Kieback&Peter TQF10 Instruction manual

Technical data sheet 1.10-51.010-01-en
Device Description TQF10, TQF12, TQF14, TQF16 Room Service Module
TQF10, TQF12, TQF14, TQF16
Room Service Module
The Room Service Modules TQF10, TQF12, TQF14,
TQF16 and the technolon®Single Room Control
FBR100-L form a device unit in the LON network.
They are designed to record room temperatures in
living and business premises.
The room setpoint is set with the setpoint adjustor.
The TQF12 Room Service Module additionally also
has a user button for the switchover to day /night.
The TQF14 Room Service Module additionally also
has a user button for switching to three ventilator
levels.
The TQF16 Room Service Module like the TQF12
additionally also has a user button for switching to
three ventilator levels.
Contents Notes on the device description Page 2
Safety Instructions Page 2
Qualified specialists Page 2
Application Page 3
Types Page 3
Technical data Page 4
Assembly Page 5
Installation Page 6
Kieback & Peter GmbH & Co KG
Tempelhofer Weg 50, D-12347 Berlin
Telephone +49 (0) 30 / 600 95-0
Telefax +49 (0) 30 / 600 95 164
http://www.kieback-peter.de
Contents sub
j
ect to chan
g
e
Issue date: 04/20/2004
Technology for building automation

Technical data sheet 1.10-51.010-01-en
TQF10, TQF12, TQF14, TQF16 Room Service Module Device Description
Notes on the device description
The description contains references for the deployment and assembly of the Room Service Modules
TQF10, TQF12, TQF14 and TQF16.
In case of questions which cannot be clarified with this device description, please refer to the supplier or
manufacturer for further information.
The indicated installation instructions/regulations are valid in the Federal Republic of Germany.
When utilizing the devices in other countries, the builder or operator of the plant is responsible for the observation
of the respective national regulations.
The operating staff is to be instructed in accordance with the description of the technical data sheet.
Safety Instructions
The currently valid worker’s occupational health regulations and regulations for the prevention of industrial
accidents must be observed when assembling and using the devices.
Any work concerning the assembly, installation or initial operation of the devices shall be exclusively carried out
by qualified specialists, see section “Qualified specialists”.
Every person utilizing the devices shall have read and understood the descriptions in the technical data sheet.
Meaning of the symbols in the technical data sheet:
General warning, strictly observe this notice
Warning
Further notice to observe
Note
means danger of bodily injuries or material damage in case of non-observance.
Warning
indicates an information which is particularly stressed.
Note
Qualified specialists
Qualified specialists for the purposes set out in this technical data sheet are persons who are familiar with the described
devices and possess a qualification for their respective occupation.
These are for instance:
•Authorization to connect the devices according to the VDE rules and local Electricity Board regulations, as
well as the authorization to switch the devices on and off taking the in-house regulations into account.
•Knowledge of the regulations for prevention of accidents.
•Knowledge of the utilization of the devices within the plant system.
•etc.
Page 2 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
Device Description TQF10, TQF12, TQF14, TQF16 Room Service Module
Application
TQF10 TQF12
TQF16
The Room Service Modules TQF10, TQF12, TQF14 and
TQF16 are employed with the technolon®Single room
control FBR100-L.
®
At every technolon Single room control FBR100-L a Room
Service Module TQF10, TQF12, TQF14 or TQF16 can be
connected.
Types
TQF10 Room Service Module with a room
temperature sensor and the manual
adjustment of the room setpoint
TQF12 Room Service Module with a room
temperature sensor and the manual
adjustment of the room setpoint with
user button for switchover to day/night
TQF14 Room Service Module with a room
temperature sensor and the manual
adjustment of the room setpoint with user
button for the switching of three ventilator
speeds
TQF14
TQF16 Room Service Module with a room
temperature sensor and the manual
adjustment of the room setpoint
with operating key for switchover to day/night
as well as the switching of three ventilator
speeds
Page 3 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
TQF10, TQF12, TQF14, TQF16 Room Service Module Device Description
Technical data
Measured variable Room temperature in residential and office space
Measuring system Active measuring system KP10, 2.73 V at 0°C, TC 10 mV/C
Set value adjuster digital, regulating knob with trend arrow
Measuring range 0..45°C
Control buttons TQF12 Key Switchover to day operation, automatic for blower
Key Switchover to night or lowering operation,
as well as automatic for ventilator
TQF14 Keys,
setting of the ventilator speeds off, level 1, level 2, level 3
Key Switchover to day operation, automatic for blowerTQF16
Key Switchover to night or lowering operation,
as well as automatic for ventilator
Keys,
setting of the ventilator speeds off, level 1, level 2, level 3
Backlighting of the keys depending on the configuration:
Steady burning light, on for 5 sec after keystroke or backlighting off
Housing Hood, color RAL9010 (pure white)
Ambient conditions Temperature 0..45°C,
Humidity Non-condensing
QB interface 4-conductor, for the connection of a technolon®Single room control FBR100-L,
line length max. 200m
IP30Degree of enclosure
protection
Dimensions Width x height x depth: 82.5 x 82.5 x 30 mm
Assembly Wall mounted/assembly in flush-mounted box
Weight 110 g
Page 4 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
Device Description TQF10, TQF12, TQF14, TQF16 Room Service Module
Assembly
The assembly may only be carried out by qualified personnel on voltage-free switched
connecting leads .
Warning The Room Service Modules TQF10, TQF12 and TQF16 can be assembled on the wall or in a flush-
mounted box.
For rapid and correct measurement of the room temperature, the Room Service Module is to be assembled in such
a way that the airflow of the room is included.
Airflow
1.5 m
correct false
Assembly
Page 5 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
TQF10, TQF12, TQF14, TQF16 Room Service Module Device Description
For surface-mounted or flush-mounted wiring, the hood and base have labeled housing parts that can be broken
out depending on the cable leads.
Furthermore, pluggable hood inserts are a part of the delivery which can be exchanged for the standard
inserts :
Note
C1/D1 Inserts without air vents for greater wall influence.
D2 Inserts for cable inlet from below.
C1
D1
The device protection type IP30 is only guaranteed when the air
gap at the cable inlet is ≤2.5 millimeters.
D2
Installation
The electrical installation and the Room Module connection may only be carried out by qualified
personnel.
Warning This must be done in accordance with the VDE regulations and local specifications.
Connection
12
32 2931 30
27
01PK
CDV0
ataD
klC
DV21 C
TQF10
12
32 2931 3027
01PK
CDV0
ataD
klC
DV21 C
TQF12
12
32 2931 30
27
01PK
CDV0
ataD
klC
DV21 C
TQF14
12
32 29
31 30
27
01PK
CDV0
ataD
klC
DV21 C
TQF16
Page 6 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
Device Description TQF10, TQF12, TQF14, TQF16 Room Service Module
Page 7 / 8
Technology for building automation

Technical data sheet 1.10-51.010-01-en
TQF10, TQF12, TQF14, TQF16 Room Service Module Device Description
Page 8 / 8
Technology for building automation
This manual suits for next models
3
Table of contents
Popular Thermostat manuals by other brands

Plugwise
Plugwise Lisa 158-01 installation manual

Honeywell
Honeywell DTC 100/2 User manual instructions for installation and maintenance

Chromalox
Chromalox PK405-18 Installation Instructions and RENEWAL PARTS IDENTIFICATION

Daikin
Daikin ESFV06A6 installation manual

Hunter
Hunter 44760 owner's manual

International comfort products
International comfort products TSTAT0712 owner's manual