Kieback&Peter Z45FK Technical specifications

Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, [email protected]
2.90-20.060-01-EN | 2022-10-05
Z45FK, Z46FK, Z47FK, Z60FK
Product Description L
Z45FK, Z46FK, Z47FK, Z60FK Coupling Relays
Application
These coupling relays are used to control plant components in the DDC
system. They serve as switching coupling components between the DDC
switching outputs and the device inputs; they can be used to control valve
actuators, pumps, burners or fans, for example.
These coupling relays are fitted with spring terminals which make it
possible to connect wires quickly and easily. It is not necessary to use a
tool to connect solid wires and litz wires with conductor end sleeves; an
ordinary screwdriver is sufficient to connect litz wires without conductor
end sleeves.
Connected wires can be quickly disconnected again with a screwdriver.
Terminal slots provided for the A1 and A2 connections enable the simple
and quick connection of up to 10 analog encoders or coupling relays
through connecting bridges (Z43).
Content Page
Important Information on Product Safety ...............................................................................................................2
Item........................................................................................................................................................................3
Technical data .....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................3
Dimensions ..........................................................................................................................................................4
Connection...........................................................................................................................................................4
Mounting and Installation.......................................................................................................................................5
Cable connection .................................................................................................................................................6
Connection example with input-output modules ....................................................................................................8

Product Description
Z45FK, Z46FK, Z47FK, Z60FK
L
Page 2 / 8
2.90-20.060-01-EN | 2022-10-05
Important Information on Product Safety
Safety instructions
This document contains information on installing and commissioning the product “Z45FK, Z46FK,
Z47FK, Z60FK”. Each person who carries out work on this product must have read and understood
this document. If you have any questions that are not resolved by this document, you can obtain
further information from the supplier or manufacturer.
If the product is not used in accordance with this document, the protection provided could be
impaired.
The applicable regulations must be observed when installing and using the devices. Within the EU,
these include regulations regarding occupational safety and accident prevention as well as those
from the VDE (German Association for Electrical, Electronic & Information Technologies). If the
device is used outside of the EU, it is the responsibility of the plant engineer or operator to comply
with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers based on their technical training, knowledge
and experience, as well as their knowledge of the applicable regulations.
Symbol meanings
WARNING
Indicates a hazard of medium risk which can result in death or serious bodily injury if not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if not avoided.
!CAUTION
Indicates a hazard which can result in material damage or malfunctions if not avoided.
NOTE
Indicates additional information that can simplify working with the product.
Notes on disposal
In accordance with the applicable laws and directives of the European Union countries, the product
should not be disposed of with household waste. This ensures environmental protection and
sustainable recycling or raw materials.
Commercial users should contact their supplier and observe the conditions of the purchase
agreement. This device may not be disposed of together with other commercial waste.
The local and currently applicable laws must be observed.

Z45FK, Z46FK, Z47FK, Z60FK
Product Description L
Page 3 / 8 2.90-20.060-01-EN | 2022-10-05
Item
Technical data
Accessories (not included in delivery)
Z45FK Coupling relay with one changeover switch
Z46FK Coupling relay with two changeover switches
Z47FK Coupling relay with one changeover switch und a manual switch at field level
Z60FK Coupling relay with one changeover switch und a manual switch at field level with a
potential-free feedback contact
Nominal voltage Z45FK/Z47FK/Z60FK AC/DC 24 V ±10%, 13 mA
Z46FK AC/DC 24 V ±10%, 20 mA
Output contact Z45FK/Z47FK/Z60FK 1 changeover switch, max. AC 250 V, 6 A,
1500 VA
Z46FK 2 changeover switches, each with max. AC
230 V, 0.25 A, 60 VA
Feedback contact Z60FK Max. AC/DC 24 V; 50 mA
Electrical service life Z45FK, Z47FK, Z60FK 200,000 switching cycles
Z46FK 2,000,000 switching cycles
Display LED operating display
Manual switch Z45FK/Z46FK None
Z47FK Manual switch at field level
Z60FK Manual switch at field level with a poten-
tial-free feedback contact
Connection Solid wire 0.08 .. 2.5 mm²
Litz wire without
conductor end sleeve
0.08 .. 2.5 mm²
Litz wire with conduc-
tor end sleeve
0.5 .. 1.5 mm²
Overvoltage category III
Rated impulse voltage 4000 V
Level of contamination 2
Automatic action Type 1
Degree of protection Housing IP20
Insulation in accordance with
VDE 0110
Z45FK, Z47FK, Z60FK Rated voltage 250 V
Z46FK Rated voltage 230 V
Ambient temperature -20 .. +55 °C
Weight 43 g
Mounting Control panel installation on standard top-hat rail TH 35-7.5; can be
snapped open without there having to be free space to the left/right;
installation position can be chosen freely
Z43 Connecting bridge for connecting up to 10 analog encoders or coupling relays using termi-
nal slots for the “A1” and “A2” connections (power). Maximum 2 A total current.

