BMA0600
Product description J
BMA0600 Input module
Application
The input module with 6 analog inputs receives analog signals in
the DDC4000e automation system.
LED displays for the operating states of the inputs.
Communication is controlled via LED.
Label carrier for system-specific description.
The power supply and the CAN bus are electrically isolated.
Data is transferred between the automation station and the input
module via the CAN bus.
The input module can be connected to an existing switch cabinet
bus or field bus.
Content Page
Important Information on Product Safety ...............................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Dimensions ..........................................................................................................................................................5
Connection...........................................................................................................................................................5
Installation..............................................................................................................................................................7
Mounting ................................................................................................................................................................8
Removal.................................................................................................................................................................8
Function and Operation .........................................................................................................................................9
Commissioning ....................................................................................................................................................10
LED displays......................................................................................................................................................11

Product description
BMA0600
J
Page 2 / 12
2.60-80.600-01-EN | 2020-08-03
Important Information on Product Safety
Safety instructions
This document contains information on installing and commissioning the product “BMA0600”. Each
person who carries out work on this product must have read and understood this document. If you
have any questions that are not resolved by this document, you can obtain further information from
the supplier or manufacturer.
If the product is not used in accordance with this document, the protection provided could be
impaired.
The applicable regulations must be observed when installing and using the devices. Within the EU,
these include regulations regarding occupational safety and accident prevention as well as those
from the VDE (German Association for Electrical, Electronic & Information Technologies). If the
device is used outside of the EU, it is the responsibility of the plant engineer or operator to comply
with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers based on their technical training, knowledge
and experience, as well as their knowledge of the applicable regulations.
Symbol meanings
WARNING
Indicates a hazard of medium risk which can result in death or serious bodily injury if not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if not avoided.
!CAUTION
Indicates a hazard which can result in material damage or malfunctions if not avoided.
NOTE
Indicates additional information that can simplify working with the product.
Notes on disposal
In accordance with the applicable laws and directives of the European Union countries, the product
should not be disposed of with household waste. This ensures environmental protection and
sustainable recycling or raw materials.
Commercial users should contact their supplier and observe the conditions of the purchase
agreement. This device may not be disposed of together with other commercial waste.
The local and currently applicable laws must be observed.

BMA0600
Product description J
Page 3 / 12 2.60-80.600-01-EN | 2020-08-03
Item
Technical Data
BMA0600 Input module with 6 analog inputs
Nominal voltage 12..24 V DC ± 10 %; 2.5 W
Inputs and outputs ■6 analog inputs, See chapter “Sensor Types”, page 4.
■separate auxiliary power (terminal 53, 56) 10 V DC; 70 mA
for connecting external setpoint generators
■Support terminal blocks terminal “81” to “86” and terminal “91” to “96”
max. load 230 V AC; 6 A (3 A)
Indicators and
controls
■6 status LEDs of inputs
■6 freely parameterizable LEDs
■1 LED for displaying bus communication
See chapter “LED displays”, page 11.
Address switch Two rotary switches for addressing from 01..63
Interfaces CAN bus as:
■Fieldbus, F-bus: 2000 m, 20 kBaud or
■Switch cabinet bus, SBM bus: 200 m, 40 kBaud (note special CAN BUS
settings. Further information can be found in the DDC4000 project
planning documentation)
Housing Plastic housing
Overvoltage category III
Rated impulse voltage 800 V
Level of contamination 2
Method of operation Type 1
Degree of protection IP20
Ambient temperature 0..55 °C
Ambient humidity 20..80 % r.h., non-condensing
Mounting TH 35x7.5 top hat rail in closed housing. This device is intended for
installation in a wall-mounted enclosure or switch cabinet with protection
class I or II.
Weight 0.141 kg
Dimensions WxHxD: 71.8 x 90 x 60 mm

