manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Kidde
  6. •
  7. Rack & Stand
  8. •
  9. Kidde KI-ABST Assembly instructions

Kidde KI-ABST Assembly instructions

© 2017 United Technologies Corporation 1 / 4 P/N 3102475-EN • REV 001 • ISS 09NOV17
KI-ABST Sounder Base
Installation Sheet
Description
The KI-ABST sounder base adds alarm signaling capability to
compatible single-function smoke detectors. See “Specifications” on
page 3 for compatible detectors.
The KI-ABST sounder base is field-configurable for a low dB or
high dB output, and for a steady or temporal signal. See Figure 1.
In temporal mode, the KI-ABST generates the required fire alarm
signal and uses a separate synchronization module and polarity
reversal relay for signal synchronization. See Figure 4.
For application and programming details, refer to the control unit
documentation.
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
Cautions
• To prevent accidentally alarming the system, disconnect the
signaling line circuit (SLC) from the control unit before connecting
this device.
• Electrical supervision requires that you break the wire run at each
terminal. Do not loop the field wires around the terminals.
• Equipment damage hazard. Printed circuit boards are not field
repairable. When configuring the sounder base, make sure you are
cutting the correct location before you make the cut.
• Equipment damage hazard. Overtightening the screw terminals
can damage the terminal and make wire connections less secure.
Tighten screws firmly, but do not overtighten.
Notes
• Always connect the base to a steady voltage, whether the output
signal on the audible detector base is set to steady or temporal.
• This device is prohibited from being installed in a dwelling unit as
defined in the National Building Code of Canada.
• For determining where to locate the sounder base, refer to the
detector installation instructions.
To install the sounder base:
1. Configure the sounder base. See Figure 1.
To select a low dB output, cut the printed circuit board at J1. For a
high dB output, leave J1 intact.
To select a steady output, cut the printed circuit board at J2. For a
temporal output, leave J2 intact.
2. Connect the field wiring to the terminals. Observe the signal
polarity of the AUX riser (plus to minus and minus to plus). See
Figure 3 and Figure 4. Do not overtighten the screws.
3. Attach the base plate to the electrical box. See Figure 5. Do not
overtighten the screws.
If you are using the AB4G-SB surface mount box, make sure to
install a reinforcing plate at each knockout used. Reinforcing plates
are included with the AB4G-SB. See Figure 2.
4. Align the trim ring so that the four tabs on the ring mate with the
four slots in the base plate, and then press the trim ring onto the
base plate until the tabs lock.
Figure 1: Output configuration
(1) High dB, Temporal
(2) Low dB, Temporal (3) High dB, Steady
(4) Low dB, Steady
Figure 2: Installing reinforcing plates on the AB4G-SB box
J1 J2
(1)
J1 J2
(2)
J1 J2
(3)
J1 J2
(4)
2 / 4 P/N 3102475-EN • REV 001 • ISS 09NOV17
Figure 3: Typical unsynchronized sounder base circuit (steady output signal)
(1) From the control unit signaling line circuit controller.
(2) From a 24 VDC auxiliary power supply that is UL/ULC Listed for
fire protective signaling systems.
(3) First KI-ABST on the AUX riser.
(4) Last KI-ABST on the AUX riser.
(5) AUX riser supervision circuit.
Figure 4: Typical synchronized sounder base circuit (temporal output signal)
(1) From a 24 VDC auxiliary power supply that is UL/ULC Listed for
fire protective signaling systems.
(2) Polarity reversal relay module. Polarity shown in the normal state.
(3) First KI-ABST on the AUX riser.
(4) Last KI-ABST on the AUX riser.
(5) AUX riser supervision circuit.
(6) From the control unit signaling line circuit controller.
(4)(3)
(5)
(2) AUX+
AUX–
SIG+
SIG–
DATA– OUT
DATA– IN
DATA+ IN/OUT
SIG+
SIG–
DATA– OUT
DATA– IN
DATA+ IN/OUT
(1) SLC+
SLC–
+
–
SLC+
SLC–
(6)
(4)(3)
SLC+
SLC–
+
–
(1) AUX+
AUX–
EG1M-RM
12
3
4
65
7
8
+
–
+
–
SLC+
SLC–
+
–
SLC+
SLC–
SIG+
SIG–
DATA– OUT
DATA– IN
DATA+ IN/OUT
SIG+
SIG–
DATA– OUT
DATA– IN
DATA+ IN/OUT
(2)
(5)
P/N 3102475-EN • REV 001 • ISS 09NOV17 3 / 4
Figure 5: Mounting diagram
Maintenance and testing
Caution: Equipment damage hazard. To maintain the required agency
listings, do not change factory-applied finishes.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for a replacement.
Perform a visual and operational inspection in accordance with
applicable codes and standards or as directed by the local authority
having jurisdiction.
Specifications
Operating voltage 24 VDC or 24 VFWR, nominal
Current
Operating
Supervisory
See Table 1
DC = 1.46 mA, FWR = 2.15 mA
Default settings
Output level
Output signal
High dBA
Temporal
Sound level output
ULC
UL
See Table 2
See Table 3
Resonant frequency 3.2 kHz
A
udible directional
characteristics
See Table 4
Temporal pattern 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s
on, 1.5 s off, repeat cycle
Compatible detectors All KI and KIR Series detectors
Compatible electrical
boxes
AB4G-SB surface box for audible base;
4 in. square × 2-1/2 in. (64 mm) deep box;
3-1/2 in. octagonal × 2-1/2 in. (64 mm) deep
box; Standard European 100 mm² box
Wire size 12 to 18 AWG (1.0 to 4.0 mm²)
Sizes 16 and 18 AWG (1.0 and 1.5 mm²) are
preferred
Screw torque
Base mounting
Terminal
18 Ibf-in (2.0 N·m) max.
12 Ibf-in (1.4 N·m) max.
Base diameter 6.8 in. (173 mm)
Base height from box 0.8 in. (21 mm)
Maximum distance
from ceiling (wall
mount)
12 in. (305 mm)
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature −4 to 140°F (−20 to 60°C)
Table 1: Operating current in mA (RMS)
Voltage Low dBA High dBA
16 VDC 17 28
24 VDC 24 41
33 VDC 31 52
16 VFWR 41 48
24 VFWR 51 60
33 VFWR 60 66
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Table 2: Sound pressure level per CAN/ULC-S525
Voltage High dBA Low dBA
Reg. 24 VDC 93 89
Reg. 24 VFWR 96 92
Table 3: Sound level output (dBA)
Signal Voltage Low dBA High dBA
Reverberant room per UL 464 [1]
Steady 16 VDC 75.5 81.7
24 VDC 79.5 84.5
33 VDC 81.8 86.5
Reverberant room per UL 268 and FM [1]
Steady 16 VDC 81.5 87.7
24 VDC 85.5 90.5
33 VDC 87.8 92.5
[1] For UL 464 and UL 268 applications, low dBA settings are for
private mode only
Table 4: Audible directional characteristics [1]
Angle (degrees) Change in output sound pressure level
90 (ref) 0 dBA
75 and 105 −3 dBA
65 and 110 −6 dBA
[1] Measured in a ULC anechoic room. Horizontal and vertical axes
reflect the same pattern.
4 / 4 P/N 3102475-EN • REV 001 • ISS 09NOV17
Regulatory information
UL ratings Regulated 24 DC, Regulated 24 FWR
ULC ratings 20 to 31 VDC or 20 to 31 VFWR
Environmental class Indoor, dry
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause
harmful interference, and (2) this device must
accept any interference received, including
interference that may cause undesired
operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.kiddelifesafety.com

