
HIGH TEMPERATURE
(also observed as high reading on
temperature indicator)
DRAIN
COMPRESSOR
HEATER
TEMP SENSOR
a. Power failure; open circuit
a. Compressor commanded off by manual
switch or programmed schedule
b. Open circuit
c. Control circuit open on high or low
pressure cutout
a. Service interval specified has elapsed
a. Hot gas bypass valve requires adjustment
b. Low on refrigerant
a. Lack of condenser cooling
Air-cooled - Ambient temperature too
high, clogged condenser fins, obstructed
flow across condenser, faulty fan motor or
fan control switch.
Water-cooled - Cooling temperature too
high, flow too low, clogged strainer, faulty
water regulating valve
a. Dryer overloaded
b. Refrigeration system off or not cooling
sufficiently
a. Drainlinerestrictedorfrozen
b. Drain mechanism faulty
a. Faulty compressor contactor.
b. FaultyN.O.auxiliarycontacton
compressor contactor.
a. Faulty compressor contactor.
b. FaultyN.C.auxiliarycontacton
compressor contactor.
a. Temperature sensor or wiring to sensor
is open (only the left-most LED in the
temperature display will be illuminated).
b. Temperature sensor or wiring to sensor is
shorted (all of the LEDs in the temperature
display will be illuminated).
a. Check for power to dryer
a. Check current command status
b. Check power to compressor
c. Check display for fault
a. Perform scheduled service
a. Contact qualified technician or
manufacturer’s service department
Check air temperature 6” in front of
condenser; Clean condenser and check
for free air flow; Check fan and switch
operation
Check cooling medium temperature and
flow, clean strainer, check valve operation
a. Check compressed air flow, temperature,
and pressure
b. Check power to unit, power to
compressor, Low or High pressure faults
Have qualified technician evaluate system
a. Open drain line
b. Turn3-wayvalvetohorizontalposition
and open petcock for manual draining.
Rebuild drain mechanism.
a. Check wiring and operation of contactor.
b. Checkwiringandoperationofauxiliary
contact.
a. Check wiring and operation of contactor.
b. Checkwiringandoperationofauxiliary
contact.
a. Replace sensor or repair wiring.
b. Replace sensor or repair wiring.
NOTE: After fault correction, press reset button to clear display

17
PARTS LIST
MAINTENANCE KITS
MODEL TF 171E TF 210E
Standard KRDKT25S KRDKT26S
With Optional Cold Coalescer KRDKT45S KRDKT46S
208-230/3/60 380-420/3/50, 460/3/60, and 575/3/60
PARTS DESCRIPTION TF 171E TF 210E TF 171E TF 210E
Condensing Unit Assembly 5002013 5002015 5002014 5002016
Compressor (Only) 5002921 3227182 5002930 3232811
Fan Motor 5002922 3233153 5002931 3228005
Fan Blade 5002923 3219406 5002923 3219406
Crankcase Heater 3223261 3223261 3223260 3223260
Condenser 5002924 3232832 5002924 3232832
Low Refrigerant Pressure Switch 3230762 3230762 3230762 3230762
High Refrigerant Pressure Switch 3230764 3230764 3230764 3230764
Fan Cutout Switch 1 3230762 3230762 3230762 3230762
Fan Cutout Switch 2 3230763 3230763 3230763 3230763
Hot Gas By-Pass Valve (Air-Cooled) 5002351 5002351 5002351 5002351
Filter Dryer (Liquid Line) 5002925 5002925 5002925 5002925
Temperature Sensor 3210926 3210926 3210926 3210926
Contactor 5002926 5002928 5002926 5002928
AuxiliaryContactor 5004254 5004254 5004254 5004254
Transformer 230/400/460 3159128 3159128 3159128 3159128
Fuse Primary 3223962 3223962 3223962 3223962
Fuse Secondary 4010495 4010495 4010495 4010495
Board, Printed Circuit (EMMII) 3227156 3227156 3227156 3227156
Digital PC Board Fuse 5002943 5002943 5002943 5002943
Power Transformer (575V) N/A N/A 3230895 3230895
575V Transformer Primary Fuse N/A N/A 3049090 3049090
575V Transformer Secondary Fuse N/A N/A 5007288 5007288
Refrigerant High Pressure Switch (H2O) 3230764 3230764 3230764 3230764
On-Off Switch 3230777 3230777 3230777 3230777
Cooling Water Regulatory Valve 3232503 3232503 3232503 3232503
Cooling Water Strainer Screen 3230672 3230672 3230672 3230672

18
NOTES

19

WARRANTY
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL IS
RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in
accordance with procedures and recommendations outlined in manufacturer’s instruction manuals, to be free from defects
in material or workmanship for a period as specified below, provided such defect is discovered and brought to the manufac-
turer’s attention within the aforesaid warranty period.
The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the
warranty period, provided such defect occurred in normal service and not as a result of misuse, abuse, neglect or accident.
Normal maintenance items requiring routine replacement are not warranted. The warranty covers parts and labor for the
warranty period unless otherwise specified. Repair or replacement shall be made at the factory or the installation site, at the
sole option of the manufacturer. Any service performed on the product by anyone other than the manufacturer must first
beauthorizedbythemanufacturer.
Unauthorizedservicevoidsthewarrantyandanyresultingchargeorsubsequentclaimwillnotbepaid.Productsrepairedor
replacedunderwarrantyshallbewarrantedfortheunexpiredportionofthewarrantyapplyingtotheoriginalproduct.
Theforegoingistheexclusiveremedyofanybuyerofthemanufacturer’sproduct.Themaximumdamagesliabilityofthe
manufacturer is the original purchase price of the product or part.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR STATUTORY,
AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A
PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT
OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAIL-
URE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN.
THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER
INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF
WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warrant any product, part, material, component, or accessory manufactured by others and sold
or supplied in connection with the sale of manufacturer’s products.
Warranty Period
Partsandlaborfortwo(2)yearsfromthedateofshipmentfromthefactory;heatexchangersarecovered(partsonly)for
an additional three (3) years (total of five [5]). On units that manufacturer requests be returned to the factory, a one time
removal/reinstallation labor allowance as noted in the Service Warranty Policies and Procedures Handbook will apply. Freight
to the factory from the installation site and to the installation site from the factory will be paid by the manufacturer; means
of transportation to be specified by manufacturer.
SERVICE DEPARTMENT: (724) 745-3038
U.S.A. • PO Box 946 • Fredericksburg, VA 22404 • Tel: 540/898-5500 • Fax: 540/898-5520 • Service: 724/745-3038
Canada • 3760 Rue La Verendrye • Boisbriand (Quebec) J7H 1R5 • Tel: 450/971-1414 • Fax: 450/971-1415 • Service: 450/971-1414
This manual suits for next models
1
Table of contents