Product description
BMA0600
J
Page 4 / 12
2.60-80.600-01-EN | 2020-08-03
Connection terminal
■Spring-loaded terminals, printers
■All terminals can be inserted with conductor end sleeves of 10 mm length
■Twisting two conductors is not permitted, twin wire-end ferrules can be used
Sensor Types
Input terminals
Terminal 21..32
and 51..56
Support terminals
Terminal 81..86
and 91..96
Bus terminals
Terminal 17..20
Stripping length 8..9 mm 10 mm 10 mm
Conductor cross
section Solid con-
ductor
0.2..1.5 mm20.08..1.5 mm20.2..1.5 mm2
Conductor cross
section
Fine-stranded con-
ductor
0.25..1.5 mm20.08..1.5 mm20.25..1.5 mm2
Conductor cross
section
Fine-stranded con-
ductor with ferrule
0.25..0.75 mm20.8..1.5 mm20.25..0.75 mm2
Recommended
crimp
square
hexagonal
square
hexagonal
square
hexagonal
Sensor type Measuring range
0(2) V..10 V 0..100 %
KP10 -50..+150 °C
KP250 -50..+150 °C
ML2 -50..+150 °C
Ni100 -50..+150 °C
Ni1000 (DIN) -50..+150 °C
Ni1000 (L&G) -50..+150 °C
NTC1,8K -50..+150 °C
NTC5K -50..+150 °C
NTC10K -40..+150 °C
NTC10KPRE -40..+150 °C
NTC20K -30..+150 °C
PT100 -100..+850 °C
PT1000 -100..+850 °C
Balco500 -40..+150 °C
Satchwell DC1100 -20..+120 °C
Satchwell DC1400 -40..+120 °C
Resistor (potentiometer) 0..500 k

BMA0600
Product description J
Page 5 / 12 2.60-80.600-01-EN | 2020-08-03
NOTE
You can find more information on the sensor types in the “Temperature Sensor Tables” product
description (1.10-90.100-01).
Dimensions
Connection
NOTE
The devices have galvanic isolation between the bus voltage supply and the input. This is a
separation of duties that prevents unwanted ground loops.
Thanks to this functional separation, each module can provide its own ground plane that structurally
prevents mass loops and potential shifts between the modules.
If the system layout requires it, however, the ground planes of the modules can also be connected
without any issues.
- Two support terminal blocks for terminals “81” to “86” and terminals “91” to “96”
44,7
0,09
60,0
71,8
19 2017 18
19 2017 18
83
82
81 86
85
84 93
92
91 96
95
94
CAN
12.. 24V=
Can +
Can –
0V
27 28
25 26
23 24
21 22
AI6AI5AI4AI3
GND GND GND GND
6(3) A 230V~
6(3) A 230V~
GND GND
32
31
53
52
51
GND
AI1
+10V
56
55
54
GND
AI2
+10V
AI1.. AI2 70 mA

Product description
BMA0600
J
Page 6 / 12
2.60-80.600-01-EN | 2020-08-03
DDC4000e connection
Sensor connection
- Connection of several input/output modules via CAN bus
NOTE
The terminal block terminal “17” through terminal “20” (feed-through terminals) can be inserted and
disconnected without interruption.
17 18 19 20
0V
12..24V=
CAN +
CAN -
19
18
DDC4000e
20
12..24V=
-
+
39
38
DDC4000e
40
BMA0600
CAN 1
CAN 2
AI1..AI6
24V
24V
0V
24V
0V A
0..10VDC
KP10
-
NTC 500k
+
AI1..AI6
24V
24V
0V
24V
0V A
0..10VDC
0V
AI1..AI6
+10V
AI1..AI2
AI1..AI6
GND
GND
GND
-
GND
GND
PTC
0..10VDC
0..10VDC
17 18
18
17 19 20
20
19
BMA0600
17 18
18
17 19 20
20
19
BMA0600
17 18
18
17 19 20
20
19
BMD1204
12..24V=
0V
Can+
Can-
01 02 03

BMA0600
Product description J
Page 7 / 12 2.60-80.600-01-EN | 2020-08-03
Installation
!CAUTION
This product description contains the specific settings and functions of the input module. In addition
to these instructions, the product descriptions of other system components, such as the automation
station, are to be observed.
!CAUTION
Switching on the power supply of unparameterized products can lead to unforeseen consequences
such as malfunctions or material damage.
Switch on the power only after the device has been configured by the commissioning technician.
NOTE
The input module can be connected to an existing field bus or switch cabinet bus.
Further information can be found in the DDC4000 project planning documentation.
Switch cabinet bus
When connecting the switch cabinet bus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two
leads stranded into a pair, plastic insulation and an electrostatic shield with a lead diameter of at least
0.8 mm. Use a stranded pair of leads for the data lines (+ and -) and another free lead for the
ground (0).
At the end of the switch cabinet bus (farthest point from the DDC controller), install a terminating
resistor of about 180 ohms between both data lines (+ and -). The terminating resistor is included with
the DDC controller
The maximum cable length for the switch cabinet bus is 200 m.
Fieldbus
When connecting the fieldbus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two wires,
twisted to a pair with plastic insulation and an electrostatic shield with a wire diameter of at least
0.8 mm. Use a stranded pair of wires for the data lines (+ and -) and another free wire for the ground
connection (0).
At the end of the fieldbus (furthest point from the DDC controller), install a terminating resistor of
about 180 ohms between both data lines (+ and -). The terminating resistor is included with the DDC
controller.
The maximum cable length for the Fieldbus is 2000 m.