Product Description
Z45FK, Z46FK, Z47FK, Z60FK
L
Page 4 / 8
2.90-20.060-01-EN | 2022-10-05
Dimensions
Connection
ZxxFK
Z43
250 V AC
6 A
1500 VA
11
A1
14
12
GN
A2
Z45FK
14 2412 22
11
A1
21
230 VAC
0,25 A
60 VA
GN
A2
Z46FK
A1
A3
0
ON
A3
AUTO
OFF 11
A1
12
14
250 V AC
6 A
1500 VA
GN
A2
Z47FK
A1
A2
12
14
11
A1
A1
A3
0
A3
B1
B2
GN
ON
AUTO
OFF
Z60FK
250 V AC
6 A
1500 VA
A1

Z45FK, Z46FK, Z47FK, Z60FK
Product Description L
Page 5 / 8 2.90-20.060-01-EN | 2022-10-05
Mounting and Installation
WARNING
Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.
Comply with VDE guidelines and local wiring regulations when mounting/removing.
Control cabinet installation on TH 35-7.5 top-hat rail can be snapped open with no need for free
space to the left/right. Installation position can be chosen freely.

Product Description
Z45FK, Z46FK, Z47FK, Z60FK
L
Page 6 / 8
2.90-20.060-01-EN | 2022-10-05
Cable connection
■ Disconnect unit from power supply.
■ Strip the insulation from 10 mm of the wire. Cross-sectional area of
connection:
Solid wire 0.08 .. 2.5 mm²
Litz wire without conductor end sleeve 0.08 .. 2.5 mm² Litz wire with conductor
end sleeve 0.5 .. 1.5 mm²
Solid wires and litz wires with conductor end sleeves can be inserted into the
spring terminals (1) directly. Insert the wire straight and press it in until the wire
will not go any further and it clicks into place in the spring terminal.
In the case of litz wires without conductor end sleeves, the spring terminal must
be opened using a slotted screwdriver. Insert the screwdriver into the test
socket (2) under the contact in order to open it, insert the litz wire straight, and
then remove the screwdriver.
■"Terminal slot (3) for Z43 connecting bridge.
■"Device connection - see wiring diagram.
Removing a Wire
Insert a slotted screwdriver (max. blade width 3 mm) into the
test socket (2) under the contact to open the spring
terminal (1), then remove the wire.
Removing the Module from the Standard Rail
Gently press in the spring under the module with a slotted
screwdriver and remove the module upward.
1
3
2

Z45FK, Z46FK, Z47FK, Z60FK
Product Description L
Page 7 / 8 2.90-20.060-01-EN | 2022-10-05
Z43 connecting bridge
The Z43 connecting bridge (not included in the delivery) can be used to connect up to 10 analog
encoders or coupling relays (max. 2 A total current).
Use a side-cutting pliers to cut off the required number of contacts at the corresponding notch that
indicates the proper place to make the cut. Then insert the connecting bridge (Z43) from the top or
from the bottom into the contact slot and press it down.
WARNING
Contact with live components of the building’s electrical system can cause death due to electric
shock.
- The ends of the connecting bridge are live during operation.
- The connecting bridge must be placed so that it cannot be touched (i.e. in the center).
Switch position for Z47FK and Z60FK
Coupling relay Z60FK also has a feedback contact for the “Auto” message (switch position A3,
B1/B2 closed).
Z43 connecting bridge
ON, OFF and AUTO

Product Description
Z45FK, Z46FK, Z47FK, Z60FK
L
Page 8 / 8
2.90-20.060-01-EN | 2022-10-05
Connection example with input-output modules
!CAUTION
Previously, the binary outputs of the GND were switched in our devices.
The implemented new device concept provides that the +24V DC are switched at the output
terminals.
In secondary earthed systems (PELV), this prevents any unwanted connection to ground or the
reference potential and prevents an active signal from being generated at the input/output module.
■Connection example BMD3216 new device concept
■Connection example BMD4032 old device concept
Z47
Z47
A1
A3
0
ON
A3
AUTO
OFF 11
A1
12
14
250 V AC
6 A
1500 VA
GN
A2
Z47FK
A1
A1
A3
0
ON
A3
AUTO
OFF 11
A1
12
14
250 V AC
6 A
1500 VA
GN
A2
Z47FK
A1