Other Kidde Rack & Stand manuals

Kidde SMK23R Assembly instructions

Kidde

Kidde SMK23R Assembly instructions

Kidde SMK23 Assembly instructions

Kidde

Kidde SMK23 Assembly instructions

Kidde SMK23RU Assembly instructions

Kidde

Kidde SMK23RU Assembly instructions

Popular Rack & Stand manuals by other brands

BlueHive 035-7330-0 user manual

BlueHive

BlueHive 035-7330-0 user manual

Kogan OSTIA Series user guide

Kogan

Kogan OSTIA Series user guide

Kargo Master 42000 Instruction guide

Kargo Master

Kargo Master 42000 Instruction guide

MW MOUNTS Large Ceiling Mount instruction manual

MW MOUNTS

MW MOUNTS Large Ceiling Mount instruction manual

ricoo S3511 quick start guide

ricoo

ricoo S3511 quick start guide

CHIEF MSP-BBSP installation instructions

CHIEF

CHIEF MSP-BBSP installation instructions

SilverStone TM01 user manual

SilverStone

SilverStone TM01 user manual

Perlesmith PSLF2 Installation instruction

Perlesmith

Perlesmith PSLF2 Installation instruction

Premier Mounts PSD-TL installation instructions

Premier Mounts

Premier Mounts PSD-TL installation instructions

Soundoff Signal ETSSLFVBK10 Installation

Soundoff Signal

Soundoff Signal ETSSLFVBK10 Installation

Tormach PCNC 440 installation guide

Tormach

Tormach PCNC 440 installation guide

ricoo FS304 Assembly instructions

ricoo

ricoo FS304 Assembly instructions

ATD Tools ATD-7479 manual

ATD Tools

ATD Tools ATD-7479 manual

Mustang MPT-X116A instruction manual

Mustang

Mustang MPT-X116A instruction manual

Swagman 64663 instruction sheet

Swagman

Swagman 64663 instruction sheet

NEC ST-4020 installation instructions

NEC

NEC ST-4020 installation instructions

Wali 1342LM Accessory Installation Manual

Wali

Wali 1342LM Accessory Installation Manual

Tech Craft SF50 Assembly manual

Tech Craft

Tech Craft SF50 Assembly manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.