Product description
BMA0600
J
Page 8 / 12
2.60-80.600-01-EN | 2020-08-03
Mounting
WARNING
Contact with live parts of electrical domestic installation can cause death due to electric shock.
Mounting/removal may only be carried out when power is switched off.
Removal
TH 35-7.5
1 2 3 4
1 2 3 4
5 6 7

BMA0600
Product description J
Page 9 / 12 2.60-80.600-01-EN | 2020-08-03
Function and Operation
Parameterization
The following functions are defined via parameterization:
- Analog inputs can be configured according to the sensor type table
NOTE
Parameterization is retained in the event of a power failure.
Set address 99 to delete the parameterization.
Setting CAN Bus Address
Permitted range for the switch cabinet bus address: 01..63.
Permitted range for fieldbus address: 01..63.
►Set the first number of the bus address on the address switch, the second
number on the second rotary address switch.
The example shows the address 15.
(1) Combi LED (green, red) CAN bus
(2) Address switch
(3) Status LEDs of inputs
(4) freely parameterizable LEDs
12
4
3
01
2
3
4
5
6
7
8
9
01
2
3
4
5
6
x 10 x 1

Product description
BMA0600
J
Page 10 / 12
2.60-80.600-01-EN | 2020-08-03
NOTE
In the delivery state, the address is set to “00”, meaning:
- no bus communication
- no parameterization possible
- sensor inputs in test mode
Commissioning
!CAUTION
Commissioning by switching on the supply voltage may occur only after the commissioning
technician/engineer has finished configuring the DDC and has set the bus address.
■Parameterization is described in the project planning documentation for the automation station.
■Before switching on the supply voltage, check the electric installation and the device connections.
■After configuring the device and switching on the supply voltage, check the functions of the module
and the connected inputs.
Functional test
It is possible to check the correct wiring and function of the inputs.
►Set the bus address “00”.
■The correct polarity and wiring of the 8 inputs AI1 to AI6 can be checked with a diode and a resistor
180 (series connection).
Target display:
- Open contact: Red LED
- Resistance diode combination correctly poled: Green LED
Possible wiring errors:
- Open contact: Green LED
- Resistance diode combination connection: Red LED

BMA0600
Product description J
Page 11 / 12 2.60-80.600-01-EN | 2020-08-03
LED displays
LED CAN Bus
Status LED of the inputs
- Sensor value valid: LED lights up green
- Sensor value outside the measuring range: LED lights up red
- No sensor (sensor type) configured: LED off
- Negative voltage at the input falsifies the measuring signal: all input LEDs light up red.
The affected input flashes red.
- The +10 V DC auxiliary voltage breaks down. Caused by incorrect wiring:
LEDs of the 0/2..10 V DC inputs lights up red.
LED status (combination
LED)
Meaning Cause
off Module not in operation No operating voltage or operating
voltage too low
Yellow on (green LED and red
LED on)
Module in operation, but
there is a bus error
no CAN communication
possible, module not
logged on
Bus line short circuit (with respect to
ground or each other),
Bus lines reversed or
interrupted
Address 00 (manual oper-
ation effective, functional
test possible)
Yellow flashing (green LED and
red LED flashing simultane-
ously)
Flashing rate 1 sec.
Address error, no bus
activity
Outside of address range #01..#63
address assigned multiple times
Green flashes and red LED off Module OK, bus activity
Red LED and green LED flash
alternately slowly
Flashing rate 6 sec.
Update is being trans-
ferred from DDC4000e to
module
Red LED permanent light Address 99 (deleting the
configuration, manual con-
trol effective)

Product description
BMA0600
J
Page 12 / 12
2.60-80.600-01-EN | 2020-08-03
Table of contents
Other Kieback&Peter Relay manuals
Popular Relay manuals by other brands

Westinghouse
Westinghouse KRD-4 Installation, operation, & maintenance instruction

iO HVAC Controls
iO HVAC Controls iO-WR Installation & operation manual

Pilz
Pilz PNOZ X1 operating instructions

Honeywell
Honeywell 7800 SERIES installation instructions

Victron energy
Victron energy BP48|100 Installation

ABB
ABB C6701 instructions

Leuze electronic
Leuze electronic MSI-SR-LC31AR Series Original operating instructions

Pilz
Pilz PNOZ s30 operating manual

ABB
ABB Relion 615 series Operation manual

Grenton
Grenton WRE-222-W-01 user manual

BIG TREE TECH
BIG TREE TECH Relay V1.2 Operating instruction

HANYOUNG NUX
HANYOUNG NUX HSR-SL Series instruction manual