- 12 -
•Install condensate collector in the bottom;
•To fill the gap of chimney between insert and chimney walls, at least in the
external part of the chimney with non-combustible heat insulation material. Seal
the gap on the top right with plaster and trim with tin with inclination from the
hole towards chimney edge;
•Winterize chimney in cold loft with non-combustible heat insulation material;
•If inside of the chimney gets on fire, close air supply to the boiler and call
firemen;
•In the chimney joint, in the comfortable place, make holes for periodic (once a
month) sooth cleaning;
•It is recommended to have chimney examined by qualified chimney
maintenance specialist once a year.
6.3. Connection to heating system
Requirements for connection:
•Boiler has to be connected to heating system in accordance with the project
prepared by thermal technique specialists or the works can be performed
independently by highly qualified plumber-welder, well experienced and
familiarized with boiler design and this manual;
•If in the system pipes there are installed valves, disconnecting the boiler
from heating system, they must be fully open. In order to avoid mishap due
to negligence, after opening of the valves it is advisable to remove their
handles;
•Heating system can be of open or closed type. In this case instead of
pressure expansion vessel expansion reservoir can be correctly installed;
•In order to avoid condensate formation, which may reduce service life of
the boiler significantly, install in the heating system 4-way or 3-way
automatic mixing valves, (see recommended diagrams fig. 4a - 4d), in order
to maintain no less than 60°C return water temperature;
•It is necessary to install into the system safety valve, which does not permit
exceeding 0,15 MPa (1,5 kgf/cm
2
) working pressure in the heating system.
Check valve operation every time when firing the boiler, by turning valve
handle;
•Boiler can be connected into heating system (with expansion reservoir
which is also safety valve backuping device protecting from overpressure),
with working pressure no more than 0,15 MPa (1,5 kgf/cm
2
);
•It is recommended to have boiler examined by qualified boiler maintenance
specialist once a year;
•Water discharge pipe is used to discharge water from the system and boiler
in the case there is system frosting risk.
Recommended boiler connection diagram options Fig. 4a – 4d
- 21 -
KALVIS - 2-30U, -2-40U 2012.02.06
To fill boiler with fuel:
-Open firing valve (6);
-Open door (22) and verify that ash does not block firegrate holes (21) for
air could enter hearth (27). If needed, move bottom fuel layer with poker;
-Close the door (22);
-Turn draught regulator handle1) to close primary air supply valves in the
door (23);
-Open fuel loading door (29), after 15...20 seconds (for opening time: keep
opened observing for there is no more smoke in the chamber) fully open
the door and load hearth with fuel;
-close tightly the fuel loading door and valves;
-with the means of draught regulator (28) open primary air valves (24).
We recommend to refill fuel only when the last charge has fully burned
out; refilling on non-fully burned out charge is possible only in the case
of necessity when there is no other option.
Combustion process control without measuring devices is done by
monitoring colour of the smoke going out of the chimney. If combustion
process is good, smoke is thin, grey. If smoke is thick and dark, fuel is not
fully burn, secondary air is insufficient. In such case open secondary air valves
more. secondary air volume is established depending on fuel type and fuel
moisture. Combustion quality is checked when water temperature is ≥80ºC.
It is advisable for secondary air adjustment to call a specialist with gas
analyser; this is expedient if you have large volume of good quality
homogenous fuel..
When fuel burns, ash remains, it covers firegrate; combustion intensity and
boiler efficiency drops. Due to this reason fuel has to be poked. Burning coal
is poked with poker through gaps if inner door or by moving firegrate with the
help of pedal. Large volume of generated ash prevents primary air from
entering, so ash has to be removed timely.
Avoid opening fuel loading door during intense combustion (2 and 29).
Boiler combustion needs much air, so enough volume of air has to enter
into the premises where boiler is installed.
Recommended consumed fuel moisture is no more than 15-22 %.
Note. When boiler is started to operate, during firing, on internal boiler walls,
when there is no sooth layer yet, when firewood burns, water condensate
forms, which can look like the boiler is not tight and leaks water. Water
steam condensate disappears when water temperature in the boiler raises
up to 70-80°C with the help of 4-way distributor. It is recommended to
maintain water temperature in the boiler as high as possible. If return
water temperature is less than 60°C, water steam condenses on internal
surfaces of the boiler, which combine with combustion products and form
Example